Velociti® Series AOM-2RF Description Addressable Output Relay Control Module The Gamewell-FCI Velociti® Series, addressable output relay control module (AOM-2RF) allows a Gamewell-FCI analog addressable fire alarm control panel to switch discrete relay contacts by code command. The relay provides two isolated sets of Form-C contacts which transfer simultaneously. Circuit connections to the relay contacts are not supervised by the module. The Velociti® Series use a communication protocol that substantially increases the speed of communication between the SLC devices and certain Gamewell-FCI analog addressable fire alarm control panels. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and concentrates on the single device. The net result produces a superior response speed up to five times greater than earlier designs. The AOM-2RF Module is designed for installation in the signaling line circuit of any Gamewell-FCI analog addressable fire alarm control panel. The module contains a panel controlled LED. The AOM-2RF is designed to mount in a 4” (10.16 cm) square junction box 2 1/8” (5.53 cm) deep. Table 1 lists the relay contact ratings. Current Rating 3A 2A 0.9A 0.5A 0.5A Maximum Voltage 30 VDC 30 VDC 110 VDC 125 VAC 30 VDC 1A 30 VDC 0.5A 125 VAC 0.7A 75 VAC Load Description Resistive Resistive Resistive Resistive Inductive (L/R=5ms) Inductive (L/R=2ms) Inductive (PF=.35) Inductive AOM-2RF Features • Listed under UL® Standard 864. • Offers two sets of Form “C” contacts. • Provides visual rotary, decimal switch addressing (01-159). • Includes a bicolor LED that flashes green whenever the module is addressed, and lights steady red upon activation.* • Designed as a compact size to allow easy installation. Note: Only the red LED is operative in panels that do not operate in Velociti® mode. Application Non-Coded Coded Non-Coded Non-Coded Coded Specifications Coded Dimensions: Non-Coded Ordering Information Non-Coded Part Number Description AOM-2RF Addressable output relay control module Table 1: Relay Contact Ratings Supervisory current: Alarm current: Operating temperature: Relative humidity: .000375 amps. .0065 amps. 32° to 120° F (0° to 49° C) 10 to 93% relative humidity (non-condensing) 4 1/2” H x 4” W x 1 1/4” (11.4 x 10.2 x 3.2 cm) SIGNALING FM UL® is a registered trademark of Underwriter’s Laboratories Inc. Velociti® Series is a registered trademark of Honeywell International Inc. APPROVED MEA Approved S1913 3023594 219-02-E Vol. VI 7300-1703:0102 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com 9020-0625 Rev. F page 1 of 1 ©2014 Honeywell International Inc. All rights reserved.