DELTA EOE11010006

CliQ Din Rail Power Supply
24V 60W 1 Phase
DRP024V060W1AA
DRP024V060W1AA
60Watts
Total Power: 60Watts
Input Voltage: 85-264Vac
# of Output: Single
Model number
Reference no.
OUTPUT (DC)
DRP024V060W1AA
EOE11010006
Output power
Output voltage range
Output current
Residual ripple/peak switching (20MHz)
(@ nominal values)
Mains buffering at nominal load (typ.)
60W
22 - 28V
2.5A
< 50mV / < 240mVpp
Line regulation
< 0.5% typ. (@ 85 - 264Vac input, 100% load)
Load regulation
< 1% typ. (with rated input, 0 - 100% load)
> 20ms @ 115Vac, > 125ms @ 230Vac
INPUT (AC)
Input voltage range
Input frequency
Nominal current
85 - 264Vac (DC input range 120 - 375Vdc)
47 - 63Hz
1.1A @ 115Vac, 0.7A @ 230Vac
Efficiency
Power factor
> 85% typ.
Conform to EN61000-3-2 STD
Inrush current limitation I²t (+25°C) typ.
Leakage current
< 40A @ 115Vac, < 80A @ 230Vac
< 1mA
Special Features
- Ease of wire connection to
terminals
- Compact design for easy handling
- Overload protection
- Overvoltage protection
- Thermal protection
- Power boost 150% for 3 seconds
- Expected life time : 10 years
- Shock proof IEC60068-2-27
- Vibration IEC60068-2-6
- Cooling : Convection
- Operating Humidity : < 95%
- Redundancy : Yes
(with external ORing diode)
- RoHS compliant
MECHANICAL DESIGN
Case cover
Aluminium (AI5052)
Dimensions (L x W x H)
121mm x 32mm x 120mm
Unit weight / box
0.370kg
MTBF
> 800,000 hrs
Noise
Cooling
Sound pressure level (SPL) < 40dBA
Convection
Input terminal
M4 x 3
Output terminal
M4 x 2
Mounting rail
Standard TS35 mounting rail
Shock proof
Vibration
IEC60068-2-27
IEC60068-2-6
Protection structure
EN60950 meet IPX0
3 PET
E315355
R
L3M1
CliQ Din Rail Power Supply
24V 60W 1 Phase
DRP024V060W1AA
MECHANICAL DRAWING
Delta Electronics (Thailand)
Public Company Limited
909 Moo 4, E.P.Z.,
Bangpoo Industrial Estate,
Tambon Prakasa, Amphur
Muang Samutprakarn,
Samutprakarn 10280, Thailand
Tel: +662 709 2800
Fax: +662 709 2827
E-mail: [email protected]
www.deltaenergysystems.com
SAFETY / ENVIRONMENTAL
EMC / Emissions
Immunity
Safety standard
Voltage dips
Galvanic isolation
Operating ambient temperature
Storage temperature
Operating humidity
Note (*)
Class B / EN55022, CISPR22, Class B;
FCC Tilte 47; EN61204-3 (Class B on AC &
Class A on DC side), EN55022:2006 Class
B, EN61000-3-2:2006, EN61000-3-3:1995/
A1:2001/A2:2005
EN55024:1998/A1:2001/A2:2003
UL508, CSA C22.2 No.107.1-01,UL60950-1,
CSA C22.2 No.60950-1, IEC60950-1,
EN60950-1, EN50178, IEC62103 and
IEC60204-1
Conform to EN61000-4-11
Input to output: 4KVac
Input to ground: 1.5KVac
Output to ground: 1.5KVac
-20°C ~ 75°C *
-25°C ~ 85°C
< 95%
* Operating amb. < 0°C until -20°C derate
power by 1% / °C; Operating amb. > 50°C