S P V- 6 0 0 600W Single Output with PFC Function series Features : ry Universal AC input / Full range Built-in active PFC function Protections: Short circuit / Overload / Over voltage / Over temperature Forced air cooling by built-in DC fan Output voltage programmable from 20~110% by 1~5.5VDC external control signal With DC OK Signal output Built-in remote ON-OFF control na Fixed switching frequency at PFC:88KHz PWM:100KHz 3 years warranty SPECIFICATION MODEL SPV-600-12 DC VOLTAGE 12V RATED CURRENT 50A CURRENT RANGE 0 ~ 50A RATED POWER 600W RIPPLE & NOISE (max.) Note.2 240mVp-p OUTPUT VOLTAGE ADJ. RANGE 10 ~ 13.2V VOLTAGE TOLERANCE Note.3 1.0% LINE REGULATION SETUP, RISE TIME INPUT 12.5A 0 ~ 25A 0 ~ 12.5A 600W 600W 240mVp-p 300mVp-p 20 ~ 26.4V 1.0% 41 ~ 56V 1.0% 0.5% 0.5% FREQUENCY RANGE 47 ~ 63Hz POWER FACTOR (Typ.) 0.95/230VAC EFFICIENCY(Typ.) 84% 124 ~ 370VDC 0.99/115VAC at full load 86% 6.8A/115VAC 20A/115VAC <1.3mA/240VAC OVERLOAD 105 ~ 135% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed OVER VOLTAGE 13.8 ~ 16.2V 27.6 ~ 32.4V Protection type : Shut down o/p voltage, re-power on to recover OVER TEMPERATURE 85 (TSW1) detect on heatsink of power transistor; 80 (TSW51) detect on heatsink of power diode Protection type : Shut down o/p voltage, re-power on to recover REMOTE CONTROL POK SIGNAL WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION RC+/RC-: Short = power on ; Open = power off PSU turn on: 3.3V ~ 5.6V PSU turn off: 0V ~ 1V 4.8 ~ 26.4V 2.4 ~ 13.2V -20 ~ +60 (Refer to output load derating curve) NOTE DIMENSION PACKING 57.6 ~ 67.2V 9.6 ~ 52.8V 20 ~ 90% RH non-condensing -40 ~ +85 , 10 ~ 95% RH 0.03%/ (0 ~ 50 ) 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes Design refer to UL60950-1, TUV EN60950-1 I/P-O/P:3KVAC Pr SAFETY STANDARDS WITHSTAND VOLTAGE ISOLATION RESISTANCE MTBF OTHERS 87% 3.4A/230VAC 40A/230VAC LEAKAGE CURRENT OUTPUT VOLTAGE TRIM WORKING TEMP. SAFETY 0.5% 20ms at full load Note.4 88 ~ 264VAC eli FUNCTION 0.5% 1500ms, 50ms at full load AC CURRENT (Typ.) INRUSH CURRENT (Typ.) PROTECTION 48V 25A 0.5% 0.5% HOLD UP TIME (Typ.) VOLTAGE RANGE SPV-600-48 24V mi LOAD REGULATION SPV-600-24 I/P-FG:1.5KVAC O/P-FG:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH 116.4K hrs min. MIL-HDBK-217F (25 ) 170*120*93mm (L*W*H) 1.9Kg; 8pcs/15.5Kg/1.06CUFT 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. Derating may be needed under low input voltages. Please check the derating curve for more details. File Name:SPV-600-SPEC 2009-12-21 S P V- 6 0 0 600W Single Output with PFC Function Mechanical Specification Terminal Pin No. Assignment 58.3 Assignment AC/L AC/N FG PV POK R.C. G R.C. DC OUTPUT +V DC OUTPUT -V 2-M3 L=4mm max. 100 Air flow direction 2-M3 L=4mm max. na Pin No. 1 2 3 4 5 6 7 8~11 12~15 Unit:mm ry Case No.910A series 150 185 170 1 2 3 150 11.5 4 5 6 7 2-M3 L=4mm max. 2-M3 L=4mm max. mi 14 max. 8 9 10 11 12 13 14 15 9.5 Block Diagram 11.5 FAN EMI FILTER I/P ACTIVE INRUSH CURRENT LIMITING RECTIFIERS & P.F.C. POWER SWITCHING PFC fosc : 88KHz PWM fosc : 100KHz SIGNAL CONTROL RECTIFIERS & FILTER POK EXTERNAL VOLTAGE CONTROL eli O.L.P. DETECTION CIRCUIT PWM CONTROL Derating Curve PV +V -V RC.G. RC O.C.P. FG O.V.P. O.T.P. Output Derating VS Input Voltage 100 24V,48V 80 60 12V Pr Ta=25 100 90 80 70 50 LOAD(%) LOAD (%) 93 8 50 120 40 20 -20 0 10 20 30 40 45 50 AMBIENT TEMPERATURE ( ) 60 (HORIZONTAL) 60 50 40 88 100 115 135 155 230 264 INPUT VOLTAGE (V) 60Hz File Name:SPV-600-SPEC 2009-12-21 S P V- 6 0 0 600W Single Output with PFC Function series ry Control Terminal Instruction Manual POK(+) RCG(-) RCG RC N FG PV POK RCG RC +V +V +V +V -V -V -V -V + +V +V +V +V -V -V -V -V - + LOAD Remote Control Power ON: RCG and RC for short Power OFF: RCG and RC for open mi POK Signal is the voltage difference between "RCG" and "POK" pin output POK Signal for TTL level signal PSU turn on: 3.3V ~ 5.6V PSU turn off: 0V ~ 1V 1.External Voltage Control - LOAD POK Signal Function Manual N FG PV POK RCG RC L na L Vout 120 LOAD 80 PV 1~5.5V Non-Linear 60 40 20 Pr RCG OUTPUT CURRENT (%) -V 100 eli -V 100 +V OUTPUT VOLTAGE (%) +V 1 2 3 4 5 5.5 6 EXTERNAL VOLTAGE (DC) 80 60 40 20 V 20 40 60 80 100 110 120 V OUTPUT VOLTAGE (%) File Name:SPV-600-SPEC 2009-12-21