RFSOLUTIONS XNET8100

DIN RAIL TELEMETRY SYSTEM
XNET 8100
FEATURES
•
•
§
§
§
§
§
§
§
§
Operates on international licensed and licence free radio telemetry bands.
Range:
X8100 – 433 MHz 2km in free space, 0.2 - 0.5km in buildings
X8100 – 458 MHz 20km in free space, 1 – 3km in buildings
X8100 – 868 MHz 10km in free space, 0.7 – 2km in buildings
X8100 – GSM
World Wide GSM Mobile Phone Network
X8100 – LLM
Leased Telephone Line
Type approved to ETSI 300-220, ETSI 300-113, ETSI 300-683,
MPT1328, MPT1329, MPT1340, MPT1344
8 to 128 Digital Inputs
8 to 128 Digital Outputs, Voltage Free Contacts 30Vdc @ 1A
2 to 128 Analogue Inputs 0-20mA (Standard), 0-10V, 0-500mV.
(factory set option)
2 to 128 Analogue Outputs 0-20mA (Standard), 0-10V, 0500mV. (factory set option)
1 Serial Output Port for SCADA System
DIN Rail Mounted
Powered from 24Vdc (Standard), 110Vac, 240Vac.
Size: X8100 Control Module 160mm by 105mm by 60mm
X8100 I/O Modules
52mm by 105mm by 60mm
DESCRIPTION
The XNET Radio Data Network offers a cost effective and flexible means of transmitting analogue, digital, and
pulse counter data over large areas without the need for cables. A programmable modular approach allows the
user to configure the exact combination of IO required for a specific application from standard XNET modules.
A system can be as simple as a one-way link or as complex as a multi-drop network.
An XNET Control Module consists of:
1 Synthesised Radio Transceiver
8 Opto Isolated Inputs
8 Voltage Free Relay Outputs 1A, 30Vdc
2 Analogue Inputs ,12bit, 0 to 20mA or 0 to 5V
2 Analogue Outputs, 12 bit, 0 to 20mA or 0 to 5V
1 RS232 Serial Gateway Port
1 RS232 Programming Port
1 X-Bus Expansion Module Port
1 12V DC Power Supply for Transducers
Additional analogue and digital Input/Output modules can be connected to the Control Module by means of a
single 10-way ribbon cable. The modules can be located locally or up to 50 metres away.
X8100
Repeater
X8100 Analogue,
Digital & Serial
Data
X8100 Analogue,
Digital & Serial
Data
DS8100_1 Oct ‘01
X8100 Analogue,
Digital & Serial
Data
Expanded I/O
Expanded I/O
X8100 Analogue,
Digital & Serial
Data
SCADA
SYSTEM
Expanded I/O
©2001 R eg. N o. 227 4001, ENGLAND
X8100 Analogue,
Digital & Serial
Data
Page 1
DIN RAIL TELEMETRY SYSTEM
XNET 8100
SPECIFICATION
ABSOLUTE MAXIMUM RATINGS
Storage Temperature........................................ -30 to +85 Celsius
Operating Temperature .................................... -10 to +55 Celsius
Power Supply Voltage ..................................... +/- 35Vdc
Digital Inputs..................................................... +35Vdc to –5V
Analogue Inputs................................................ +35V to –5V
External Regulated Power Source .................... +100mA
DIMENSIONS
Length = 160mm Width = 80mm
ELECTRICAL
CHARACTERISTICS
Frequency Range
Channel Separation
Modulation
RF Power
Digital Inputs
Analogue Inputs
Height = 55mm
MIN
TYPICAL
130
400
860
12.5
5
7
0
0
GMSK
500
20
5
J, K
Volt Free Contacts
Analogue Outputs
Power Supply Voltage
Transmit Current
Receiver Current
Standby Current
0
0.5
14
110
80
410
150
2
20
5
90
420
160
3
MAX
DIMENSION
NOTE
180
500
960
25.0
MHz
MHz
MHz
KHz
VHF
UHF
UHF
500
30
20
10
mW
V
mA
V
30
125
20
10
30
240
120
440
180
4
Vdc
Vac
mA
V
Vdc
Vac
mA
mA
mA
mA
Current I/P
Voltage I/P
Thermocouple
At 1A
At 0.5A
12 bit resolution
DC PSU
AC PSU
10mW ERP
500mW ERP
XNET OPERATION
XNET control modules communicate with each other by means of time division multiplexing. All control
modules in the network are set by the user to the same RF frequency and then programmed with consecutive
node addresses. These are then used as time slots. The control module with time slot zero will start the
sequence by transmitting the status of its inputs with the addresses of the destination digital outputs. After
receiving data from the first Node a timing pulse will be sent from Node 0 to request data from the next Node.
When there is a time break of 6 time slots, the control module with time slot zero will start the sequence again.
The network can be easily expanded by adding control modules programmed with the next node address in
the sequence.
XNET control modules can be configured as repeaters thereby extending the range of a network over
geological obstacles.
DS8100_1 Oct ‘01
©2001 R eg. N o. 227 4001, ENGLAND
Page 2
DIN RAIL TELEMETRY SYSTEM
XNET 8100
CONNECTIONS
PIN
1
2
3
4
5
6
7
8
9
FUNCTION
0V
24V
REG 0V
REG 12V
AO2
AO1
AI2
AI1
IN COMM
DESCRIPTION
Power Supply -Ve
Power Supply +Ve
Transducer Regulated 0V
Transducer Regulated 12V at 100mA
Second Analogue Output (0-20mA)
OUT 1.2
First Analogue Output
(0-20mA)
OUT 1.1
Second Analogue Input (0-20mA)
IN 1.2
First Analogue Input
(0-20mA)
IN 1.1
Opto-Isolated Common ( 0V )
10
11
12
13
14
15
16
17
18
DI8
DI7
DI6
DI5
DI4
DI3
DI2
DI1
RLY COM
Opto-Isolated Input ( 7 - 30V)
Opto-Isolated Input ( 7 - 30V)
Opto-Isolated Input ( 7 - 30V)
Opto-Isolated Input ( 7 - 30V)
Opto-Isolated Input ( 7 - 30V)
Opto-Isolated Input ( 7 - 30V)
Opto-Isolated Input ( 7 - 30V)
Opto-Isolated Input ( 7 - 30V)
Output Relay Common Contact
IN 1.8
IN 1.7
IN 1.6
IN 1.5
IN 1.4
IN 1.3
IN 1.2
IN 1.1
19
20
21
22
23
24
25
26
27
ERR OUT
D08
D07
D06
D05
D04
D03
D02
D01
Communications Fail Indication
Relay Output 8 (1A at 30V )
Relay Output 7 (1A at 30V )
Relay Output 6 (1A at 30V )
Relay Output 5 (1A at 30V )
Relay Output 4 (1A at 30V )
Relay Output 3 (1A at 30V )
Relay Output 2 (1A at 30V )
Relay Output 1 (1A at 30V )
( 1A at 30V )
OUT 1.8
OUT 1.7
OUT 1.6
OUT 1.5
OUT 1.4
OUT 1.3
OUT 1.2
OUT 1.1
DS8100_1 Oct ‘01
©2001 R eg. N o. 227 4001, ENGLAND
DIRECTION
IN
IN
OUT
OUT
OUT
OUT
IN
IN
IN
IN
IN
IN
IN
IN
IN
IN
IN
IN
OUT
OUT
OUT
OUT
OUT
OUT
OUT
OUT
OUT
Page 3
DIN RAIL TELEMETRY SYSTEM
XNET 8100
PROGRAMMING
An XNET control module is programmed by a PC or Organiser configured as a dumb terminal. A three wire
asynchronous RS232 serial port (RD, TD, 0V) with a baud rate set at 9600 with 2 stop bits and no parity is
connected to the control module programming port. When the Esc key is pressed, a configuration menu will
be displayed. Control Parameter such as node number and serial data port can be selected along with
allocating the destination of the node input ports.
RADIO TRANSMISSION
Radio Frequency for the UK Licence Exempt Band
HEX
CHANNEL
RF
CHANNEL
RF FREQUENCY
MHZ
SW5
SW3
SW2
SW1
02H
A
458.525
ON
ON
ON
ON
04H
B
458.550
ON
ON
OFF
OFF
06H
C
458.575
ON
ON
OFF
ON
08H
D
458.600
ON
OFF
ON
OFF
0AH
E
458.625
ON
ON
ON
ON
0CH
F
458.650
ON
ON
OFF
OFF
0EH
G
458.675
ON
ON
OFF
ON
10H
H
458.700
ON
OFF
ON
OFF
12H
I
458.725
ON
OFF
ON
ON
14H
J
458.750
ON
OFF
OFF
OFF
16H
K
458.775
ON
OFF
OFF
ON
18H
L
458.800
ON
OFF
ON
OFF
1AH
M
458.825
ON
OFF
ON
ON
1CH
N
458.850
ON
OFF
OFF
OFF
1EH
O
458.875
ON
OFF
OFF
ON
20H
P
458.900
ON
OFF
ON
OFF
22H
Q
458.925
OFF
ON
ON
ON
Note: SW1,SW2,SW3,SW4 and SW5 refer to the DIL switches located inside the RF Module
To change the RF Frequency remove the top plate from the case and set the DIL switches.
NOTES
NOT USED
NOT USED
INPUT / OUTPUT MODULES
The number of inputs and outputs connected to an X8100 Transceiver can be expanded from 2 Analogue
Inputs/Outputs and 8 Digital Inputs/Outputs to 128 Analogue Inputs/Outputs and 128 Digital Inputs/Outputs by
means external modules:
X8101 Digital Input Module with 8 Opto-Isolated Inputs
X8102 Digital Output Module with 8 voltage free relay contacts rated at 1A , 30Vdc
X8103 Pulse Counter Output with 8 open collector outputs
X8104 Analogue Input Module with 4 Analogue Inputs, 12 bit resolution, 0-20mA (standard) 0-5V, 0-10V
X8105 Analogue Output Module with 4 Analogue Outputs, 12 bit resolution, 0-20mA (standard) 0-5V.
R. F. Solutions Ltd.,
Unit 21, Cliffe Industrial Estate,
Lewes, E Sussex, BN8 6JL, England
Tel +44 (0)1273 898 000
Fax +44 (0)1273 480 661
Email [email protected]
http://www.rfsolutions.co.uk
R F Solutions is a member of the Low Power Radio Assoc iation.
All Tr ademarks acknowledged and r emain the pr operty of the r espec ted owners.
Inform ation contained in this docum ent is believed to be accurate, however no representation or w arranty is given and R.F. Solutions Ltd. assum es no liability w ith respect to the accuracy of such
inform ation. Use of R.F.Solutions as critical com ponents in life support systems is not authorised except w ith express w ritten approval from R.F.Solutions Ltd.
DS8100_1 Oct ‘01
©2001 R eg. N o. 227 4001, ENGLAND