GAMEWELL-FCI SS-I

SS-I
Features
Intelligent Addressable Plug-In
Ionization Smoke Detector
Description
Gamewell’s
intelligent
TM
SmartScan plug-in smoke
detector with integral communication provides features
that surpass conventional detectors. Detector sensitivity
can be programmed in the
control panel software. Sensitivity is continuously moni6934pho1.jpg
tored and reported to the
panel. Point ID capability alSS-I with SS-B6 base
lows each detector’s address
to be set with decade address
switches, providing exact detector locations for selective maintenance when chamber contamination reaches
an unacceptable level. The SS-I ionization detector incorporates a unique singlesource, dual-chamber design to respond quickly and dependably to a broad range of
fires. The SS-I detector is compatible with Gamewell’s 602, 610, 632, 654 and 658
FACPS with a SmartScanTM SLC.
Installation
• Sleek, low-profile design.
• Addressable-analog communication.
• Stable communication technique
with noise immunity.
• Low standby current.
• Two-wire SLC connection.
• Rotary, decimal addressing (1 –
99).
• Optional remote, single-gang LED
accessory (RA400Z).
• Dual LED design provides 360°
viewing angle.
• Visible bicolor LEDs blink green
every time the detector is addressed, and illuminate steady red
on alarm.
• Remote test feature from the
panel.
• Built-in functional test switch
activated by external magnet.
• Built-in tamper-resistant feature.
• Sealed against back pressure.
• Constructed of off-white
Bayblend®, designed to commercial standards, and offers an
attractive appearance.
• 94-5V plastic flammability rating.
• SEMS screws for wiring of the
separate base.
• Optional relay, isolator, or sounder
bases.
• Backward-compatible.
The SS-I plug-in detector uses a separate base to simplify installation, service, and
maintenance. A special tool allows maintenance personnel to plug in and remove
detectors without using a ladder.
Mount base on an electrical backbox which is at least 1.5" (3.81 cm) deep. Suitable
mounting back boxes include:
• 4.0" (10.16 cm) square box.
• 3.5" (8.89 cm) or 4.0" (10.16 cm) octagonal box.
• Single-gang box (except for relay or isolator base).
• With B501BH or B501BHT base, use a 4.0" (10.16 cm) square box.
• With B224RB or B224BI base, use a 3.5" (8.89 cm) octagonal box, or a 4.0"
(10.16 cm) octagonal or square box.
NOTES: 1) Because of the inherent supervision provided by the SLC loop, end-ofline resistors are not required. Wiring “T-taps” or branches are permitted for Style 4
(Class “B”) wiring. 2) When using relay or sounder bases, consult data sheet CS2464 (SS-LI) for device limitations between isolator modules and isolator bases.
Bayblend® is a registered trademark of Bayer Corporation.
SS-I CS-2459 09/01/06
Page 1 of 2
Listings
Listings and approvals below
apply to the SS-I Intelligent Plug-In
Ionization Smoke Detector. In
some cases, the detector may not
be listed by certain approval
agencies, or listing may be in
process. Consult factory for latest
listing status.
• UL Listed: file S1195.
• CSFM approved:
file 7271-1288:168.
Specifications
Product Line Information
SS-I: Low-profile intelligent ionization
M02-09-00: Test magnet with telescope
smoke detector. Must be mounted to one stick.
of the bases listed below.
XR2B: Detector removal tool. Allows
Bases:
installation and/or removal of SS-I
detector heads from base in high ceiling
SS-B6: Standard U.S. low-profile base,
installations.
UL Listing.
B501BP: Standard European flangeless T55-127-000: Detector removal tool
without pole.
base, pkg. of 10.
XP-4: Extension pole for XR2B. Comes
B501BH: Sounder base, includes B501
in three 5-ft. sections.
base above.
Size
2.1" (5.3 cm) high x 4.1" (10.4 cm)
diameter installed in B501 base, 6.1"
(15.5 cm) diameter installed in SS-B6
base.
Shipping weight
5.4 oz. (154 g).
Operating temperature
0°C to 49°C (32°F to 120°F).
UL-Listed velocity range:
B501BHT: Same as B501BH, but
Detector Guards:
ION: 0 – 1200 ft./min. (365.76 m/min.).
includes temporal sounder.
NOTE: The following guards are not UL
Relative humidity
B224RB: Intelligent relay base.
listed with the SS-I detectors. Consult AHJ. 10% – 93% noncondensing.
STI 9601: Low-profile, flush-mount smoke
Accessories:
DETECTOR SPACING:
detector guard, wire.
RA400Z: Remote LED annunciator. 3 –
Gamewell recommends spacing detec32 VDC. Fits U.S. single-gang electrical STI 9602: Low-profile, surface-mount,
tors in compliance with NFPA 72. In low
smoke detector guard, wire.
box. Supported by SS-B6 and B501
airflow applications with smooth ceilings,
STI 9609: High-profile, flush-mount, smoke space detectors 30 feet (9.144 m). For
bases only.
SMK400: Surface mounting kit provides detector guard, wire.
specific information regarding detector
STI 9605: High-profile, surface-mount,
for entry of surface wiring conduit. For
spacing, placement, and special applicasmoke detector guard, wire.
use with B501 base only.
tions, refer to NFPA 72. System Smoke
STI 9604: Flush-mount heat detector
RMK400: Recessed mounting kit. For
Detector Application Guide, document
guard, wire.
use with B501 base only.
A05-1003, is available at
systemsensor.com.
SMB600: Surface mounting kit for use
STI 9610: Surface-mount heat detector
with SS-B6.
guard, wire.
ELECTRICAL SPECIFICATIONS:
BCK-200B: Black detector covers, box of STI-8200-SS: Flush-mount stainless
Voltage range
10. Use with SS-I.
steel smoke detector guard
15 - 32 volts DC peak.
M02-04-01: Test magnet.
STI-8230-SS: Surface-mount stainless
Standby current (max. avg.)
steel smoke detector guard
200 µA @ 24 VDC (without communication); 300 µA @ 24 VDC (one communication every 5 seconds with LED
enabled).
LED current (max.)
6.5 mA @ 24 VDC (“ON”).
Wiring Diagrams
BASES AVAILABLE:
SS-B6: 6.1" (15.5 cm) diameter.
B501: 4.1" (10.4 cm) diameter.
B501BH or B501BHT: Sounder base
assembly. Includes B501 base.
B224RB Relay Base: Screw terminals:
up to 14 AWG (2.0 mm²). Relay type:
Form-C. Rating: 2.0 A @ 30 VDC
resistive; 0.3 A @ 110 VDC inductive; 1.0
A @ 30 VDC inductive. Dimensions:
6.2" (15.748 cm) x 1.2" (3.048 cm).
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com
A Honeywell Company
© 2006 Gamewell-FCI
Address dial on back of detector.
B224BI Isolator Base: Dimensions:
6.2" (15.748 cm) x 1.2" (3.048 cm).
Maximum: 25 devices between isolator
bases.
Specifications and wiring information are provided for information only and are believed
to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring instructions
shipped with the product shall always be used for actual installation. For more
information, contact Gamewell-FCI.
Page 2 of 2
SS-I
CS-2459
09/01/06