SUPERTEX HV312DB1

HV312DB1
Hotswap Controller
Introduction
Specifications
The Supertex HV312DB1 demo board contains all circuitry
necessary to demonstrate the features of the HV312
hotswap controller. Intended primarily as a negative
hotswap controller, the HV312 controls the negative supply
path. Four sequenced power-good signals are provided,
with timing controlled via 3 resistors.
Input Voltage
Included on board is a 100*F capacitor to provide a
capacitive load for testing. Additional capacitance may be
connected to the VOUT terminals. Or the 100*F may be
removed altogether
Undervoltage Trip
38.0V on, 32.2V off
Overvoltage Trip
64.5V on, 70.0V off
10V to 90V
Inrush Limit
1A ±20%
Circuit Breaker Trip
6.7A ±20%
Retry Interval
16sec typ
On Resistance
40m 8 max
Active Low
~5ms after CLOAD charged
~200ms after ‘A’
~100ms after ‘B’
~5ms after ‘C’
Power Good Signals
PWRGD A
PWRGD B
PWRGD C
PWRGD D
The board may be modified to meet custom requirements.
Instructions are provided on the next page for modifications.
Board Layout and Connections
+
R10
R9
HV312
R8
C6
R4
C3
C1
C2
R6
Q1
R5
VIN
Connect the supply voltage to these terminals. Supply
voltage may range from 10 volts to 90 volts.
A high source impedance may cause oscillations when the
input voltage is near the undervoltage trip point. A high
source impedance results in a large voltage drop when
loaded, causing undervoltage lockout to kick in,
disconnecting the load. With the load removed, input voltage
rises, causing undervoltage to release and reconnecting the
load. The cycle repeats, resulting in oscillations. Source
impedance must be less than the following to avoid
oscillations:
RSOURCE <
+
enable
DC/DC
Converter
–
+
enable
DC/DC
Converter
–
+
enable
DC/DC
Converter
–
R7
C4
VIN
enable
DC/DC
Converter
–
3V
I LOAD
VOUT
Connect the power supply or other load to these terminals.
VOUT+ is connected to VIN+, it is VOUT– that is switched.
last enabled
first enabled
reason, DC load at start-up should be less than 900mA.
Note that DC start-up load limitation decreases with added
load capacitance.
Connecting additional load capacitance alters the inrush
current limit. See the HV302/312 data sheet for details.
PWRGD
Connect to the power supply’s ENABLE inputs. Depending
on the power supply, it may be necessary to level-translate
this signal via opto-isolator or discrete circuit. Refer to the
HV302/312 data sheet for a description of PWRGD and
related application circuits.
PWRGD is an open-drain output. During start-up and
whenever VIN is lower than the undervoltage trip point or
greater than the overvoltage trip point, PWRGD assumes a
high impedance state. Once VIN is within the proper range
and the load capacitance has fully charged, PWRGD is
pulled down to VIN-.
Application of a DC load during start-up extends the time
inrush limiting is active. If this time exceeds 100ms, the
HV312 shuts off, retrying as quickly as 12s later. For this
rev 2 12SEP02
1
HV312DB1
Hotswap Controller
Schematic
VIN+
VOUT+
14
VDD
R1
487k
R2
9.09k
6
5
R3
9.09k
UV
PWRGDA
PWRGDB
PWRGDC
PWRGDD
HV312
TB
TC
TD
OV
VEE
7
R4
not used
4
3
2
1
RAMP
SENSE
10
GATE
8
C2
not used
C1
10nF
9
11
12
13
R8
121k
C5
not used
R9
60.4k
R10
3.01k
C6
100*F
C3
680pF
R6
0
VINR5
15m
R7
not used
C4
not used
Q1
IRF3710S
VOUT-
Inrush Limit
Circuit Breaker Transient Immunity
As supplied, the inrush current limit is set at 1 amp. To set
inrush limit to another value, please refer to the HV302/312
data sheet.
The HV312 has built-in transient immunity of 2–5*s. To
increase transient immunity, an RC low-pass filter (R6C2)
may be placed on the SENSE input. (The demo board is
supplied with no filtering.)
The circuit breaker trip point is set at 6.7 Amps. To set at a
different level, change R5 according to the following
equation:
I CB =
100mV
R5
The power rating of R5 should be selected based on
maximum current during normal operation, which could be
just under the circuit breaker trip point.
P5 = 100mV I CB
Timing
Timing capacitor C1 determines start-up delay, rise time, and
circuit breaker retry interval,. Changing C1 will alter these
timings. Refer to the HV302/312 datasheet for the equations
that relate these timings to the value of C1. For use in the
equations, the nominal gate threshold voltage (VGS) of the
supplied IRFR3710 is 3V and transconductance is about 10
siemens.
Resistors R8, R9, and R10 set the delays for PWRGDs B, C,
and D according to the following equation:
t D = 1.67µF R X
rev 2 12SEP02
Be aware that filtering the sense input will cause the inrush
current limit to overshoot at turn-on – the greater the filtering,
the greater the overshoot.
Undervoltage/Overvoltage Lockout
Resistors R1, R2, and R3 set the undervoltage and
overvoltage trip points. New trip points may be programmed
by changing the values of these resistors. Refer to the
HV302/312 data sheet for more information.
Additional Components
The RC network (R7C4) across the gate-source of the
external FET provides control loop compensation which
prevents inrush current peaking.
If the PWRGD A signal is used and experiences large
voltage swings, a 10nF capacitor should be installed at C5.
This limits dV/dt which may otherwise cause undesirable
coupling to internal circuits.
To defeat the circuit breaker auto-retry, install a 2.4M
resistor at location R4.
For servo-mode inrush control, remove C3. Inrush limit will
then be 3.3 Amps. See the HV302/312 data sheet for
details.
2