OMRON MY4N

General-purpose Relay
MY New model
Versatile and Function-filled Miniature Power
Relay for Sequence Control and Power
Switching Applications
• Models with lockable test buttons now available.
• Many variations possible through a selection of operation indicators (mechanical and LED indicators), lockable test button,
built-in diode and CR (surge suppression), bifurcated contacts,
etc.
• Arc barrier standard on 4-pole Relays.
• Dielectric strength: 2,000 VAC (coil to contact)
• Environment-friendly cadmium-free contacts.
• Safety standard approvals obtained.
• Wide range of Sockets (PY, PYF Series) and optional parts are
available.
• Max. Switching Current: 2-pole: 10 A, 4-pole: 5 A
• Provided with nameplate.
LR
Ordering Information
■ Relays
Standard Coil Polarity
Type
Contact form
Plug-in socket/Solder terminals
Standard with LED indicator
Standard
With built-in diode
(DC only)
With built-in CR
(220/240 VAC, 110/120 VAC
only)
Without LED indicator
With LED indicator and
lockable test button
DPDT
MY2N
MY2IN
4PDT
MY4N
MY4IN
MY2
MY4
4PDT (bifurcated)
MY4ZN
MY4ZIN
MY4Z
DPDT
MY2N-D2
MY2IN-D2
---
4PDT
MY4N-D2
MY4IN-D2
---
4PDT (bifurcated)
MY4ZN-D2
MY4ZIN-D2
---
DPDT
MY2N-CR
MY2IN-CR
---
4PDT
MY4N-CR
MY4IN-CR
---
4PDT (bifurcated)
MY4ZN-CR
MY4ZIN-CR
---
Reverse Coil Polarity
Type
Contact form
Plug-in socket/Solder terminals
With LED indicator
Standard (DC only)
With built-in diode
(DC only)
With LED indicator and
lockable test button
DPDT
MY2N1
MY2IN1
4PDT
MY4N1
MY4IN1
4PDT (bifurcated)
MY4ZN1
MY4ZIN1
DPDT
MY2N1-D2
MY2IN1-D2
4PDT
MY4N1-D2
MY4IN1-D2
4PDT (bifurcated)
MY4ZN1-D2
MY4ZIN1-D2
Note: When ordering, add the rated coil voltage and “(s)” to the model number. Rated coil voltages are given in the coil ratings table.
Example: MY2 6VAC (S)
New model
Rated coil voltage
General-purpose Relay
MY New model
1
■ Accessories (Order Separately)
Sockets
Poles
Front-mounting
Socket (DIN-track/
screw mounting)
Back-mounting Socket
Solder terminals
Without clip
Wire-wrap terminals
With clip
Without clip
PCB terminals
With clip
2
PYF08A-E
PYF08A-N
PY08
PY08-Y1
PY08QN
PY08QN2
PY08QN-Y1
PY08QN2-Y1
PY08-02
4
PYF14A-E
PYF14A-N
PY14
PY14-Y1
PY14QN
PY14QN2
PY14QN-Y1
PY14QN2-Y1
PY14-02
Socket Hold-down Clip Pairing
Relay type
Poles
Front-connecting Socket (DIN-track/
screw mounting)
Socket
Without 2-pole test 2
button
PYF08A-E
PYF08A-N
4
PYF14A-E
PYF14A-N
2
PYF08A-E
PYF08A-N
2-pole test button
Back-connecting Socket
Solder/Wire-wrap terminals
Clip
Socket
PYC-A1
PCB terminals
Clip
PY08(QN)
Socket
PYC-P
PYC-P2
PY14(QN)
PYC-E1
Clip
PY08-02
PYC-P
PYC-P2
PY14-02
PY08(QN)
PYC-P2
PY08-02
PYC-P2
Mounting Plates for Sockets
Socket model
For 1 Socket
PY08, PY08QN(2), PY14, PY14QN(2)
For 18 Sockets
PYP-1
For 36 Sockets
PYP-18
PYP-36
Note: PYP-18 and PYP-36 can be cut into any desired length in accordance with the number of Sockets.
Track and Accessories
Supporting Track (length = 500 mm)
PFP-50N
Supporting Track (length = 1,000 mm)
PFP-100N, PFP-100N2
End Plate
PFP-M
Spacer
PFP-S
Specifications
■ Coil Ratings
Rated voltage
Rated current
50 Hz
AC
DC
Coil
resistance
60 Hz
Coil inductance
(reference value)
Arm. OFF
Arm. ON
6 V*
214.1 mA
183 mA
12.2 Ω
0.04 H
0.08 H
12 V
106.5 mA
91 mA
46 Ω
0.17 H
0.33 H
24 V
53.8 mA
46 mA
180 Ω
0.69 H
1.30 H
48/50 V*
24.7/
25.7 mA
21.1/
22.0 mA
788 Ω
3.22 H
5.66 H
110/120 V
9.9/10.8 mA
8.4/9.2 mA
4,430 Ω
19.20 H
32.1 H
4.2/4.6 mA
220/240 V
4.8/5.3 mA
18,790 Ω
83.50 H
136.4 H
6 V*
151 mA
39.8 Ω
0.17 H
0.33 H
12 V
75 mA
160 Ω
0.73 H
1.37 H
24 V
37.7 mA
636 Ω
3.20 H
5.72 H
48 V*
18.8 mA
2,560 Ω
10.60 H
21.0 H
100/110 V
9.0/9.9 mA
11,100 Ω
45.60 H
86.2 H
Must
operate
voltage
Must
release
voltage
Max.
voltage
Power
consumption
(approx.)
% of rated voltage
80% max.
30% min.
110%
1.0 to 1.2 VA
(60 Hz)
0.9 to 1.1 VA
(60 Hz)
10% min.
0.9 W
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/–20% for rated currents and
±15% for DC coil resistance.
2. Performance characteristic data are measured at a coil temperature of 23°C.
3. AC coil resistance and impedance are provided as reference values (at 60 Hz).
4. Power consumption drop was measured for the above data. When driving transistors, check leakage current and connect a bleeder resistor if required.
5. Rated voltage denoted by “*” will be manufactured upon request. Ask your OMRON representative.
2
General-purpose Relay MY
New model
■ Contact Ratings
Item
2-pole
Resistive load
(cosφ = 1)
4-pole
Inductive load
(cosφ = 0.4, L/R = 7 ms)
2A, 250 VAC
2 A, 30 VDC
Resistive load
(cosφ = 1)
Rated load
5A, 250 VAC
5A, 30 VDC
Carry current
10 A (see note)
5 A (see note)
Max. switching
voltage
250 VAC
125 VDC
250 VAC
125 VDC
Max. switching
current
10 A
5A
Max. switching
power
2,500 VA
300 W
Failure rate
(reference value)
5 VDC, 1 mA
1,250 VA
300 W
3 A, 250 VAC
3 A, 30 VDC
1,250 VA
150 W
4-pole (bifurcated)
Inductive load
(cosφ = 0.4, L/R = 7 ms)
Resistive load
(cosφ = 1)
Inductive load
(cosφ = 0.4, L/R = 7 ms)
0.8 A, 250 VAC
1.5 A, 30 VDC
3 A, 250 VAC
3 A, 30 VDC
0.8 A, 250 VAC
1.5 A, 30 VDC
500 VA
150 W
1,250 VA
150 W
500 VA
150 W
1 VDC, 100 µA
1 VDC, 1 mA
Note: Don’t exceed the carry current of a Socket in use. Please see page 9.
■ Characteristics
Item
All Relays
Contact resistance
100 mΩ max.
Operate time
20 ms max.
Release time
20 ms max.
Max. operating frequency
Mechanical: 18,000 operations/hr
Electrical:
1,800 operations/hr (under rated load)
Insulation resistance
1,000 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1.0 min (1,000 VAC between contacts of same polarity)
Vibration resistance
Destruction: 10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)
Malfunction: 10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)
Shock resistance
Destruction: 1,000 m/s2
Malfunction: 200 m/s2
Endurance
See the following table.
Ambient temperature
Operating: –55°C to 70°C (with no icing)
Ambient humidity
Operating: 5% to 85%
Weight
Approx. 35 g
Note: The values given above are initial values.
■ Endurance Characteristics
Pole
2-pole
Mechanical life (at 18,000 operations/hr)
Electrical life
(at 1,800 operations/hr under rated load)
AC:50,000,000 operations min.
DC:100,000,000 operations min.
500,000 operations min.
4-pole
4-pole (bifurcated)
20,000,000 operations min.
100,000 operations min.
200,000 operations min.
General-purpose Relay
MY New model
3
■ Approved Standards
VDE Recognitions (File No. 112467UG, IEC 255, VDE 0435)
No. of poles
2
Coil ratings
Contact ratings
6, 12, 24, 48/50, 100/110
110/120, 200/220,
220/240 VAC
6, 12, 24, 48, 100/110,
125 VDC
4
Operations
10 A, 250 VAC (cosφ=1)
10 A, 30 VDC (L/R=0 ms)
10 x 103
5 A, 250 VAC (cosφ=1)
5 A, 30 VDC (L/R=0 ms)
100 x 103
MY4Z AC; 50 x 103
UL508 Recognitions (File No. 41515)
No. of poles
2
Coil ratings
6 to 240 VAC
6 to 125 VDC
Contact ratings
10 A, 30 VDC (General purpose)
10 A, 250 VAC (General purpose)
4
Operations
6 x 103
5 A, 250 VAC (General purpose)
5 A, 30 VDC (General purpose)
CSA C22.2 No. 14 Listings (File No. LR31928)
No. of poles
2
Coil ratings
6 to 240 VAC
6 to 125 VDC
Contact ratings
10 A, 30 VDC
10 A, 250 VAC
4
Operations
6 x 103
5 A, 250 VAC (Same polarity)
5 A, 30 VDC (Same polarity)
IMQ (File No. EN013 to 016)
No. of poles
2
Coil ratings
6, 12, 24, 48/50, 100/110
110/120, 200/220,
220/240 VAC
6, 12, 24, 48, 100/110,
125 VDC
4
Contact ratings
Operations
10 A, 30 VDC
10 A, 250 VAC
10 x 10
5 A, 250 VAC
5 A, 30 VDC
100 x 103
MY4Z AC; 50 x 103
3
LR Recognitions (File No. 98/10014)
No. of poles
2
Coil ratings
6 to 240 VAC
6 to 125 VDC
4
Contact ratings
Operations
10 A, 250 VAC (Resistive)
2 A, 250 VAC (PF0.4)
10 A, 30 VDC (Resistive)
2 A, 30 VDC (L/R=7 ms)
50 x 103
5 A, 250 VAC (Resistive)
0.8 A, 250 VAC (PF0.4)
5 A, 30 VDC (Resistive)
1.5 A, 30 VDC (L/R=7 ms)
50 x 103
SEV Listings (File No. 99.5 50902.01)
No. of poles
2
Coil ratings
6 to 240 VAC
6 to 125 VDC
4
4
General-purpose Relay MY
Contact ratings
Operations
10 A, 250 VAC
10 A, 30 VDC
10 x 103
5 A, 250 VAC
5 A, 30 VDC
100 x 103
MY4Z AC; 50 x 103
New model
Engineering Data
Maximum Switching Power
AC resistive load
AC inductive load
(cosφ=0.4)
DC resistive load
Switching current (A)
MY4, MY4Z
Switching current (A)
MY2
AC resistive load
AC inductive load
(cosφ=0.4)
DC resistive load
DC inductive load
(L/R=7 ms)
DC inductive load
(L/R=7 ms)
Switching voltage (V)
Switching voltage (V)
Endurance
MY2 (Inductive Loads)
10000
5000
3000
250 VAC
1000
500
300
30 VDC
30 VDC
250 VAC
100
Endurance (x10 3operations)
Endurance (x10 3 operations)
MY2 (Resistive Loads)
10000
5000
3000
250 VAC
1000
500
300
30 VDC
30 VDC
250 VAC
100
50
30
50
30
10
10
Switching current (A)
MY4 (Resistive Loads)
MY4 (Inductive Loads)
Endurance (x10 3 operations)
Endurance (x10 3 operations)
Switching current (A)
10000
5000
3000
250 VAC
1000
500
300
30 VDC
30 VDC
100
250 VAC
50
30
10
10000
5000
3000
30 VDC
1000
500
300
30 VDC
250 VAC
100
50
30
250 VAC
10
Switching current (A)
Switching current (A)
General-purpose Relay
MY New model
5
MY4Z (Inductive Loads)
Endurance (x10 3operations)
Endurance (x10 3 operations)
MY4Z (Resistive Loads)
10000
5000
3000
1000
250 VAC
500
300
30 VDC
100
50
30
30 VDC
250 VAC
10
10000
5000
3000
1000
30 VDC
100
50
30
250 VAC
250 VAC
10
Switching Current (A)
6
30 VDC
500
300
General-purpose Relay MY
New model
Switching Current (A)
Dimensions
Note: All units are in millimeters unless otherwise indicated.
2-Pole Models
MY2N
2.6
Eight, 1.2 dia. × 2.2 long holes
0.5
28 max.
6.4
36 max.
21.5 max.
4-Pole Models
MY4N
2.6
Eight, 1.2 dia. × 2.2 long holes
0.5
28 max.
36 max.
6.4
21.5 max.
Models with Test Button
MY2IN
2.6
Eight, 1.2 dia. × 2.2 long holes
6.3
8
14.2
80.5
5
28 max.
36 max.
21.5 max.
MY4IN
2.6
Fourteen, 1.2 dia. × 2.2 long holes
0.5
6.3
8
14.2
80.5
5
28 max.
36 max.
<1.417>
6.4
21.5 max.
General-purpose Relay
MY New model
7
Terminal Arrangement/Internal Connections (Bottom View)
MY2
MY2N/MY2IN
(AC Models)
MY2N/MY2IN
(DC Models)
1
4
1
4
1
4
1
4
5
8
5
8
5
8
5
8
9
12
9
12
9
12
9
13
14
13
14
MY2N-CR/MY2IN-CR
(AC Models Only)
MY4(Z)
13
−
+
14
MY2N1/MY2IN1
(DC Models Only)
13
12
−
+
14
MY2N1-D2/MY2IN1-D2
(DC Models Only)
1
4
1
4
1
4
5
8
5
8
5
8
9
12
9
12
9
13
14
MY4(Z)N/MY4(Z)IN
(AC Models)
13
+
−
14
MY4(Z)N/MY4(Z)IN
(DC Models)
13
12
+
−
14
MY4(Z)N-D/MY4(Z)IN-D2
(DC Models Only)
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
5
6
7
8
5
6
7
8
5
6
7
8
5
6
7
8
9
10
11
12
9
10
11
12
14
13
14
13
13
14
MY4(Z)N-CR/MY4(Z)IN-CR
(AC Models Only)
−
+
MY4(Z)N1/MY4(Z)IN1
(DC Models Only)
−
+
14
MY4(Z)N1-D2/MY4(Z)IN1-D2
(DC Models Only)
2
3
4
1
2
3
4
1
2
3
4
5
6
7
8
5
6
7
8
5
6
7
8
9
10
11
12
14
13
14
Note: The DC models have polarity.
General-purpose Relay MY
13
1
13
8
MY2N-D2/MY2IN-D2
(DC Models Only)
New model
13
+
−
+
−
14
Socket for MY
Track-mounted (DIN Track) Socket
Conforms to VDE 0106, Part 100
• Snap into position along continuous sections of any mounting track.
• Facilitates sheet metal design by standardized mounting dimensions.
• Design with sufficient dielectric separation between terminals eliminates the need of any insulating sheet.
■ Safety Standards for Sockets
Model
Standards
PYF08A-E, PYF08A-N
PYF14A-E, PYF14A-N
File No.
UL508
E87929
CSA22.2
LR31928
Back-connecting Sockets
■ Specifications
Item
Pole
Model
Carry current
Screwless Clamp
Terminal Socket
2
PYF08S
10 A
4
PYF14S
5A
Track-mounted
Socket
2
PYF08A-E
7A
PYF08A-N (see note 3)
7 A (see note 4)
4
Back-connecting
Socket
2
PYF14A-E
5A
PYF14A-N (see note 3)
5 A (see note 4)
PY08(-Y1)
7A
Dielectric withstand
voltage
Insulation resistance
(see note 2)
2,000 VAC, 1 min
Less than 1,000 MΩ
2,000 VAC, 1 min
1,000 MΩ min.
1,500 VAC, 1 min
100 MΩ min.
PY08QN(-Y1)
PY08-02
4
PY14(-Y1)
3A
PY14QN(-Y1)
PY14-02
Note: 1.
2.
3.
4.
5.
The values given above are initial values.
The values for insulation resistance were measured at 500 V at the same place as the dielectric strength.
The maximum operating ambient temperature for the PYF08A-N and PYF14A-N is 55°C.
When using the PYF08A-N or PYF14A-N at an operating ambient temperature exceeding 40°C, reduce the current to 60%.
The MY2(S) can be used at 70°C with a carry current of 7 A.
General-purpose Relay
MY New model
9
■ Dimensions
Note: All units are in millimeters unless otherwise indicated.
Socket
Dimensions
Terminal arrangement/
Internal connections
(top view)
Mounting holes
38.2 max.
36.5 max.
PYF08S
23.2 max.
---
85 max.
(5.3)
PYF08A-E
Two, M3, M4, or 4.5-dia. holes
Two, 4.2 x 5
mounting
holes
Eight, M3 x 8
sems screws
72 max.
(TOP VIEW)
23 max.
Note: Track mounting is also
possible. Refer to page
12 for supporting tracks.
31 max.
22 max.
PYF08A-N
4
1
42
12
8
5
44
14
42
4
44
8
12
1
14
5
67 max.
3.5 dia. or M3
73
PYF-08A-N
41
11
12
9
A2
A2
A1
14
14
13
12
9
41
11
14 14 13
A2 A2 A1
30 max.
10
3.0 dia.
18.7
General-purpose Relay MY
New model
Note: Track mounting is also
possible. Refer to page
12 for supporting tracks.
Socket
Dimensions
Terminal arrangement/
Internal connections
(top view)
Mounting holes
36.5 max.
PYF14S
31 max.
---
85 max.
PYF14A-E
Two, 4.2 x 5
mounting
holes
Two, M3, M4, or 4.5-dia. holes
Fourteen, M3 x 8
sems screws
72 max.
(TOP VIEW)
Note: Track mounting is also
possible. Refer to page
12 for supporting tracks.
29.5 max.
31 max.
42
4
44
8
PYF14A-N
4
3
2
1
42
32
22
12
8
7
6
5
44
34
24
14
32
3
34
7
22
2
24
6
12
1
14
5
Two, 4.5 dia. or M4
67 max.
PYF-14A-N
41
31
21
11
12
11
10
9
A2
A2
A1
14
14
13
29.5 max.
26
73
12 11 10 9
41 31 21 11
30 max.
14 14
A2 A2
13
A1
General-purpose Relay
Note: Track mounting is also
possible. Refer to page
12 for supporting tracks.
MY New model
11
Socket
PY08/PY08-Y1
Dimensions
(See note)
Terminal arrangement/
Internal connections
(bottom view)
Mounting holes
Eight, 3 x 1.2 elliptical holes
25.5 max.
29.5 max.
20 max.
42 max.
24 max.
Note: The PY08-Y1 includes sections indicated by
dotted lines.
PY08QN/
PY08QN-Y1
(See note)
29.5 max.
22 max.
41.5 max.
24 max.
42 max.
Note: The PY08QN-Y1 includes sections
indicated by dotted lines.
PY08-02
25.5 max.
29.5 max.
22 max.
Eight, 1.3-dia.
holes
16.5 max.
PY14/PY14-Y1
(See note)
Fourteen, 3 x 1.2 elliptical holes
25.5 max.
29.5 max.
42 max.
20 max.
24 max.
Note: The PY14-Y1 includes sections indicated by
dotted lines.
PY14QN/
PY14QN-Y1
(See note)
29.5 max.
41.5 max.
42 max.
22 max.
24 max.
Note: The PY14QN-Y1 includes sections
indicated by dotted lines.
PY14-02
25.5 max.
29.5 max.
22 max.
Fourteen, 1.3-dia.
holes
16.5 max.
Note: Use a panel with plate thickness of 1 to 2 mm for mounting the Sockets.
12
General-purpose Relay MY
New model
Hold-down Clips
PYC-A1
(2 pcs per set)
PYC-E1
(2 pcs per set)
36.3
36.3
5.75
4.5
4.25
4.5±0.1
1.2
4.5
PYC-P
PYC-P2
5
10
29 max.
28
3.3
38.5
Mounting Plates for Back-connecting Sockets
PYP-1
PYP-36
Two, 3.4-dia. holes
72 elliptical holes
t=1.6
PYP-18
72 elliptical holes
General-purpose Relay
MY New model
13
Tracks and Accessories
Supporting Tracks
PFP-50N/PFP-100N
7.3±0.15
4.5
35±0.3
27±0.15
1
15
25
10
25
25
1000 (500) *
10
15 (5)
25
Note: The figure in the parentheses is for PFP-50N.
PFP-100N2
16
4.5
35±0.3 27
25
15
10
25
1000
25 10 25
15
End Plate
PFP-M
10
6.2
M4 x 8 pan head screw
1.8
1
50
1.8
11.5
1.3
10
M4 spring washer
4.8
Spacer
PFP-S
16
12
5
34.8
44.3
16.5
14
General-purpose Relay MY
New model
35.5 35.3
24
1
29.2
1.5
Precautions
Refer to General Precautions on page 11 of the General-purpose Relays and Power Relays Group Catalog (X034).
■ Connections
Do not reverse polarity when connecting DC-operated Relays with
built-in diodes or indicators or high-sensitivity DC-operated Relays.
■ Mounting
• Whenever possible, mount Relays so that it is not subject to vibration or shock in the same direction as that of contact movement.
General-purpose Relay
MY New model
15
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. J111-E1-03
In the interest of product improvement, specifications are subject to change without notice.
OMRON RELAY & DEVICES Corporation
General Purpose Relay Division
Marketing & Product Engineering Department
1110 Sugi, Yamaga-City,
Kumamoto, 861-0596 Japan
Tel: (81)968-44-4160/Fax: (81)968-44-4107
16
Printed in Japan
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if
specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR COMMERCIAL
LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR
STRICT LIABILITY.
In no event shall responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the product.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety
equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the product may be changed without any notice. When in doubt, special model numbers may be assigned to fix
or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
ERRORS AND OMISSIONS
The information in this catalog has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent
the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
COPYRIGHT AND COPY PERMISSION
This catalog shall not be copied for sales or promotions without permission.
This catalog is protected by copyright and is intended solely for use in conjunction with the product. Please notify us before copying or reproducing this
catalog in any manner, for any other purpose. If copying or transmitting this catalog to another, please copy or transmit it in its entirety.
Cat. No. J111-E1-03
OMRON Corporation
2007. 3
In the interest of product improvement, specifications are subject to change without notice.
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Omron:
MY3-AC110/120(S) MY4N-AC110/120S MY2E-02-AC110/120 MY2-DC100/110(S) MY4N-D2-DC24S MY4-DC6
MY2K-US-AC120 MY4N-AC24(S) MY4E-02-AC24 MY4-DC12(S) MY4Z-DC24(S) MY4-AC24(S) MY4NDC100/110S PTF08A-E MY2-DC12(S) MY3N-AC110/120 PT08-0 MY2N-AC220/240(S) MY2N-AC110/120(S)
MY4ZN-AC110/120(S) MY2N-DC12(S) PTF14A-E MY2-AC110/120(S) MY2-AC24(S) MY4-AC110/120(S) MY4INAC24(S) MY4-DC24(S) MY2-DC24(S) MY2-02-AC24 MY2N-DC24(S) MY4N-DC24(S) MY2N-D2-DC24S MY2NDC24 MY4N-DC24 MY2N-D2-DC24 MY4N-D2-DC24 MY2N-AC24(S) MY3-02-AC110/120 MY3-AC24 MY3
AC110/120 MY2-02-DC24 MY4N AC220/240 (S) MY2K AC120 MY4H-US DC24 MY4IN AC220/240 (S) MY2IN
AC110/120 (S) MY3 DC24 MY4IN AC110/120 (S) MY2IN AC24 (S) MY2IN DC24 (S) MY2 AC220/240 (S) MY4IN
DC12 (S) MY2K-US DC24 MY4-02 DC24 MY4 DC100/110 (S) MY2 DC48 (S) MY4-02-AC110-120 MY4-AC220240S MY4IN-DC24(S) MY4N-DC12(S) MY2N-D2-DC12(S) MY4-02-DC12 PY14QN PY14QN2 MY3-DC100/110
MY2-02-AC100/110 MY2-02-AC110/120 MY2-02-AC220/240 MY2-02-DC100/110 MY2-02-DC12 MY2-02-DC48
MY2-02-DC6 MY2-02-US-SV AC220/240 MY2F-AC110/120 MY2F-AC220/240 MY2F-AC24 MY2F-DC12 MY2FDC24 MY2F-V0-AC110/120 MY2IN1-D2 DC100/110 (S) MY2IN1-D2 DC12 (S) MY2IN1-D2 DC24 (S) MY2IN-CR
AC110/120 (S) MY2IN-CR AC220/240 (S) MY2IN-D2 DC100/110 (S) MY2IN-D2 DC12 (S) MY2IN-D2 DC24 (S)
MY2K-02-DC24 MY2K-US-AC24 MY2K-US-DC12 MY2K-US-DC48 MY2N1-D2 DC100/110 (S) MY2N1-D2 DC12 (S)
MY2N1-D2 DC24 (S) MY2N-CR AC110/120 (S) MY2N-CR AC220/240 (S) MY2N-D2 DC100/110 (S) MY3-02AC220/240 MY3-02-AC24 MY3-02-DC100/110