SNAC-4 - Gamewell

SNAC-4
SUPPLEMENTARY NOTIFICATION
APPLIANCE CIRCUIT PANEL
DESCRIPTION
The Supplementary Notification Appliance Circuit Panel
(SNAC-4) provides four, (4), 24 VDC Class A, Style Z or
Class B, Style Y notification appliance circuits at 1.5 amperes each, or two circuits at 3 amperes each, with a total capacity of 6 amperes per panel. These circuits may be
activated in groups of two or four by connection to normally
open dry contacts or existing Class A or Class B notification
appliance circuits with operating voltages ranging from 12 to
32 VDC. . Either non-coded operation, coded operation, temporal pattern or a combination is possible.
The SNAC-4 operates from 120/240 VAC input and contains its own battery charger, capable of maintaining a set of 7
A/H batteries. It is supervised for ground fault, overcurrent,
open circuits and low battery conditions.
The regulated power supply allows the SNAC-4 to be compatible with any Listed, nominal 24 VDC notification appliances.
Ground fault, battery and circuit trouble conditions in the
SNAC-4 automatically open the notification appliance circuit used to activate the SNAC-4, transmitting a trouble signal to the main fire alarm control panel. The ground fault
detection circuit may be disabled.
The unit contains a set of dry, jumper programmable (N/O
or N/C) trouble actuated contacts, rated 1 amp. @ 24 VDC
(resistive). Transfer of these contacts for AC power failure is
delayed for a period of ten (10) hours. This delay feature may
be disabled.
A power limited, non-resettable auxiliary power output of
1.75 amps is available if the panel is arranged via jumper to
disconnect itself from the batteries during AC power failure.
An output of 0.150 amp. is available when the SNAC-4 is
connected to a control panel requiring 24 hr. standby. The
current is reduced to .050 amp. when 60 hour standby is required.
FEATURES
• Switching Technology Power Supply
• UL Listed as a Fire Alarm Accessory for Use
•
•
•
•
•
•
APPROVALS
UL
Factory Mutual
NYC
CSFM
•
S1949
3001096
MEA 239-98-E
7300-0694:191
With any FCI or other UL Listed Fire Alarm
Control
Four (4) Class A (Style Z) or Class B
(Style Y) Notification Appliance Circuits
High Current Output (1.75 Amp.)
Compact Construction
Simple Installation
Integral Ground Fault Detection
Programmable Trouble Contacts (N/O
or N/C) with Optional Delayed AC Failure Indication
Compatible With any Listed 24 VDC
Notification Appliances
TECHNICAL INFORMATION
Operating power
Standby battery circuit
Supervisory current
Alarm current
Alarm output
Dimensions
Operating temperature
Relative humidity
120 VAC, 3 amp., or 240 VAC, 2 amp., 50/60 Hz, (Jumper selectable)
24 VDC (nominal) 7 ampere/hours, max.
0.060 amp. to 0.235 amp.
0.120 amp. (excluding notification appliances)
6.0 amp. max. @ 24 VDC
14" H x 14" W x 3 1/2" D (35.56 x 35.56 x 8.89 cm )
32o to 120o F (0o to 49o C)
85% (non-condensing)
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed
by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice.
1998 All Rights Reserved
16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099
An ISO 9001 Certified Company
9020-0449/Ver. 1.6