LEM CV3-500

Voltage Transducer CV 3-500
VPN =
350 V
For the electronic measurement of voltages : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high voltage)
and the secondary circuit (electronic circuit).
Electrical data
VPN
VP
VS
KN
RL
CL
VC
IC
Vd
Ve
Primary nominal r.m.s. voltage
Primary voltage, measuring range
Secondary analog voltage @ VP max
Conversion ratio
Load resistance
Capacitive loading
Supply voltage (± 5 %)
Current consumption
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
R.m.s. voltage for partial discharge extinction @ 10 pC
350
0 .. ± 500
10
500 V / 10 V
≥1
≤5
± 15
32 + VS / R L
6
2
V
V
V
Typ
Overall accuracy @ VP max
VO
Offset voltage @ VP = 0
TA = 25°C
- 40°C .. + 85°C
TA = 25°C
- 40°C .. + 85°C
tr
Response time 1) @ 90 % of VPN
dv/dt dv/dt accurately followed
f
Frequency bandwidth (- 1 dB) @ VPN
Max
± 0.2
± 0.6
± 5.0
± 13.0
0.3
500
DC .. 300
%
%
mV
mV
µs
V/µs
kHz
Notes :
Ambient operating temperature
Ambient storage temperature
Total primary power loss
Primary resistance
Mass
Standards 2)
1)
2)
• Insulated plastic case recognized
according to UL 94-V0
• Patent pending.
Advantages
•
•
•
•
•
•
Excellent accuracy
Very good linearity
Low thermal drift
Low response time
High bandwidth
High immunity to external
interference
• Low disturbance in common mode.
Applications
• AC variable speed drives and servo
motor drives
General data
TA
TS
P
R1
m
• Closed loop (compensated) voltage
transducer
kΩ
nF
V
mA
kV
kV
Accuracy - Dynamic performance data
XG
Features
• Static converters for DC motor drives
• Uninterruptible Power Supplies
- 40 .. + 85
- 45 .. + 90
3.1
40
560
EN 50155
°C
°C
W
kΩ
g
(UPS)
• Power supplies for welding
applications.
With a dv/dt of 500 V/µs
A list of corresponding tests is available.
011107/8
LEM Components
www.lem.com
Dimensions CV 3-500 (in mm. 1 mm = 0.0394 inch)
Front view
Left view
Secondary terminals
Terminal + : supply voltage + 15 V
Terminal M : measure
Terminal 0 : 0 V
Terminal - : supply voltage - 15 V
Connection
Top view
Mechanical characteristics
•
•
•
•
•
General tolerance
Fastening
Connection of primary
Connection of secondary
Fastening torque
Remarks
± 0.3 mm
3 holes ∅ 5.5 mm
M5 threaded studs
M5 threaded studs
2.2 Nm or 1.62 Lb. -Ft.
• VS is positive when VP is applied on terminal +HT.
• CEM tested with a shielded secondary cable.
Shield connected to 0 V at both ends, or disconnected.
• This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...), please
contact us.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.