LEM CV3-2000

Voltage Transducer CV 3-2000
VPN =
1400 V
For the electronic measurement of voltages : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high voltage)
and the secondary circuit (electronic circuit).
Electrical data
VPN
VP
VS
KN
RL
CL
VC
IC
Vd
Ve
Primary nominal r.m.s. voltage
Primary voltage, measuring range
Secondary analog voltage @ VP max
Conversion ratio
Load resistance
Capacitive loading
Supply voltage (± 5 %)
Current consumption
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
R.m.s. voltage for partial discharge extinction @ 10 pC
1400
0 .. ± 2000
10
2000 V / 10 V
≥1
≤5
± 15
32 + VS / R L
6
2
V
V
V
Typ
Overall accuracy @ VP max
VO
Offset voltage @ VP = 0
TA = 25°C
- 40°C .. + 85°C
TA = 25°C
- 40°C .. + 85°C
tr
Response time 1) @ 90 % of VP max
dv/dt dv/dt accurately followed
f
Frequency bandwidth (- 1 dB) @ 25 % of VPN
Max
± 0.2
± 0.6
± 5.0
± 13.0
0.4
900
DC .. 300
• Closed loop (compensated) voltage
transducer
kΩ
nF
V
mA
kV
kV
Accuracy - Dynamic performance data
XG
Features
%
%
mV
mV
µs
V/µs
kHz
• Insulated plastic case recognized
according to UL 94-V0
• Patent pending.
Advantages
•
•
•
•
•
•
Excellent accuracy
Very good linearity
Low thermal drift
Low response time
High bandwidth
High immunity to external
interference
• Low disturbance in common mode.
Applications
• AC variable speed drives and servo
motor drives
• Static converters for DC motor drives
• Uninterruptible Power Supplies
General data
TA
TS
P
R1
m
Notes :
Ambient operating temperature
Ambient storage temperature
Total primary power loss
Primary resistance
Mass
Standards 2)
1)
2)
- 40 .. + 85
- 45 .. + 90
3.1
640
560
EN 50155
°C
°C
W
kΩ
g
(UPS)
• Power supplies for welding
applications
• Railway overhead line voltage
measurement.
With a dv/dt of 900 V/µs
A list of corresponding tests is available
030129/8
LEM Components
www.lem.com
Dimensions CV 3-2000
(in mm. 1 mm = 0.0394 inch)
Front view
Left view
Secondary terminals
Terminal
Terminal
Terminal
Terminal
+
M
0
-
:
:
:
:
supply voltage + 15 V
measure
0V
supply voltage - 15 V
Connection
Red
Blue
Top view
Remarks
Mechanical characteristics
• General tolerance
• Transducer fastening
Fastening torque max
• Connection of primary
• Connection of secondary
• Fastening torque max
± 0.3 mm
3 holes ∅ 5.5 mm
3 M5 steel screws
4 Nm or 2.95 Lb. - Ft.
M5 threaded studs
M5 threaded studs
2.2 Nm or 1.62 Lb. -Ft.
• VS is positive when VP is applied on terminal +HT.
• CEM tested with a shielded secondary cable.
Shield connected to 0 V at both ends, or disconnected.
• This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.