Low-Profile Plug-in Intelligent Laser Smoke Detector Pinnacle™ model 7251 is an intelligent, laser-based photoelectric smoke detector featuring extensive on-board signal processing capabilities designed to improve smoke response. Features • Ultra-high-sensitivity capability • On-board drift compensation • Transient rejection algorithms • Environmental tracking • Wide sensitivity range • Rotary address switches • Analog communications • Sleek, low-profile design • Low standby current • Microprocessor design • Superior EMI protection Agency Listings Pinnacle features a patented smoke sensing chamber, designed to amplify signals from smoke but diminish stray internal reflections. By using a laser diode instead of a standard LED light source into the sensing chamber, Pinnacle is able to achieve sensitivities from 0.02 percent-per-foot to 2 percent-per-foot obscuration. The detectors’ extensive software processing includes multi-alert drift compensation, internal self diagnostics, and superior transient signal rejection algorithms to produce unprecedented stability at ultra high sensitivities over the complete temperature range. Because Pinnacle is base-compatible with all other 200 Series detectors, system designers can seamlessly mix it with other standard detection technologies thereby reducing overall cost. Unlike other high-sensitivity detectors, Pinnacle: • Can pinpoint identification of the fire location through addressability. • Experiences no delay in response time due to smoke dilution or smoke transportation time (as in aspirated systems). • Offers complete supervision of wiring and detector. Pinnacle is designed to protect valuable assets and operations where systems must remain online at all times. Many sensitive areas cannot tolerate even small amounts of smoke. Some ideal applications for Pinnacle include: • Telecommunications switching facilities • Cellular telephone infrastructure • Integrated circuit fabrication facilities • Computer rooms • Traffic control centers • Clean rooms Specifications Electrical Specifications Voltage Range Standby Current (max. avg.) LED Current (max.) Physical/Operating Specifications Height Diameter Shipping Weight Operating Temperature Range Velocity Range Operating Humidity Range Self Diagnostics Smoke Sensitivity Drift Compensation 15 – 32 volts DC peak 230 µA @ 24VDC (without communication) 330 µA @ 24VDC (one communication every 5 sec. with LED enabled) 6.5 mA @ 24VDC (on) 1.66˝ (4.2 cm) 4.0˝ (10.2 cm) 5.6 oz. (159 g) 32° to 100°F (0° to 38°C) 0 – 4000 fpm (0 to 20.3 m/s) 10% – 93% noncondensing Initiated by control panel Activated by test magnet 9 levels: 0.02, 0.03, 0.05, 0.10, 0.20, 0.50, 1.00, 1.50, 2.00%/ft. obscuration (0.06, 0.10, 0.16, 0.33, 0.66, 1.65, 3.24, 4.85, 6.41%/m obscuration) High sensitivity maintenance alert signal Low sensitivity maintenance alert signal Maintenance urgent signal M02-09-00 Test Magnet with Telescoping Handle RA400Z Remote LED Ordering Information Part No. Description 7251 Low-profile intelligent plug-in laser smoke detector 7251A Low-profile intelligent plug-in laser smoke detector (Canadian model) 200 Series Bases B501(A)* Flangeless Mounting Base B224RB(A) B210LP(A) Flanged Mounting Base B224BI(A) B501BH(A) Standard Sounder Base SMK400 B501BHT(A) Temporal Tone Sounder Base SMB600 200 Series Accessories RA400Z(A) Remote LED Annunciator (shown above) XR-2 M02-04-01 Detector Test Magnet XP-4 M02-09-00 Telescoping Test Magnet (shown above) DUST12 Relay Base Isolator Base Flangeless Surface Mounting Kit Flanged Surface Mounting Kit Detector Removal Tool Extension for XR-2 (5–15 ft.) Dust Cover *(A) suffix denotes Canadian products 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 ©2007 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. A05-0314-003 • 3/07 • #1783