LEM LB100

Current Transducer LB 100-S/SP3
IPN
=
100 A
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
Features
Electrical data
· Closed loop (compensated) current
IPN
IP
RM
Primary nominal r.m.s. current
Primary current, measuring range
Measuring resistance
with ± 15 V
ISN
KN
VC
IC
Vd
@ ± 100 A max
@ ± 200 A max
Secondary nominal r.m.s. current
Conversion ratio
Supply voltage (± 5 %)
Current consumption
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
100
0 .. ± 200
RM min
RM max
0
0
85
30
100
1 : 1000
± 15
20 + IS
5 1)
A
A
according to UL 94-V0.
W
W
mA
V
mA
kV
Accuracy - Dynamic performance data
e
X
Accuracy @ IPN, TA = 25°C
Linearity
IO
IOT
Offset current @ IP = 0, TA = 25°C
Thermal drift of IO
+ 10°C .. + 50°C
Max
± 0.4
± 0.35 ± 0.4
tr
di/dt
f
Response time 2) @ 90 % of IPN
di/dt accurately followed
Frequency bandwidth (- 1 dB)
Zero crossing distortion
<1
> 50
DC .. 150
negligeable
L
± 0.5
< 0.1
transducer using the Hall effect
· Insulated plastic case recognized
%
%
Typ
mA
mA
µs
A/µs
kHz
Special features
· VC = ± 15 (± 5 %) V
· Better zero crossing performance
· TA = + 10°C .. + 50°C
· Potted.
Advantages
· Excellent accuracy
· Very good linearity
· Low temperature drift
· Optimized response time
· Wide frequency bandwidth
· No insertion losses
· High immunity to external
interference
· Current overload capability.
Applications
· AC variable speed drives and servo
motor drives
General data
TA
TS
RS
m
Notes :
Ambient operating temperature
Ambient storage temperature
Secondary coil resistance @ TA = 50°C
Mass
Standards 3)
1)
2)
3)
+ 10 .. + 50
- 25 .. + 85
25
180
EN 50178
°C
°C
W
g
· Static converters for DC motor drives
· Battery supplied applications
· Uninterruptible Power Supplies (UPS)
· Switched Mode Power Supplies
(SMPS)
· Power supplies for welding
applications
· HVDC transmisions.
Between primary and secondary.
With a di/dt of 100 A/µs
A list of corresponding tests is available.
990723/1
Dimensions LB 100-S/SP3 (in mm. 1 mm = 0.0394 inch)
Front view
Left view
Secondary terminals
Terminal + : supply voltage + 15 V
Terminal M : measure
Terminal - : supply voltage - 15 V
Connection
Top view
Mechanical characteristics
· General tolerance
· Fastening
· Primary through-hole
· Connection of secondary
Remarks
± 0.3 mm
4 holes Æ 4.3 mm
Æ 15 mm
Faston 6.3 x 0.8 mm
· IS is positive when IP flows in the direction of the arrow.
· Temperature of the primary conductor should not exceed
70°C.
· Dynamic performances (di/dt and response time) are best
with a single bar completely filling the primary hole.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.