GAMEWELL-FCI XAL-53

September 1, 2006
CS-2506
XAL - 53
Explosion-Proof Pull Station
APPLICATIONS
California
State Fire
Marshal
7150-1439:100
XAL-53 fire alarm stations are suitable for:
• Hazardous areas due to the presence of flammable
gases or vapors, combustible dusts or easily ignitable fibers or flyings.
• Installation at petroleum refineries, chemical and petrochemical plants, storage areas, and other processing facilities where hazardous substances are
handled and stored.
• Areas where emergency control of fire alarm or signal circuits is required.
E50498
FEATURES
CE69
• Enclosure is made of copper-free aluminum alloy.
• Conduit openings are 3/4" (19.05 mm) NPT feedthrough.
• Red, textured powder epoxy paint finish is standard
on box and cover and provides high visibility for alarm
station.
• Universal (1) normally open and (1) normally closed
contact furnished standard.
• Bilingual nameplates included per CSA requirement.
• Internal ground screw is standard.
• Wiring range is #12 AWG through #24 AWG, solid
or stranded.
CSA
5274pho.jpg
LR31085
XAL-53
Pull Ring
OPERATION
XAL-53
Dimensions
The alarm station is activated by lifting the front cover
and pulling down ring. This quick, easy-to-use twostep process prevents unintentional operation. Operator is reset by depressing shaft and returning plate to
original position.
HAZARDOUS AREA
CLASSIFICATIONS
•
•
•
•
Class I, Divison 1 and 2, Group C and D.
Class II, Division 1 and 2, Group E, F, and G.
Class III, Hazardous Locations.
NEMA 7CD, 9EFG.
5274acdc.tbl
CONTACT BLOCK
RATING
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com
5274dim1.tif
A
C
D C
Volts
Make
Amperes
VA
Break
Amperes
VA
Continuous
Continuous
Make
Carrying
Carrying
Volts
Break
Amperes
Amperes
120
60
7200
6.0
720
10
125
1.10
10
240
30
7200
3.0
720
10
250
0.55
10
480
15
7200
1.5
720
10
600
0.20
10
600
12
7200
1.2
720
10
Specifications and wiring information are provided for information only and are believed
to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring instructions
shipped with the product shall always be used for actual installation.
For more information, contact Gamewell-FCI, a Honeywell company.
CS-2506 • 09/01/06 — Page 1 of 2
OPERATIONAL DATA
This enclosure is made of cast, copper-free aluminum alloy. It is suitable for: Class I, Groups C and D; Class II,
Groups E, F, and G; and Class III hazardous locations. All
installations must comply with applicable local and/or National Electrical Code.
CONTACT ARRANGEMENT
NOT ACTIVATED
POSITION
5274con1.wmf
During installation, DO NOT use looped wire under terminals. Break wire run to provide supervision of connections.
Like all electromechanical devices, these control stations
require occasional maintenance. Parts may wear out or
become defective due to adverse environmental conditions.
See Maintenance Data below.
MAINTENANCE DATA
ACTIVATED
POSITION
5274con2.wmf
Disconnect this device from the supplying circuit before removing the cover.
1) To prevent corrosion, lubricant should be occasionally
applied, as follows:
• Killark® “LUBG” lubricant to box/cover flanges.
• Dow Corning® Molykote® 33 Grease, light consistency,
to operator shaft.
2) Keep all flanges clean and free of scratches.
3) Some internal service parts are available. Consult the
Killark® factory for parts breakdowns.
KILLARK® is a registered trademark of Hubbell®. Dow Corning® and Molykote® are registered trademarks of Dow Corning Corporation.
PRODUCT LINE INFORMATION
XAL-53 Pull station, explosion-proof, N/O and N/C contacts.
SBA-10 Backbox.
Page 2 of 2 — CS-2506 • 09/01/06