FUJI EDS11-168B

PUM Series
Multi-loop module type
Temperature controller
Enhanced communication Module [PUMCM]
(Mitsubishi’s PLC Programless Communication)
DATA SHEET
PUMCM
PUMCM is the communication module to connect the module
type temperature controller, PUM series, to Mitsubishi’s PLC
(MELSEC-Q/A/AnS/FX series) without program.
High-speed communication of maximum 230.4kbps can be
performed via RS-232C, RS-422 or RS-485 interface. Also,
maximum of 16 units (64 channels) of PUMA (control module)
can be connected to one of this module,and maximum 8
units of this module can be connected to 1 communication
port, and it realizes a labor saving wiring, simple engineering
and small space.
FEATURES
I. Programless connection with Mitsubishi’s PLC
1. RS-232C, RS-422 or RS-485 high-speed communication
(max. 230.4 kbps)
2. Accessible to the almost all parameters of control
module (PUMA/PUMB)
3. High-speed data loading and setting reflection by highspeed internal communication with connected control
module (PUMA/B)
4. 1:N configuration is available, which maximum 8 units
of this module can be connected to 1 communication
port.
II.User-friendly structure and functions
1. Lateral connection to 1 unit of this module: Max. 16
units (64 channels) + event input/output module 16
units = total 32 units
Simple wiring for power supply and a labor saving wiring
for communication by programless communication.
2. Detachable structure: Terminal block, main unit, and
the base part.
→ Easy wiring with detachable terminal block
→ Main units exchangeable without re-wiring
3.Connecting method:
Lateral connecting with connectors
(For power supply and RS-485 communication, any one of connected modules
is required to be connected)
4.No. of loop, input/output
1)Control loop:
Max. 64
2)No.of input / output: DI 128 points / DO 128 points
ENHANCED COMMUNICATION MODULE
SPECIFICATIONS
(Mitsubishi’s PLC programless communication)
1. General specification
SYSTEM SPECIFICATION
1. Product type: Multi-loop module type temperature
controller
2.Module type
1)Analog module: Total max. 16 units
a)Control module (4 loops)
b)Enhanced input/output (analog) module
-Analog input/output module
(input/output 4 points/unit)
-Analog input module (input 4 points/unit)
-Analog output module (output 4 points/unit)
2)Enhanced input/output (digital) module:
Maximum 16 units
-Event input/output module
(input/output 8 points/unit)
3)Enhanced communication module: 1 unit
(1) Power supply: 24V DC ±10%
(2) Power consumption: Max. 3.2 W (135 mA)
[when 24V DC is applied]
(3) Insulation resistance: 20MW or more (500V DC)
(4) Withstand voltage:
Power supply ↔ loader communication
1000V AC 1 min.
Power supply ↔ RS-232C,RS-422,RS-485
1000V AC 1 min.
(5) Applied standards:
UL, C-UL, CE marking, RoHS directive
[Pending for UL, C-UL marking]
EDS11-168b
Date
Apr. 1, 2011
PUMCM
2. Connected devices
• MELSEC-Q series
Device
Communication port
Type
Q-compatible serial
communication unit
CH1
CH2
QJ71C24,
QJ71C24N
RS-232C
(D-sub 9P)
RS-422/485
(2-piece socket block)
QJ71C24-R2,
QJ71C24N-R2
RS-232C
(D-sub 9P)
RS-232C
(D-sub 9P)
QJ71C24N-R4
RS-422/485
(2-piece plug-in connector socket block)
RS-422/485
(2-piece plug-in connector socket block)
• MELSEC-A/Ans series
Device
A-compatible computer
link module
AnS-compatible computer link module
Communication port
Type
CH1
CH2
AJ71UC24
RS-232C(D-sub 9P)
RS-422/485(terminal block)
-
A1SJ71UC24-R2
RS-232C
(D-sub 9P)
-
A1SJ71UC24-R4
RS-422/485
(terminal block)
-
A1SJ71UC24-PRF
RS-232C
(D-sub 9P)
-
• MELSEC-FX series
Device
Communication port
Type
CH1
CH2
FX0N-232ADP
RS-232C
(D-sub 25P)
-
FX2NC-232ADP
RS-232C
(D-sub 9P)
-
RS-232C
(D-sub 9P)
-
-
RS-232C
(D-sub 9P)*1
FX-232ADP
RS-232C
(D-sub 25P)
-
FX0N-485ADP
RS-485
(terminal bock)
-
FX2NC-485ADP
RS-485
(European terminal block)
-
RS-485
(European terminal block)
-
-
RS-485
(European terminal block)*1
FX-485ADP
RS-485
(terminal bock)
-
FX1N-232-BD
RS-232C
(D-sub 9P)
-
FX2N-232-BD
RS-232C
(D-sub 9P)
-
FX3U-232-BD
RS-232C
(D-sub 9P)
-
FX1N-485-BD
RS-485
(European terminal block)
-
FX3U-485-BD
RS-485
(European terminal block)
-
FX3U-232ADP
Communication special
adaputer
FX3U-485ADP
Enhanced board
*1 When using it as CH2, FX3U-- ADP should be connected to CH1 by using FX3U--BD or two of FX3U-- ADP should
be connected to CH1 by using an enhanced board, FX3U-CNV-BD (one of 232, 422, 485 or USB goes into , and 232 or
485 goes into ).
Refer to [Data Communication Edition] in the FX SERIES USER’S MANUAL for details.
Connectable model types on FX series sequencer are shown below.
Type
FX2(FX), FX2C, FX2N, FX1N, FX2NC, FX1NC, FX3U, FX3UC
FX1S, FX0N
2
Connection
Connectable
Not connectable
3. Communication interface
3.1 Programless communication interface
Select ,
or ③ by the switch
RS-422 interface
(1) Communication standards: RS-422 compatible
(2) No. of port: 1 port
(3) Communication, synchro method:
4-wire, half duplex, asynchronous cycle
(4) Communication speed:
9.6k, 19.2k, 38.4k, 57.6k, 115.2k,
230.4kbps
(5) Max. communication distance:
MELSEC-Q series 1000m or less
MELSEC-A series 500m or less
MELSEC-FX series 500m or less
(6) Recommended cable:
KFPEV-SB2P 0.5sq-equivalent / FUJI
ELECTRIC CABLE CO., LTD
(7) Data format: Start bit1, data bit 8,
Parity even/odd/none
Stop bit 1
(8) Insulation: No insulation with any communication
interface other than loader interface,
Functional insulation with loader communication interface and other all signals
② RS-485 interface
(1) Communication standards: RS-485 compatible
(2) No. of port: 1 port
(3) Communication, synchro method:
2-wire, half duplex, asynchronous cycle
(4) Communication speed:
9.6k, 19.2k, 38.4k, 57.6k, 115.2k,
230.4kbps
(5) Max. communication distance:
MELSEC-Q series 1000m or less
MELSEC-A series 500m or less
MELSEC-FX series 500m or less
(6) Recommended cable:
KFPEV-SB2P 0.5sq / FUJI ELECTRIC
CABLE CO., LTD
(7) Data format: Start bit1, data bit 8,
Parity even/odd/none
Stop bit 1
(8) Insulation: No insulation with any communication
interface other than loader interface,
Functional insulation with loader communication interface and other all signals
ELECTRIC CABLE CO., LTD
(7) Data format: Start bit1, data bit 8,
Parity even/odd/nene
Stop bit 1
(8) Insulation: No insulation with any communication
interface other than loader communication interface, Functional insulation with
loader communication interface and other
all signals
3.2 Loader communication interface
(1) Communication standards: RS-232C compatible
(2) No. of port: 1 port
(3) Communication, synchro method:
Half-duplex, asynchronous cycle
(4) Communication speed: 19.2kbps (fixed)
(5) Data format: Data bit 8, no prity
(6) Protocol:
Modbus RTU compatible
(7) Connection method:
2.5 diameter mini-plug / jack
[on the front of module]
(Common cable with PXG, PXH)
(8) Insulation: Functional insulation with any other signals
4. Display, configuration
Status display LED
(2 colors × 2 points + 4points)
(2) Display contents:
RUN/FAULT, internal communication status
Communication TX/RX (Port1),
Communication TX/RX (Port2)
(3) Setting device and setting contents
(1) Display:
Setting device
Front face
Rotary SW × 1
Within the devace DIP SW (6bit) × 1
Setting contents
Programless communication station setting
RS-232C/RS-422/RS485
Operation mode
5. Power outage
(1) Impact of power outage:
Outage of 2ms or less; no impact
(2) Operation after power outage:
Start from the first step (cold start)
(3) Memory backup:
Nonvolatile memory (EEPROM)
(No. of update; 100,000)
③ RS-232C interface
(1) Communication standards: RS-232C compatible
(2) No. of port: 1 port
(3) Communication, synchronous method:
Half-duplex, asynchronous cycle
(4) Communication speed:
9.6k, 19.2k, 38.4k, 57.6k, 115.2k,
230.4kbps
(5) Max. communication distance: 15m
(6) Recommended cable:
KFPEV-SB 1P 0.5sq-equivalent / FUJI
3
PUMCM
6. Self diagnosis
Diagnosis method:
Program error monitoring by watch dog
timer
7. Structure
(1) Installation method:
DIN rail mounting or mounting with M3
screws inside a cabinet
(2) Dimensions: 30 (W) × 100 (H) × 85 (D) mm
(excluding terminal cover and projected
part)
(3) Weight:
Approx. 200 g
(4) Extrenal terminal
- Programless communication interface:
Detachable terminal block
(M3 screw × 20 terminals)
- Power supply connection:
Terminal block on the base part
(M3 screw × 2 terminals)
Power is supplied via side connectors
in case of lateral connecting. (Max. 33
units)
- Loader communication port:
2.5 diameter 3-pole mini-plug/jack
[on the front of module]
(5) Case material: Polyphenylene oxide
(flame retardant grad: UL94V-0
equivalent)
(6) Case color: Case ; red
Terminal, base part ; black
(7) Protection
- Body:
IP20 grade protection
(ventilation slits on the top and the bottom of body)
- Terminal: IP00 grade protection,terminal cover is
available as an option
10. Packing list
Temperature controller:1unit
Instruction manual:
1 copy
11. Loader software
(1) Distribution medium:
Free download from Fuji Electric Systems
HP (http://www.fic-net.jp)
(2) Recommended operating environments
PC:
DOS/V (PC-AT compatible)
OS:
Windows XP (operation confirmed in
Japanese / English)
RAM:
256M bytes or more
Free space on the hardware: 500M bytes or more
Display resolution: 1024 × 768 or over
Serial interface: RS-232C 1 port
(without RS-232C, USB serial converter
cable required)
(3) Connection with PUM
Via loader interface on the front face of module
(special cable available from Fuji is required)
CODE SYMBOLS
[Enhanced communication module]
Digit
1 2 3 4 5 6 7 8
9 10
P UM
0
Digit
Description
4 < Module type >
Enhanced communication module
5 < Communication functions >
Mitsubishi’s PLC programless communication
10 < Operation manual >
Japanese
English
C
M
A
B
Digit
8. Normal operating condition
(1) Ambient temperature*: −10 to 50°C
* “Ambient temperature” is the temperature underneath the controller inside
the equipment or the cabinet where
the controller is installed.
(2) Ambient humidity:
90% RH or less (non condensing)
(3) Vibration:
10 to 70Hz, 9.8m/s2 (1G) or less
9.Transporting, storage condition (packing condition)
(1) Storage temperature: −20 to 60°C
(2) Ambient humidity: 90%RH or less (no condensing)
(3) Vibration:
10 to 70Hz, 9.8m/s2 (1G) or less
(4) Shock:
294m/s2 (30G) or less
4
YY1
1 2 3 4 5 6 7 8
Digit
Description
6 DIN rail mounting end plate
7 Connecting terminal cover (right & left 1 set)
8 Front face screw terminal cover
Loader connecting cable (RS-232C)
P UM Z *
A
A
A
L
0
0
0
0
2
3
4
1
[Table 1]Insulation block diagram
Power
Loader communication
Functional insulation (1000VAC)
RS-323C
RS-422
RS-485
Functional insulation (500VAC)
OUTLINE DIAGRAM (Unit : mm)
Front terminal cover (option)
(10)
Base part
(Main unit is detached)
Terminal block
(at attach/detach)
30
85
Hole for screw mounting
LOADER
1.5
50
STATION
100
6
DIN rail
6.1
Terminal
screw M3
(8)
At mounting to
the DIN rail
(30)
5
Terminal
screw M3
Hole for screw mounting
Main unit (at attach/detach)
DIN rail fixture
Dimensions for Screw Mounting
(30)
9±0.2
Please keep the distance of 30mm from this instrument to radiate.
(50mm is recommended.)
30 or more
88.5±0.2
(3)
(100)
30 or more
2-M3
Notice at the Installation
30+0.7
+0.2
5
PUMCM
Terminal connection diagram
Loader interface (RS-232C)
3 TX
2 RX
1 GND
LOADER
φ2.5 3-pole miniature plug
STATION
RS-485
RS-422
21
Don’t
connect
22
21
Don’t
connect
23
A
B
SG
24
25
26
27
28
Don’t
connect
29
30
22
23
SDA
SDB
SG
RDA
RDB
Don’t
connect
RS-232C
21
11
TX
22
12
11
23
13
12
24
14
RX
SG
21
22
23
13
24
24
25
25
25
15
26
26
16
27
17
26
27
28
Don’t
connect
27
28
14
Don’t
connect
15
16
17
18
29
29
28
18
19
30
30
29
19
20
30
20
Base part
Power
1
3
+
24V DC
2
4
5
3
1
2
4
5
−
Don’t connect
6
Programless communication module status
Contents
Setting faults
Reading out/Writing data setting range
0101h: St. No. configuration SW is invalid value
0102h: DIP SW is invalid value
0201h: PLC communication speed is invalid value
0202h: PLC communication data length is invalid value
0203h: MC protocol is invalid value
0204h: PLC communication inter-cycle time is invalid value
0205h: PLC communication starting time is invalid value
0206h: PLC response monitoring time is invalid value
0207h: Number of PLC communication retry is invalid value
0208h: Connection method is invalid value
0209h: Number of connected units is invalid value
020Ah: Operation at PLC communication fault is invalid value
020Ch: MC protocol frame type is invalid value
0210h: Setting area device type is invalid value
0211h: Setting area device size is invalid value
0212h: Monitor area device type is invalid value
0213h: Monitor area device size is invalid value
0214h: Setting area detail (The 1 st word) is invalid value
0215h: Monitor area detail (The 1 st word) is invalid value
Factory-set value
-
Register No.
30232
Reading out/Writing data setting range
0 → 1→ …→ 65535 → 0 → 1 → …times
0000h to 0042h: Error code of A compatible 1C frame
0100h: Command message timeout
0101h: Response message timeout
0102h: Sum check code error
0103h: Header format error
0104h: ASCII code error
0110h: Hardware failure 1
0111h: Hardware failure 2
0120h: Continuous reception error
7000h to 7FFFh: Error code of QJ71C24N
0 → 1→ …→ 65535 → 0 → 1 → …times
0 → 1→ …→ 65535 → 0 → 1 → …times
0 to 65535ms
0 → 1→ …→ 65535 → 0 → 1 → …times
Factory-set value
-
-
Register No.
31001
31002
-
-
-
-
31003
31004
31007
31008
Reading out/Writing data setting range
0005h: 9600bps
0007h: 19200bps
0009h: 38400bps
000Ah: 57600bps
000Bh: 115200bps
000Ch: 230400bps
b0: OFF (fixed)
b1: Data bit (ON: 8bits (fixed))
b2: Parity bit (OFF: No, ON: Yes)
b3: Odd/Even parity (OFF: Odd, ON: Even)
b4: Stop bit (OFF: 1, ON: 2)
b5 to b15: OFF (fixed)
2: Type2
4: Type 4
5: Type5
0 to 5000ms
1 to 255sec
10 to 10000ms
0 to 10 times
0=1:1 connection
1=1:N connection
1 to 8
0: QnA compatible 4C frame
1: A compatible 1C frame
Factory-set value
000Bh
Register No.
40001
000Eh
40002
5
100
1
200
0
0
1
0
40003
40004
40005
40006
40007
40008
40009
40019
Factory-set value
0001h
Register No.
40010
Communication status with PLC
Contents
PLC error counter
PLC error code
PLC
PLC
PLC
PLC
sending counter
receiving counter
inter-cycle time monitor
inter-cycle time over counter
PLC communication setting
Contents
PLC communication speed
PLC transmission setting
MC protocol
PLC communication inter-cycle time
PLC communication starting time
PLC response monitoring time
Number of retry times
Connection method
No. of connected units
MC protocol frame type
Programless communication module
Contents
Operation selection at
programless communication fault
Reading out/Writing data setting range
0000h: RUN
0001h: STOP
7
PUMCM
Memory configuration (Setting area)
Contents
Setting area device type
Setting area start address (lower)
Setting area start address (upper)
Setting area device size
Setting area entry St. No.
(The 1st word)
Setting area entry register No.
(The 1st word)
Setting area entry St. No.
(The 2nd word)
Setting area entry register No.
(The 2nd word)
Reading out/Writing data setting range
00A8h: Data register (D)
00B4h: Link register (W)
00AFh: File register (R)
00B0h: File register [for sequence No. access] (ZR)
Addressable range: according to PLC (product of Mitsubishi) setting
Addressable range: according to PLC (product of Mitsubishi) setting
0 to 712
0: Not used
1 to 16: Control/Analog module
17 to 32: Event module
0, 40000 to 49999 (Note1)
Factory-set value
00A8h
Register No.
40011
1000
0
0
0
40012
40013
40014
41001
0
41002
0
41003
0
41004
0: Not used
1 to 16: Control/Analog module
17 to 32: Event module
0, 40000 to 49999 (Note1)
0
42421
0
42422
0: Not used
1 to 16: Control/Analog module
17 to 32: Event module
0, 40000 to 49999 (Note1)
0
42423
0
42424
0: Not used
1 to 16: Control/Analog module
17 to 32: Event module
0, 40000 to 49999 (Note1)
・
・
・
Setting area entry St. No.
(The 711th word)
Setting area entry register No.
(The 711th word)
Setting area entry St. No.
(The 712th word)
Setting area entry register No.
(The 712th word)
Note 1: Only the address written in " setting/monitor area register number" (control module 5-6, event module 5-7) can be set.
However, the parameters marked * in the "Entry ban" column cannot be set.
Memory configuration (Monitor area)
Contents
Monitor area device type
Monitor area start address (lower)
Monitor area start address (upper)
Monitor area device size
Monitor area entry St. No.
(The 1st word)
Monitor area entry register No.
(The 1st word)
Monitor area entry St. No.
(The 2nd word)
Monitor area entry register No.
(The 2nd word)
Reading out/Writing data setting range
00A8h: Data register (D)
00B4h: Link register (W)
00AFh: File register (R)
00B0h: File register [for sequence No. access] (ZR)
Addressable range: according to PLC (product of Mitsubishi) setting
Addressable range: according to PLC (product of Mitsubishi) setting
0 to 712
0: Not used
1 to 16: Control/Analog module
17 to 32: Event module
128: Programless communication module
0, 30000 to 49999 (Note2)
Factory-set value
00A8h
Register No.
40015
0
0
0
0
40016
40017
40018
43001
0
43002
0
43003
0
43004
0: Not used
1 to 16: Control/Analog module
17 to 32: Event module
128: Programless communication module
0, 30000 to 49999 (Note2)
0
44421
0
44422
0: Not used
1 to 16: Control/Analog module
17 to 32: Event module
128: Programless communication module
0, 30000 to 49999 (Note2)
0
44423
0
44424
0: Not used
1 to 16: Control/Analog module
17 to 32: Event module
128: Programless communication module
0, 30000 to 49999 (Note2)
・
・
・
Monitor area entry St. No.
(The 711th word)
Monitor area entry register No.
(The 711th word)
Monitor area entry St. No.
(The 712th word)
Monitor area entry register No.
(The 712th word)
Note 2: Only the address written in " setting/monitor area register number" (control module 5-6, event module 5-7) can be set.
However, the parameters marked * in the "Entry ban" column cannot be set.
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
International Sales Div
Sales Group
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fujielectric.com
Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425
http://www.fjielectric.com/products/instruments/
Information in this catalog is subject to change without notice.
Printed in Japan