GAMEWELL-FCI FC-2104

FC-2224
TWO-ZONE PANEL
CONVENTIONAL FIRE ALARM CONTROL
DESCRIPTION
The FC-2224 Fire Alarm Control panel is a proven, versatile, two-zone control with space to accommodate an optional digital communicator. It meets the requirements of
NFPA Standard 72 for Central Station, Protected Premises,
and Remote (DACT) Supervising Station Fire Alarm Systems. It is Listed to UL Standard 864, inherently power limited and meets all UL transient immunity requirements.
The many features of the FC-2224 control provide a cost
effective approach to systems design, and allow a great degree of flexibility in one enclosure. These features include
two (2) Class B, Style B initiating circuits and two (2) Class
B, Style Y notification appliance circuits, rated at 1.25 amps
each. Notification appliance circuits can be configured as
silenceable or non-silenceable.
DIP switch programming is used throughout, eliminating
the need for computers and associated software.
A time delay of 30, 60, or 90 seconds is available for
waterflow switches.
The control is housed in a red steel enclosure with a window offering a view of LEDs displaying the status of vital
functions. The surface mounted enclosure, with its slim appearance (3 3/8-inch depth) is designed to blend with any environment. Space is available for two (2) B-7R batteries.
Supervision of vital components, plug-in modules, functional switches and standby batteries is provided.
The optional digital communicator includes a wide range
of selectable transmission formats to communicate to most
central stations. Other features of the communicator are: A
line-active indicator for each of two phone lines, “Kiss-Off”
signal LED, dual “low telephone voltage detect” circuitry
and programmable event codes per format. The FC-2224 is
programmable for AC power loss delay required for DACT
operation.
An optional serial annunciator driver allows remote alarm
annunciation to as many as four (4) Model FC-2866 remote
annunciators.
Other optional modules include the FC-2880 I/O module
which provides 34 pre-defined open collector outputs that
can be used to drive LEDs or relays.
FEATURES
·
·
·
·
·
·
·
·
·
Inherently Power Limited
DIP Switch Programming
Choice of Output Patterns Including
ANSI S3.41
Programmable Time Delay for
Waterflow Switches
Periodic Trouble Reminder
Walk Test Feature
Optional Digital Communicator with
Multiple Reporting Formats
Serial Annunciator Output (Optional)
Surface Mount Technology
AGENCY APPROVALS
UL
CSFM
S1869
Approved
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice.
© 2000 All Rights Reserved
16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099
An ISO 9001 Certified Company
9020-0483/Ver. 1.5
FC-2880 Annunciator Driver
Module
FC-2884 Serial Driver Module
FC-2866 Remote Zone
Annunciator
FC-2104 Digital Alarm
Communicator Transmitter
CHARACTERISTICS AND DIMENSIONS
Supervisory current
Alarm current
Operating temperature
Relative humidity
Dimensions
`
.050 amp.
.250 amp.
32 - 120o F (0 - 49o C)
85% (non-condensing)
15 1/8”H x 12 13/16” W x 3 3/8” D
(38.4 cm x 33 cm x 8.5 cm)
ORDERING INFORMATION
Part Number
150-00001
Model
FC-2224
Description
Two-zone Control, 120 VAC
151-00001
151-00003
151-00004
151-00005
151-00019
151-00017
151-00018
FC-2884
FC-2880Å
FC-2866Å
FC-2104
2190
5230
7860
Serial Driver Module
Annunciator Driver Module
Remote Zone Annunciator w/reset and silence switches
Digital Alarm Communicator Transmitter
Cabinet for FC-2104 DACT (optional)
Programmer for FC-2104 DACT
Cable w/spade lugs for connection
to Telco RJ31X plug. (Optional)
Quick connect cable to connect
5230 Programmer to FC-2104 DACT
FC-2224PC
7628
Replacement PC board
UL Listed EOL resistor
151-00020
151-00007
151-00011
151-00012
Å
120 VAC Transformer (replacement)
230 VAC, 50 Hz Transformer (optional)
Requires one (1) FC-2884
FC-2104 DACT reporting formats are:
SIA 8 or 20
SK 3/1 1,400 or 2,300 Hz
Contact ID
SK 4/2
BFSK 1,400 or 2,300 Hz
9020-0483