Intelligent Bases

Intelligent
Bases
Description
B501, B224RB, B224BI, and B210LP,
Mounting Kits, and Accessories
The Intelligent Velociti® and CLIP™ mounting bases
and kits provide a variety of ways to install
Gamewell-FCI detectors in any application. These
mounting bases are non-addressable and are available in both the Velociti and Clip protocols. The intelligent detectors can be mounted in any of the
following, depending on the junction box selection
(see Table 1 - Junction Box Selection Guide).
• flanged bases
• flangeless bases
• plastic rings
Relay, isolator, and sounder bases can be used to
meet local code requirements. Relay bases provide
one Form-C contact relay for the control of auxiliary
functions such as door closure and elevator recall.
Isolator bases allow loops to continue to operate
under fault conditions and automatically restore
when the fault is removed. Sounder bases are available in a combination temporal 3 and continuous
tone model.
The Intelligent Bases provide a variety of mounting
options to meet your installation challenges. The
bases come in flanged or flangeless versions so that
you can mount the bases to a variety of junction
boxes. See Table 1 for the Junction Box Selection
Guide. You can use the SMB600 surface mounting
box to mount the following bases:
• B224RB relay base
• B210LP relay base
• B224BI isolator base
System Temperature and Humidity Ranges:
These bases comply with the NFPA requirements for
operation at 0°C to 49°C (32°F to 120°F); and at a
relative humidity (non-condensing) of 85% at 30°C
(86°F) per NFPA, and 93% ± 2% at 32°C ± 2°C
(89.6°F ± 1.1°F) per ULC®. However, the useful life
of the system’s standby batteries and the electronic
components may be adversely affected by extreme
temperature ranges and humidity. Therefore, it is
recommended that the bases and all peripherals be
installed in an environment with a nominal room temperature of 15°C to 27°C (60°F to 80°F).
Figure 2 B210LP Mounting Base
Figure 3 B224BI Mounting Base
Figure 4 B224RB Mounting Base
Features
All sounder bases offer the following features.
• Complies with UL Standards 268 and 464.
• Includes the following three types of bases that
comply with local code requirements:
- Relay
- Isolator
- Sounder
• Offers temporal and non-temporal pattern
versions.
Relay Base Feature
•
Relay bases provide one Form-C contact relay.
Isolator Base Feature
•
Specifications
Figure 1 B501 Mounting Base
Isolator bases include data communications
lines to operate under fault condition.
Installation Features
The bases offer the following flexible installation
characteristics.
• Has multiple accessory options.
• Includes an installation mounting kit and
accessories for several types of model options.
• Supports 12-24 AWG gauge wire ranges to
provide the bases with flexible installation.
• Contains bases that enable quick and secure
detector plug-in.
• Provides SEMS screws for easy wiring
connections.
SIGNALING
®
Velociti is a registered trademark & Clip™ is a trademark of Honeywell International Inc.
UL® is a registered trademark of Underwriters Laboratories Inc.
ULC® is a registered trademark of Underwriters Laboratories of Canada Inc.
FM
APPROVED
S911
3035027 7135-1653:0213
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9021-60540 Rev. F page 1 of 2
©2014 Honeywell International Inc. All rights reserved.
Temperature Range:
For B501, B224RB, B224BI,
and B210LP
32°F to 120°F (0°C to 49° C)
Humidity Range:
10% to 93% RH,
non-condensing
Wire Gauge:
For B224BI, B224RB:
14 to 24 AWG
Electrical Ratings
For B224RB, B224BI:
Operating Voltage: 15 to 32 VDC (powered by SLC)
Standby Ratings:
<500 µA maximum @ 24 VDC
Set Time
(B224RB only):
Short delay: 55-90 mseconds
Long delay: 6 to 9 seconds
Reset Time
(B224RB only):
20 mseconds maximum
Relay
Characteristics
(B224RB only):
Two-coil Latching Relay
One Form-C Contact
Ratings (UL/CSA): 0.9 A @ 125 VAC (inductive)
0.9 A @ 110 VDC (inductive)
3.0 A @ 30 VDC (resistive)
Ordering Information
Intelligent Bases
Part Number
B501
Dimensions:
B501BP
Dimensions:
B224BI
Dimensions:
B224RB
Dimensions:
B210LP
Dimensions:
B210LPBP
Dimensions:
XR2B
XP-4
T55-127-000
BCK-200B
WCK-200B
Description
Flangeless mounting base
4.1” (10.41 cm) diameter
Flangeless mounting base bulk pack
4.1” (10.41 cm) diameter
Isolator base
6.875” (17.462 cm) diameter
Relay base
6.875” (17.462 cm) diameter
Flanged mounting base
6.1” (15.5 cm) diameter
Flanged mounting base bulk pack
6.1” (15.5 cm) diameter
Detector removal tool
(T55-127-000 included).
Extension pole for XR2B
(5 to 15 ft/1.524 to 4.572 m)
Detector removal head.
Black detector kit.
White detector kit.
Mounting Kits and Accessories
Part Number
SMB600
F110
F110BP
F210
M02-04-01
M02-09-00
Description
Surface mounting kit, flanged.
Accessory retrofit flange ring for B210LP
Accessory retrofit flange ring for the
B210LPBP bulk pack of 15.
Accessory with a new smaller flange ring
for the B210LP.
Detector test magnet.
Test magnet with telescoping handle.
Table 1 shows the Junction Box Selection Guide.
Table 1: Junction Box Selection Guide
3.5"
4.0"
4.0"
4.0" Square with
Single-Gang Octagonal Octagonal Square 3.0" mud ring 50 mm
60 mm 70 mm
B501
No
Yes
No
No
Yes
Yes
Yes
Yes
B210LP
Yes
Yes
Yes
Yes
Yes
No
No
No
B224BI
No
Yes
Yes
Yes
Yes
No
Yes
Yes
B224RB
No
Yes
Yes
Yes
Yes
No
Yes
Yes
NOTE: The box depth is contingent on the base and the wire size.
For information on applicable local codes for appropriate recommendation, refer to the National Electrical Code.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60540 Rev. F page 2 of 2
www.gamewell-fci.com
75 mm
No
No
Yes
Yes