EMERSON-NETWORKPOWER LPS170-M

Embedded Power for
Business-Critical Continuity
Rev. 12.08.08_113
LPS170-M Series
of 3
LPS170-M Series
Medical
175 Watts
Total Power:
Input Voltage:
# of Outputs:
100 - 175 Watts
85-264 VAC
120-300 VDC
Single
Electrical Specifications
Special Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Medical safety approvals
Active power factor correction
IEC EN61000-3-2 compliance
Wide Range Adjustable output
Remote sense on main output
Single wire current sharing
Power fail and remote inhibit
Built-in EMI filter
Low output ripple
Overvoltage protection
Overload protection
Thermal overload protection
DC power good
5 V standby output
12 V Aux output
Optional cover (-C suffix)
Safety
•
•
•
•
VDE
UL
CSA
CE
0750/EN60601-1 (IEC601)
UL2601
CSA 22.2 No. 601.1
Mark (LVD)
Input
Input ra­nge:
85-264 VAC; 120-300 VDC
Frequency:
47-67 Hz
Inrush current:
38 A max, cold start @ 25 °C
Efficiency:
EMI filter:
75% typical at full load
FCC Class B conducted
CISPR 22 Class B conducted
EN55022 Class B conducted
VDE 0878 PT3 Class B conducted
Power Factor:
0.99 typical
Safety ground
leakage current:
<250 µA @ 50/60 Hz, 264 VAC inputS
Output
Maximum power:
110 W convection (75 W with cover)
175 W with 30 CFM forced air
(130 W with cover)
Adjustment range:
2:1 wide ratio minimum
Standby outputs:
Hold-up time:
5 V @ 2 A regulated ±5%
20 ms @175 W load at nominal line
Overload protection:
Short circuit protection on all outputs.
Case overload protected @ 110-145% above peak rating
Overvoltage protection: 10% to 40% above nominal output
Aux output:
12 V @ 1 A -5 %, +10%
Embedded Power for
Business-Critical Continuity
Rev. 12.08.08_113
LPS170-M Series
of 3
Logic Control
Power failure:
TL logic signal goes high 100 - 500 msec after V1 output; It goes low
T
at least 4 msec before loss of regulation
Remote inhibit:
Requires contact closure to inhibit outputs
Remote sense:
ompensates for 0.5 V lead drop min. Will operate without remote
C
sense connected. Reverse connection protected.
Pin Assignments
Connector LPS17x
SK1
PIN 1
+12 V
PIN 2
5 V Standby
Pin 3
Common
Pin 4
V1 SWP
PIN 5
Common
PIN 6
+V1 sense
PIN 7
Sense common
PIN 8
Remote inhibit
PIN 9
DC poer good
PIN 10
POK
TB-1
COMMON
TB-2
Main output
PIN 1
GROUND
PIN 2
LINE
Pin 5
NEUTRAL
TTL logic signal goes high after main output is in regulation. It goes
low when there is a loss of regulation
DC - OK:
Environmental Specifications
Operating temperature:
Low temperature start:
0° to 50 °C ambient;
derate each output at 2.5% per degree from 50° to 70 °C
-20 °C
SK2
SK3
Temperature coefficient:
Storage temperature:
Electromagnetic
susceptibility:
Humidity:
±0.4% per °C
-40° to 85 °C
Vibration:
Three orthogonal axes, sweep at 1 oct/min, 5 min. dwell at four
major resonances 0.75G peak 5Hz to 500Hz, operational
>550,000 hours at full load and 25 °C ambient conditions
MTBF demonstrated:
Designed to meet IEC EN61000-4, -2, -3, -4, -5, -6, -8, -11 Level 3
Operating; non-condensing 5% to 95%
Output
Voltage
AC Input (SK4):
Molex 09-50-8051 (USA)
Molex 09-91-0500 (UK)
PINS: 08-58-0111
DC Outputs (SK3): Molex 19141-0058
Control Signals
(SK1):
Molex 90142-0010 (USA)
PINS: 90119-2110 or
Amp: 87977-3
PINS: 87309-8
Emerson Network Power Connector Kit #70-841-016
Ordering Information
Model
Number
Mating­ Connectors
Minimum Maximum Load with
Load
Convection Cooling
Maximum Load
with 30CFM Peak Load 1 Regulation 2
forced Air
Ripple P/P
(PARD)3
LPS172-M 5 V (2.5 - 6 V)
0A
22 A
35 A
38 A
±2%
50 mV
LPS173-M 12 V (6 - 12 V)
0A
9.1 A
15 A
16.5 A
±2%
120 mV
LPS174-M 15 V (12 - 24 V)
0A
7.3 A
12 A
13.2 A
±2%
<1%
LPS175-M 24 V (24 - 54 V)
0A
4.5 A
7.5 A
8.2 A
±2%
<1%
1. Peak current lasting <30 seconds with a maximum 10% duty cycle.
2. At 25 °C including initial tolerance, line voltage, load currents and output voltages adjusted to factory settings.
3. Peak-to-peak with 20 MHz bandwidth and 10 µF in parallel with a 0.1 µF capacitor at rated line voltage and load
ranges.
4. Remote inhibit resets OVP latch.
Note: -C suffix added to the model number indicates cover option.
Notes:
1. Specifications subject to change without notice.
2. All dimensions in inches (mm), tolerance is ±0.02”.
3. Specifications are for convection rating at factory settings unless
otherwise stated.
4. Mounting screw maximum insertion depth is 0.12”.
5. Warranty: 2 year
6. Weight: 1.8 lb / 0.85 kg
Embedded Power for
Business-Critical Continuity
Mechanical Drawing
1
5
6
­Americas
+
5810 Van Allen Way
Carlsbad, CA 92008
USA
Telephone:+1 760 930 4600
Facsimile: +1 760 930 0698
-
10
SK1
SK3
Europe (UK)
1.50
(38.1)
Voltage Adj
POT
Rev. 12.08.08_113
LPS170-M Series
of 3
0.75
(19.0)
0.95
(24.0)
Waterfront Business Park
Merry Hill, Dudley
West Midlands, DY5 1LX
United Kingdom
Telephone:+44 (0) 1384 842 211
Facsimile: +44 (0) 1384 843 355
0.55
(14.0)
Asia (HK)
14/F, Lu Plaza
2 Wing Yip Street
Kwun Tong, Kowloon
Hong Kong
Telephone:+852 2176 3333
Facsimile: +852 2176 3888
6.61
(168.0)
7.4
(188.0)
For global contact, visit:
8.5
(216.0)
www.powerconversion.com
techsupport.embeddedpower
@emerson.com
While every precaution has been taken to ensure
accuracy and completeness in this literature, Emerson
Network Power assumes no responsibility, and disclaims
all liability for damages resulting from use of this
information or for any errors or omissions.
5 3 1
Emerson Network Power.
The global leader in enabling
business-critical continuity.
M3
AC Power
#6-32
Connectivity
SK4
DC Power
0.88
(22.2)
1.07
(27.2)
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
4.25
(108.0)
2.50
(63.5)
2.11
(53.5)
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
#6-32(8 PLACES)
M3(8 PLACES)
EmersonNetworkPower.com
Emerson Network Power and the Emerson
Network Power logo are trademarks and
service marks of Emerson Electric Co. ©2008 Emerson Electric Co.