GAMEWELL-FCI PIM-SS

PIM-SS
Features
Ten-Input Monitor Module
• Ten addressable Class B or
five addressable Class A
initiating device circuits.
Description
• Removable 12 AWG (3.25
mm²) to 18 AWG (0.9 mm²)
plug-in terminal blocks.
Gamewell’s SmartScanTM PIM-SS teninput monitor module provides an
interface between a control panel
and normally open contact devices
in intelligent alarm systems such as
conventional pull stations and heat
detectors.
SS-M with SS-B6 base
The first address on the PIM-SS is
set from 01 to 90 and the remaining
modules are automatically assigned
to the next nine higher addresses.
Provisions are included for disabling
a maximum of two unused addresses.
The supervised state (normal, open,
or short) of the monitored device is
sent back to the panel. A common SLC input is used for all modules, and the
initiating device loops share a common supervisory supply and ground — otherwise each monitor operates independently from the others.
Each PIM-SS module has panel-controlled green LED indicators. The panel can
cause the LEDs to blink, latch on, or latch off.
Product Line Information
PIM-SS: Ten-input monitor module.
BB-25: Optional cabinet for up to six modules mounted on CHS-6 chassis (below). Dimensions, DOOR: 24.0" (60.96 cm) wide x 12.632" (32.0852 cm) high, x
1.25" (3.175 cm) deep, hinged at bottom; BACKBOX: 24.0" (60.96 cm) wide x
12.550" (31.877 cm) high x 5.218" (13.2537 cm) deep.
CHS-6: Chassis, mounts up to six modules in a BB-25 cabinet.
PIM-SS
CS-2468
09/01/06
• Use with Gamewell’s IF602,
610, 632, 654 and 658 with
SmartScan™ loop card.
• Status indicators for each
point.
• Unused addresses may be
disabled.
• Rotary address switches.
• Class A or Class B operation.
• Mount one or two modules in a
BB-XP cabinet (optional).
• Mount up to six modules on a
CHS-6 chassis in a BB-25
cabinet (optional).
• Mounting hardware included.
Listings
Listings and approvals below
apply to the PIM-SS Ten-Input
Monitor Module. In some
cases, certain modules may
not be listed by certain approval agencies, or listing may
be in process. Consult factory
for latest listing status.
• UL Listed: file S521.
• CSFM approved:
file 7300-1288:169.
• MEA approved:
file 368-01-E Vol. II.
Page 1 of 2
Specifications
Dimensions: 6.8" (172.72 mm) high x
5.8" (147.32 mm) wide x 1.25" (31.75
mm) deep.
Power-limited circuits must employ
type FPL, FPLR, or FPLP cable as required by Article 760 of the NEC.
Shipping weight: 1.1 lb. (0.499 kg) including packaging.
PIM-SS is shipped in Class B position;
remove shunt for Class A operation.
Temperature range: 32°F to 120°F (0°C
to 49°C) for UL applications
Mounting options: CHS-6 chassis, BB25 cabinet, or suitably grounded metallic
cabinet.
Maximum IDC wiring resistance: 1500
ohms.
Humidity: 10% to 85% noncondensing
for UL applications
Wire gauge: 12 AWG (3.25 mm²) to 18
AWG (0.9 mm²).
Maximum IDC current: 1 mA.
Standby current: 3.5 mA (SLC current
draw with all addresses used; if some
addresses are disabled, the standby current decreases).
Alarm current: 55 mA (assumes all ten
LEDs solid ON).
Maximum IDC voltage: 12 VDC.
FIGURE 1:
Typical Initiating Device Circuit
Configuration —
Class B, Style B.
NOTE: Any number of UL-Listed contact
closure devices may be used. DO NOT MIX
fire alarm initiating and supervisory devices
on the same initiating device circuit. Install
contact closure devices per manufacturer’s
installation instructions.
52347w1.wmf
52347w2.wmf
FIGURE 2:
Typical Fault-Tolerant Initiating
Device Circuit Configuration —
Class A, Style D.
NOTE: Any number of UL-Listed contact closure
devices may be used. DO NOT MIX fire alarm initiating and supervisory devices on the same initiating device circuit. Install contact closure devices
per manufacturer’s installation instructions.
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com
A Honeywell Company
© 2006 Gamewell-FCI
Specifications and wiring information are provided for information only and are believed
to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring instructions
shipped with the product shall always be used for actual installation. For more
information, contact Gamewell-FCI.