ASM-SENSOR 3455

3455
HIGH VOLTAGE INSULATION HiTESTER
Field Measuring Instruments
5KV
COMPACT
PERFORMANCE
Test Voltage 250V to 5kV
Insulation Resistance Measurement Up to 5TΩ
Measure insulation of high-voltage equipment (such as transformers, cables, and motors)
Automatically calculate and display PI (Polarization Index) and DAR (Dielectric
Absorption Ratio)
Step voltage testing, temperature compensation, temperature measurement,
and leakage current display
Data storage and USB interface
CAT IV 600V
2
Wide Range Test Voltage Settings
■ Features
Generate Test Voltages Across a Wide Spectrum
The 3455 can generate test voltages ranging from 250 V
to 5 kV. Settings can be made in steps as fine as 25 V. Very
high insulation resistance measurement up to 5 teraohms is
possible.
Ideal for All Insulation Diagnostic Applications
Functions such as automatic calculation and display of PI
(Polarization Index) and DAR (Dielectric Absorption Ratio),
as well as step voltage test, temperature compensation,
temperature measurement, and leakage current display make
the 3455 suitable for a variety of diagnostic applications.
Data Memory Function
The 3455 provides a manual storage function for 100 data
and a logging function for 10 data (360 times). The date and
time of measurement are also recorded.
USB Interface
Easily transfer data to a PC
via the USB interface using
our free PC application
software. The software also
features a convenient report
creation function.
safety regulations for category IV measurements (600
V). A shutter mechanism prevents simultaneous use of
measurement terminals and other terminals. Other safety
features include a voltage measurement
function, high-voltage warning
indicator, and auto discharge function.
Large, Easy to Read Display
The display is backlit and features a
logarithmic bar graph as an analog
type indicator in addition to the digital
readout.
Safety Foremost
The 3455 complies with
■ Primary Measurement Functions
❚ Insulation resistance measurement
❚ Leakage current display
Measurement voltage is selectable from 250 V, 500 V, 1.00
kV, 2.50 kV, and 5.00 kV. More finely graded settings are also
possible. When measurement is completed, the unit shows
the insulation resistance value, test voltage (setting and actual
output), leakage current, DAR, PI, and elapsed time.
When measuring insulation resistance, the instrument can be
switched to display leakage current. This is possible before,
during, and after measurement.
Insulation resistance measurement display
Display of leakage current during measurement
Actual output
voltage
Insulation
resistance value
Actual output
voltage
> flashes
if less than 1 nA
> flashes if
measurement
range was
exceeded
Elapsed time
leakage current value
STEP 5.0 kV step voltage test
Elapsed time
Insulation resistance value
❚ Step voltage test
In this type of test, the voltage is gradually raised and the insulation resistance
and leakage current change is measured. Two different step settings are
available: 500 V→ 1 kV → 1.5 kV → 2 kV → 2.5 kV and 1 kV → 2 kV → 3
kV → 4 kV →5 kV. The test time for each step can also be selected.
�����������
���������
���
�����
���
������
���
������
���
���
������
������
�������������������������������������������������������
3
Make Complete Diagnostic Tests of Transformers, Cables, Motors and Other Equipment
❚ PI and DAR display
Measurement time
PI: Polarization Index
DAR: Dielectric Absorption Ratio
The PI and DAR values which are used as an evaluation standard
for insulation are automatically calculated. With the insulation
resistance measurement start point as reference, the calculation
is performed as follows, using two resistance values obtained at
a prescribed time interval.
Formulas :
resistance value 10 min after start
resistance value 1 min after start
resistance value 1 min after start
resistance value 15 sec after start
resistance value 1 min after start
resistance value 30 sec after start
PI=
DAR 1min/15s =
DAR 1min/30s =
Right: first measurement
Left: second measurement
DAR value
Resistance value
Right: first measurement value
Left: second measurement value
Measurement time
First : 1 min ; Second : 10 min
PI value
Resistance value
Right: first measurement 30.0 GΩ
Left: second measurement 60.0 GΩ
■ Specifications
■ Measurement Items:
■ Insulation Resistance
Insulation resistance, leakage current, voltage, temperature
Test voltage: 250V to 5.00kV DC
Setting: Preset test voltages: 250 V, 500 V, 1 kV, 2.5 kV, 5 kV
Fine adjustment: possible in 25 V steps between 250 V
and 1 kV and in 100 V steps between 1 and 5 kV
Applies only when the measured resistance is equal to or
higher than the value gained from dividing the test voltage
(setting voltage) by the rated measurement current. Output
voltage is not guaranteed if measured resistance is lower than
[test voltage/rated measurement current].
Measurement current:
Test voltage
250V to 1.00kV
1.10kV to 2.50kV
2.60kV to 5.00kV
Measurement current
1mA
0.5mA
0.25mA
Rated measurement current tolerance: -0%, +10%
Short-circuit
current: 2 mA or less
Output voltage Display range: 0 to 999 V, 0.98 to 5.50 kV
Monitor function: Monitor accuracy: ± 5% rdg. ± 5 dgt.
Measurement range:
Resistance range:
(auto range)
Test voltage
250 V
500 V
1 kV
2.5 kV
5 kV
Measurement range
0.00MΩ to 250GΩ
0.00MΩ to 500GΩ
0.00MΩ to 1.00TΩ
0.00MΩ to 2.50TΩ
0.00MΩ to 5.00TΩ
Resistance range
10MΩ
100MΩ
1000MΩ
10GΩ
100GΩ
1000GΩ
5TΩ
Measurement range
0.00MΩ to 9.99MΩ
9.0MΩ to 99.9MΩ
90MΩ to 999MΩ
0.90GΩ to 9.99GΩ
9.0GΩ to 99.9GΩ
90GΩ to 999GΩ
0.90TΩ to 5.00TΩ
����������������
Insulation resistance
500G�
250G�
���������������
100G�
Measurement range
Up to [Test voltage / Resistance measurable at
100 nA]
Accuracy
±5%rdg.±5dgt.
[Test voltage / Resistance measurable at 100 nA]
to 500 GΩ
±20%rdg.±5dgt.
501GΩ to 5.00TΩ
±30%rdg.±50dgt.
(temperature and humidity range for guaranteed accuracy 0 to 28˚C, max. 90%rh, no condensation)
Response time: 15s max. (from measurement start to until guaranteed
accuracy display, no averaging)
■ Leakage Current (current measurement with test voltage being generated)
Measurement range: 1.00nA to 1.20mA
Current range
and accuracy:
Current range
10nA
100nA
1000nA
10µA
100µA
1mA
Measurement range
1.00nA to 9.99nA
9.0nA to 99.9nA
90nA to 999nA
0.90µA to 9.99µA
9.0µA to 99.9µA
90µA to 999µA,
0.90mA to 1.20mA
Accuracy
±15%rdg. ±1nA
± 15%rdg. ±5dgt.
±2.5%rdg. ±5dgt.
±2.5%rdg. ±5dgt.
±2.5%rdg. ±5dgt.
±2.5%rdg. ±5dgt.
(auto range, temperature and humidity range for guaranteed accuracy 0 to 28˚C, max. 90%rh, no condensation)
Response time: 15 s max. (from measurement start to until guaranteed
accuracy display, no averaging)
(temperature and humidity range for guaranteed
■ Voltage
accuracy 23±5 ˚C, max. 90%rh, no condensation)
Measurement range: DC ±50V to ±1.00kV , AC 50V to 750V
Frequency: DC/ 50Hz/ 60Hz
Accuracy: ±5%rdg. ±5dgt.
(for DC, absolute values of 1.01 kV and above are out
of guaranteed accuracy range)
Input impedance: Approx. 10 MΩ
Response time: 3 s or less
■ Temperature
Resistance range accuracy
5.00T�
2.50T�
1.00T�
Accuracy:
Measurement range
and Accuracy:
Measurement range
–10.0˚C to –0.1˚C
0.0˚C to 40.0˚C
40.1˚C to 70.0˚C
Accuracy
±1.5˚C
±1.0˚C
±1.5˚C
50.0G�
25.0G�
10.0G�
When using the 9631-05 temperature sensor, accuracy is
5.00G�
guaranteed only for 0.0 - 40.0 ˚C range
2.50G�
1.00G�
Response time: Approx. 100 s, including response of temperature
sensor models 9631-01 to 9631-05
��������������
100M�
10.0M�
(reference value, time until a 90% value of a
temperature change is shown)
1.00M�
0.00M�
250V
500V
1kV
2.5kV
Test voltage (setting value)
5kV
4
■ General Specifications
■ Specifications
■ Insulation Diagnosis
Temperature compensation: Result converted to insulation resistance at reference
temperature. 10 different temperature compensation
tables can be selected, according to insulation material
of measurement object. Reference temperature: 20˚C
or 40˚C by default, setting can be changed.
PI/DAR display: PI: Polarization Index
DAR: Dielectric Absorption Ratio
After insulation resistance measurement has started,
calculation is performed using two resistance values
obtained at prescribed time intervals.
Step voltage test: Measurement of insulation resistance while raising
voltage at specific intervals. Two voltage step patterns
can be selected.
STEP 2.5kV : 500V→1kV→1.5kV→2kV→2.5kV
STEP 5kV : 1kV→2kV→3kV→4kV→5kV
Voltage application time for each step: 30 s./1/2/5 m.
■ Supplementary Functions
Data memory: Manual recording: store up to 100 data , Data type:
standard measurement data/ temperature compensation
data/step voltage test data, Data logging: store
measurement value at preset intervals, available for
insulation resistance measurement only, Number of
data: 10, Number of logging instances: 360 times per
data, Recording interval: 15/30 s /1/2/5m, Data content:
date, time, measurement interval, temperature, set
voltage, actual output voltage × times, resistance ×
times, Additional functions: write mode, read mode, all
clear, selective clear, overwrite
Communication: Interface: USB ver 2.0 (full speed)
PC application software: transfer of memory data from
3455 to computer, data display, create graph,
3455 items that can be set/changed from computer:
date, time, PI time, step time for step voltage test,
report function
Other items: Temperature/humidity value input, timer, elapsed time
display, clock, averaging, data hold, auto discharge,
active voltage warning indication, hot conductor
warning indication, LCD backlight, auto power-off,
buzzer
9750 TEST LEAD
9751 ALLIGATOR CLIP
9459 BATTERY PACK
9631-01 TEMPERATURE SENSOR
Molded plastic, thermistor type
Operating temp. , humidity: 0 to 40˚C, max90%rh (no condensation)
10 to 40˚C, max. 80%rh for battery pack charging
Storage temp. , humidity: -10 to 50˚C, max 90%rh (no condensation)
Guaranteed accuracy period: 1 year
Operating environment: Indoors, up to 2000 m ASL
Measurement method: DC voltage application method (insulation resistance),
average value rectification method (voltage)
A/D conversion: Double integral method
Display: LCD, with backlight
Indication: Numeric: up to 999, Bar graph: insulation resistance
only, range 0 to 1 TΩ
Display update rate: Insulation resistance/leakage current: 1 time/second
(0.25 times/second when using averaging)
Output voltage monitor: 2 times/second
Voltage measurement: 4 times/second
Temperature measurement: 1 time/second
Power supply: LR6 (AA) alkaline battery × 6
9459 battery pack: 7.2 V DC (rechargeable, Ni-MH)
9753 AC adapter: rated input voltage 100 to 240 V AC,
rated output15VA
Max. power consumption: 15 VA (using AC adapter), 6 VA (using batteries or battery
pack) (5 kV generated, +/- terminals open, backlight off)
Continuous operation time: approx. 5 hours (with alkaline batteries)
(reference value) approx. 9 hours (with 9459 battery pack)
Max. input voltage: AC750Vrms, DC1000V
Max.rated voltage to ground: 600Vrms(CATIV) , 1000Vrms (CATIII)
Withstand voltage: 6880 V AC, 15 sec.
Dimensions & Mass: 260(W) × 250.6(H) × 119.5(D) mm, 2.8kg
Applicable standards: Safety: EN61010-1:2001, EN61010-031:2002
EMC:EN61326:1997+A1:1998+A2:2001
EN61000-3-2:2000
EN61000-3-3:1995+A1:2001
Accessories: 9750-01 TEST LEAD (RED) × 1, 9750-02 TEST
LEAD (BLACK) × 1, 9750-03 TEST LEAD (BLUE,
GUARD) × 1, 9751-01 ALLIGATOR CLIP (RED) × 1,
9751-02 ALLIGATOR CLIP (BLACK) × 1, 9751-03
ALLIGATOR CLIP (BLUE, GUARD) × 1, LR6 (size
AA) battery × 6, USB CABLE × 1, PC APPLICATION
SOFTWARE (download from HIOKI web site)
Options: 9631-01 TEMPERATURE SENSOR
(Thermistor, Molded type, Approx. 1 m)
9631-05 TEMPERATURE SENSOR
(Thermistor, Molded type, Approx. 6 cm)
9750-11 TEST LEAD (Red, Approx. 10 m)
9750-12 TEST LEAD (Black, Approx. 10 m)
9750-13 TEST LEAD (Blue, Approx. 10 m,GUARD)
BATTERY PACK
9459
AC ADAPTER
9753
9631-05 TEMPERATURE SENSOR
Molded plastic, thermistor type
9753 AC ADAPTER
DISTRIBUTED BY
HEAD OFFICE :
81 Koizumi, Ueda, Nagano, 386-1192, Japan
TEL +81-268-28-0562 / FAX +81-268-28-0568
E-mail: [email protected]
HIOKI USA CORPORATION :
6 Corporate Drive, Cranbury, NJ 08512 USA
TEL +1-609-409-9109 / FAX +1-609-409-9108
E-mail: [email protected]
Shanghai Representative Office :
1704 Shanghai Times Square Office
93 Huaihai Zhong Road
Shanghai, 200021, P.R.China
TEL +86-21-6391-0090, 0092
FAX +86-21-6391-0360
E-mail: [email protected]
All information correct as of Sep. 14, 2005. All specifications are subject to change without notice.
3455E3-59M-00P
Printed in Japan