TI SLUA159

U-138
APPLICATION NOTE
Zero Voltage Switching
Resonant Power Conversion
Bill Andreycak
Abstract
The technique of zero voltage switching in
modern power conversion is explored. Several
ZVS topologies and applications, limitations of
the ZVS technique, and a generalized design
procedure are featured. Two design examples
are presented: a 50 Watt DC/DC converter,
and an off-line 300 Watt multiple output power
supply. This topic concludes with a performance comparison of ZVS converters to their
square wave counterparts, and a summary of
typical applications.
Introduction
Advances in resonant and quasi-resonant
power conversion technology propose alternative solutions to a conflicting set of square
wave conversion design goals; obtaining high
efficiency operation at a high switching frequency from a high voltage source. Currently,
the conventional approaches are by far, still in
the production mainstream. However, an
increasing challenge can be witnessed by the
emerging resonant technologies, primarily due
to their lossless switching merits. The intent of
this presentation is to unravel the details of
zero voltage switching via a comprehensive
analysis of the timing intervals and relevant
voltage and current waveforms.
The concept of quasi-resonant, “lossless”
switching is not new, most noticeably patented
by one individual [1] and publicized by another
at various power conferences [2,3]. Numerous
efforts focusing on zero current switching
ensued, first perceived as the likely candidate
for tomorrow’s generation of high frequency
power converters [4,5,6,7,8]. In theory, the onoff transitions occur at a time in the resonant
cycle where the switch current is zero, facilitat3-329
ing zero current, hence zero power switching.
And while true, two obvious concerns can
impede the quest for high efficiency operation
with high voltage inputs.
By nature of the resonant tank and zero
current switching limitation, the peak switch
current is significantly higher than its square
wave counterpart. In fact, the peak of the full
load switch current is a minimum of twice that
of its square wave kin. In its off state, the
switch returns to a blocking a high voltage
every cycle. When activated by the next drive
pulse, the MOSFET output capacitance (Goss)
is discharged by the FET, contributing a significant power loss at high frequencies and high
voltages. Instead, both of these losses are
avoided by implementing a zero voltage switching technique [9,lO].
Zero Voltage Switching Overview
Zero voltage switching can best be defined
as conventional square wave power conversion
during the switch’s on-time with “resonant”
switching transitions. For the most part, it can
be considered as square wave power utilizing a
constant off-time control which varies the
conversion frequency, or on-time to maintain
regulation of the output voltage. For a given
unit of time, this method is similar to fixed
frequency conversion which uses an adjustable
duty cycle, as shown in Fig. 1.
Regulation of the output voltage is accomplished by adjusting the effective duty cycle,
performed by varying the conversion frequency.
This changes the effective on-time in a ZVS
design. The foundation of this conversion is
simply the volt-second product equating of the
input and output. It is virtually identical to that
of square wave power conversion, and vastly
U-138
APPLICATION NOTE
Fig. 1 - Zero Voltage Switching vs. Conventional Square Wave
unlike the energy transfer system of its electrical dual, the zero current switched converter.
During the ZVS switch off-time, the L-C
tank circuit resonates. This traverses the voltage across the switch from zero to its peak,
and back down again to zero. At this point the
switch can be reactivated, and lossless zero
voltage switching facilitated. Since the output
capacitance of the MOSFET switch (Co& has
been discharged by the resonant tank, it does
not contribute to power loss or dissipation in
the switch. Therefore, the MOSFET transition
losses go to zero - regardless of operating
frequency and input voltage. This could represent a significant savings in power, and result in
a substantial improvement in efficiency. Obviously, this attribute makes zero voltage switching a suitable candidate for high frequency,
high voltage converter designs. Additionally, the
gate drive requirements are somewhat reduced
in a ZVS design due to the lack of the gate to
drain (Miller) charge, which is deleted when
V& equals zero.
The technique of zero voltage switching is
applicable to all switching topologies; the buck
regulator and its derivatives (forward, half and
full bridge), the flyback, and boost converters,
to name a few. This presentation will focus on
the continuous output current, buck derived
topologies, however a list of references describing the others has been included in the appendix.
3-330
Fig. 2 - Resonant Switch Implementation
Fig. 3 - General Waveforms
ZVS Benefits
n
Zero power “Lossless” switching transitions
n
Reduced EMI / RFI at transitions
n
No power loss due to discharging Goss
n
No higher peak currents, (ie. ZCS) same as
square wave systems
n
High efficiency with high voltage inputs at
any frequency
n
Can incorporate parasitic circuit and component L & C
APPLICATION NOTE
n
U-138
Reduced gate drive requirements (no
“Miller” effects)
filter section consisting of output inductor L.,,,
and capacitor CO has a time constant several
orders of magnitude larger than any power
conversion period. The filter inductance is large
in comparison to that of the resonant inductor’s
value L, and the magnetizing current ML., as
well as the inductor’s DC resistance is negligible. In addition, both the input voltage VjN and
output voltage V. are purely DC, and do not
vary during a given conversion cycle. Last, the
converter is operating in a closed loop configuration which regulates the output voltage V. .
Short circuit tolerant
ZVS Differences:
n
Variable frequency operation (in general)
q
Higher off-state voltages in single switch,
unclamped topologies
W
Relatively new technology - users must climb
the learning curve
W
Conversion frequency is inversely proportional to load current
w
A more sophisticated control circuit may be
required
Initial Conditions: Time interval < +,
ZVS Design Equations
A zero voltage switched Buck regulator
will be used to develop the design equations
for the various voltages, currents and time
intervals associated with each of the conversion
periods which occur during one complete
switching cycle. The circuit schematic, component references, and relevant polarities are
shown in Fig. 4.
Typical design procedure guidelines and
“shortcuts” will be employed during the analysis’ for the purpose of brevity. At the onset,
all components will be treated as though they
were ideal which simplifies the generation of
the basic equations and relationships. As this
section progresses, losses and non-ideal characteristics of the components will be added to the
formulas. The timing summary will expound
upon the equations for a precise analysis.
Another valid assumption is that the output
Before analyzing the individual time intervals, the initial conditions of the circuit must be
defined. The analysis will begin with switch Q,
on, conducting a drain current ZD equal to the
output current IO, and VDs = VCR = 0 (ideal).
In series with the switch Q, is the resonant
inductor L, and the output inductor L, which
also conduct the output current I,. It has been
established that the output inductance L, is
large in comparison to the resonant inductor
L, and all components are ideal. Therefore, the
voltage across the output inductor V’ equals
the input to output voltage differential; I/Lo =
VIN - VO. The output filter section catch diode
DO is not conducting and sees a reverse voltage
equal to the input voltage; V’ = V,, observing
the polarity shown in Figure 4.
Table I - INITIAL CONDITIONS
Capacitor Charging State:
to
-
t,
The conversion period is initiated at time t,
when switch Q, is turned OFF. Since the
current through resonant inductor L, and
output inductor L, cannot change instantaneously, and no drain current flows in Q, while
Fig. 4 - Zero Voltage Switched Buck Regulator
3-331
U-138
APPLICATION NOTE
Table II - CAPACITOR CHARGING: b - tl
Fig. 5 - Simplified Model
Resonant State: t, - t,
Fig. 6 - Resonant Capacitor Waveforms
it is off, the current is diverted around the
switch through the resonant capacitor CR. The
constant output current will linearly increase
the voltage across the resonant capacitor until
it reaches the input voltage (VCR = VI,,,). Since
the current is not changing, neither is the
voltage across resonant inductor L,.
At time t, the switch current IO “instantly”
drops from IO to zero. Simultaneously, the
resonant capacitor current IcR snaps from zero
to I,, while the resonant inductor current ILR
and output inductor current IL0 are constant
and also equal to I, during interval toI. Voltage
across output inductor Lo and output catch
diode D, linearly decreases during this interval
due to the linearly increasing voltage across
resonant capacitor CR. At time tl , VCR equals
and D, starts to conduct.
3-332
The resonant portion of the conversion cycle
begins at tI when the voltage across resonant
capacitor VCR equals the input voltage VIN, and
the output catch diode begins conducting. At
t, , current through the resonant components
IcR and ILR equals the output current I,.
The stimulus for this series resonant L-C
circuit is output current I, flowing through the
resonant inductor prior to time t,. The ensuing
resonant tank current follows a cosine function
beginning at time t,, and ending at time t2. At
the natural resonant frequency OR9 each of the
L-C tank components exhibit an impedance
equal to the tank impedance, ZR. Therefore,
the peak voltage across CR and switch Q, are a
function of ZR and I, .
The instantaneous voltage across CR and Q,
can be evaluated over the resonant time interval using the following relationships:
Of greater importance is the ability to solve
the equations for the precise off-time of the
switch. This off-time will vary with line and
load changes and the control circuit must
respond in order to facilitate true zero voltage
switching. While some allowance does exist for
a fixed off time technique, the degree of lati-
APPLICATION NOTE
U-138
tude is insufficient to accommodate typical
input and output variations, The exact time is
obtained by solving the resonant capacitor
voltage equations for the condition when zero
voltage is attained.
VCR (t)ve
LINE
CHANGES
The equation can be further simplified by
extracting the half cycle (180 degrees) of conduction which is a constant for a given resonant
frequency, and equal to ~rr/t+.
Fig. 7 -- Resonant Capacitor Voltage vs. Line
The resonant component current (IcR = IL.)
is a cosine function between time tl and tz,
described as:
The absolute maximum duration for this
interval occurs when 270 degrees (3x/2& of
resonant operation is required to intersect the
zero voltage axis. This corresponds to the limit
of resonance as minimum load and maximum
line voltage are approached.
Contributions of line and load influences on
the resonant time interval t12 can be analyzed
individually as shown in Figs. 7 and 8.
Prior to time tl, the catch diode Do was not
conducting. Its voltage, VW, was linearly decreasing from V,N at time to to zero at tl while
input source v,Jv was supplying full output
current, IO. At time t,, however, this situation
changes as the resonant capacitor initiates
resonance, diverting the resonant inductor
current away from the output filter section.
Instantly, the output diode voltage, Vm, changes polarity as it begins to conduct, supplementing the decreasing resonant inductor current
with diode current I’, extracted from stored
energy in output inductor Lo. The diode current waveshape follows a cosine function during
this interval, equalling IO minus IcR(t)#
Also occurring at time t,, the output filter
inductor Lo releases the stored energy required
3-333
Fig. 8 -- Resonant Capacitor Voltage vs. Load
to maintain a constant output current I,. Its
reverse voltage is clamped to the output voltage
V. minus the diode voltage drop V’ by the
convention followed by Figure 4.
Table III - RESONANT INTERVAL: tl - b
APPLICATION NOTE
Table IV - INDUCTOR CHARGING: t2 - t3
Inductor Charging State: fi - t3
To facilitate zero voltage switching, switch
Q, is activated once the voltage I& across Q,
and resonant capacitor VCR has reached zero,
occurring at time tZ. During this inductor
charging interval tu resonant inductor current
ILR is linearly returned from its negative peak
of minus I, to its positive level of plus I,.
The output catch diode D, conducts during
the tu interval. It continues to freewheel the
full output current I,, clamping one end of the
resonant inductor to ground through Do. There
is a constant voltage, V’,N - I& , across the
resonant inductor. As a result, ILR rises linearly,
I,, decreases linearly. Energy stored in output
inductor L, continues to be delivered to the
load during this time period.
A noteworthy peculiarity during this timespan can be seen in the switch dram current
waveform. At time f2, when the switch is turned
on, current is actually returning from the
resonant tank to the input source, I&. This
indicates the requirement for a reverse polarity
diode across the switch to accommodate the bidirectional current. An interesting result is that
the switch can be turned on at any time during
the first half of the fB interval without affecting
normal operation. A separate time interval
could be used to identify this region if desired.
Power Transfer State:
t3
- tr
Once the resonant inductor current ILR has
reached I, at time tJ, the zero voltage switched
converter resembles a conventional square
wave power processor. During the remainder of
3-334
COMP. STATUS
CIRCUIT VALUES
the conversion period, most of the pertinent
waveforms approach DC conditions.
Assuming ideal components, with Q, closed,
the input source supplies output current , and
the output filter inductor voltage VLo equals VIN
- Vo. The switch current and resonant inductor
current are both equal to IO, and their respective voltage drops are zero (V& = V’,=O).
Catch diode voltage Vm equals VIN, and Im = 0.
In closed loop operation where the output
voltage is in regulation, the control circuit
essentially varies the on-time of the switch
during the tJ4 interval. Variable frequency
operation is actually the result of modulating
the on-time as dictated by line and load conditions. Increasing the time duration, or lowering
the conversion frequency has the same effect as
widening the duty cycle in a traditional square
wave converter. For example, if the output
voltage were to drop in response to an
increased load, the conversion frequency would
decrease in order to raise the effective ON
period. Conversely, at light loads where little
energy is drawn from the output capacitor, the
control circuit would adjust to minimize the lJ,
duration by increasing the conversion frequency. In summary, the conversion frequency is
inversely proportional to the power delivered to
the load.
l
U-138
APPLICATION NOTE
Table V - POWER TRANSFER: t3 - t,
COMP. STATUS
CIRCUIT VALUES
Fig. 9 -- ZVS Buck Regulator Waveforms
3-335
U-138
APPLICATION NOTE
ZVS Converter Limitations:
In a ZVS converter operating under ideal
conditions, the on-time of the switch (fZ+tJ4)
approaches zero, and the converter will operate
at maximum frequency and deliver zero output
voltage. In a practical design , however, the
switch on-time cannot go to zero for several
reasons.
First of all, the resonant tank components
are selected based on the maximum input
voltage TJJN- and minimum output current
I Omin for the circuit to remain resonant over all
operating conditions of line and load. If the
circuit is to remain zero voltage switched, then
the resonant tank current cannot be allowed to
go to zero. It can, however, reach IO,,,,.,, .
There is a finite switch on-time associated
with the inductor charging interval tu where the
resonant inductor current linearly increases
from - I, to + I,. As the on-time in the power
transfer interval tJr approaches zero, so will the
converter output voltage. Therefore, the minimum on-time and the maximum conversion
frequency can be calculated based upon the
limitation of Iomin and zero output voltage.
The limits of the four zero voltage switched
time intervals will be analyzed when IO goes to
IO minimum. Each solution will be retained in
terms of the resonant tank frequency wR for
generalization.
Both the minimum on-time and maximum
off-time have been described in terms of the
resonant tank frequency , wR. Taking this one
step further will result in the maximum conversion frequency fCoti, also as a function of
the resonant tank frequency.
Maximum Off-Time:
The maximum conversion frequency corresponds to the minimum conversion period,
TcoW,, , which is the sum of the minimum ontime and maximum off-time:
The maximum conversion frequency, fcowm
= l/Tcowti,, , equals
The ratio of the maximum conversion frequency to that of the resonant tank frequency
can be expressed as a topology coefficient, Kr.
For this zero voltage switched Buck regulator
and its derivatives, KTmax equals:
3-336
U-138
APPLICATION NOTE
conversion period where tJ4 equals zero. Topology coefficient K-r will be incorporated to
define the ratio of the maximum conversion
frequency (minimum conversion period) to that
of the resonant tank frequency, OR.
Fig. IO -- Waveforms at Fcow = KT fR
l
In a realistic application, the output voltage
of the power supply is held in regulation at VO
which stipulates that the on-time in the power
processing state, tJ4 , cannot go to zero as in
the example above. The volt-second product requirements of the output must be satisfied
during this period, just as in any square wave
converter design. Analogous to minimum duty
cycle, the minimum on-time for a given design
will be a function of V’&, VO and the resonant
tank frequency, oR.
Although small, a specific amount of energy
is transferred from the input to the output
during the capacitor charging interval t,. The
voltage into the output filter section linearly
decreases from & at time t, to zero at tl,
equal to an average value of V,,,,/2. In addition,
a constant current equal to the output current
I, was being supplied from the input source.
The average energy transferred during this
interval is defined as:
The equation can be reorganized in terms of
CR and f+ as:
This minimum energy can be equated to
minimum output watts by dividing it by its
3-337
This demonstrates that a zero power output
is unobtainable in reality. The same is true for
the ability to obtain zero output voltage.
The equation can be rewritten as:
Solving for the highest minimum output
voltage, the worst case for occurs when I,
equals Iomin and VIN is at its maximum, VlN-.
Under normal circumstances the circuit will
be operating far above this minimum requirement. In most applications, the amount of
power transferred during the capacitor charging
interval t, can be neglected as it represents
less than seven percent (7%) of the minimum
input power. This corresponds to less than one
percent of the total input power assuming a
10:1 load range.
ZVS Effective Duty Cycles:
A valid assumption is that a negligible
amount of power is delivered to the load
during the capacitor charging interval to,. Also,
no power is transferred during the resonant
period from t,,. Although the switch is on
during period tw, it is only recharging the
APPLICATION NOTE
U-138
resonant and output inductors to maintain the
minimum output current, Iolrdn. In summary,
NO output power is derived from V”‘N during
interval tm.
The power required to support V0 at its
current of I0 is obtained from the input source
during the power transfer period tJ4. Therefore,
an effective “duty cycle” can be used to describe the power transfer interval fJ4 to that of
the entire switching period, tw, or Tconrv.
ZVS - Effective Duty Cycle Calculations:
could optionally be evaluated.
A computer program to calculate the numerous time intervals and conversion frequencies
as a function of line and load can simplify the
design process, if not prove to be indispensable.
Listed in the Appendix of this section is a
BASIC language program which can be used to
initiate the design procedure.
To summarize: When the switch is on, replace v;N with KWv&(On)) =
RDS(on))*
When the free-wheeling diode is on, replace V.
with (Vo+VF).
(I/IN-IO
l
And can be analyzed over line and load
ranges using previous equations for each interval.
Accommodating Losses in the Design
Equations:
Equations for zero voltage switching using
ideal components and circuit parameters have
been generated, primarily to understand each
of the intervals in addition to computer modeling purposes. The next logical progression is to
modify the equations to accommodate voltage
drops across the components due to series
impedance, like RDSo, and the catch diode
forward voltage drop. These two represent the
most significant loss contributions in the buck
regulator model. Later, the same equations will
be adapted for the buck derived topologies
which incorporate a transformer in the power
stage.
The procedure to modify the equations is
straightforward. Wherever V,N appears in the
equations while the switch is on it will be
replaced by V,N-V~~~on~ , the latter being a
function of the load current I,. The equations
can be further adjusted to accept changes of
R DS(on) and vF ? etc. with the device junction
temperatures. Resonant component initial
tolerances, and temperature variations likewise
3-338
Transformer Coupled Circuit Equations:
The general design equations for the Buck
topology also apply for its derivates; namely the
forward, half-bridge, full-bridge and push-pull
converters. Listed below are the modifications
and circuit specifics to apply the previous
equations to transformer coupled circuits.
General Transformer Coupled Circuits. Maintaining the resonant tank components on the
primary side of the transformer isolation boundary is probably the most common and simplest of configurations. The design procedure
begins by transforming the output voltage and
current to the primary side through the turns
ratio, N. The prime (') designator will be used
to signify the translated variables as seen by the
primary side circuitry.
U-138
APPLICATION NOTE
N=
Primary Turns
Secondary Turns
To satisfy the condition for resonance, IR c Iof
Determining Transformer Turns Ratio (N):
The transformer turns ratio is derived from the
equations used to define the power transfer
interval tM in addition to the maximum offtime, tcu. While this may first seem like an
iterative process, it simplifies to the volt-second
product relationship described. The general
equations are listed below.
The turns ratio N is derived by substituting
The resonant tank component equations now
become:
NW0 for the output voltage V. in the power
transfer interval tJ4 equation. Solving for N
results in the relationship:
I
Note: the calculated resonant inductance
value does not include any series inductance,
typical of the transformer leakage and wiring
inductances.
The transformer magnetizing and leakage
inductance is part of the resonant inductance.
This requires adjustment of the resonant inductor value, or both the resonant tank impedance
zR and frequency wR will be off-target. One
Note: the calculated resonant capacitor value
does not include any parallel capacitance,
typical of a MOSFET output capacitance, Goss,
in shunt. Multi-transistor variations of the buck
topology should accommodate all switch capacitances in the analysis.
Timing Equations (including N):
Fig. 11 -- Transformer Inductance “Shim ”
option is to design the transformer inductance
to be exactly the required resonant inductance,
thus eliminating one component. For precision
applications, the transformer inductance should
be made slightly smaller than required, and
“shimmed” up with a small inductor.
3-339
APPLICATION NOTE
Expanding ZVS to Other Topologies
ZVS Forward Converter - Single Ended:
The single ended forward converter can easily
be configured for zero voltage switching with
the addition of a resonant capacitor across the
switch. Like the buck regulator, there is a high
voltage excursion in the off state due to resonance, the amplitude of which varies with line
and load. The transformer can be designed so
that its magnetizing and leakage inductance
equals the required resonant inductance. This
simplifies transformer reset and eliminates one
component. A general circuit diagram is shown
in Fig. 12 below. The associated waveforms for
when &RI e q uals LR are shown in Fig. 13.
0
Fig. 12 -- ZVS Forward Converter
3-340
l
APPLICATION NOTE
U-138
ZVS Clamped Configurations -- Half and
Full Bridge Topologies: Zero voltage switching
can be extended to multiple switch topologies
for higher power levels, specifically the half and
full bridge configurations. While the basic
operation of each time interval remains similar,
there is a difference in the resonant tlZ interval.
While single switch converters have high offstate voltage, the bridge circuits clamp the
switch peak voltages to the DC input rails,
reducing the switch voltage stress. This alters
the duration of the off segment of the resonant
interval, since the opposite switch(es) must be
activated long before the resonant cycle is completed. In fact, the opposite switch(es) should
be turned on immediately after their voltage is
clamped to the rails, where their drain to
source voltage equals zero. If not, the resonant
tank will continue to ring and return the switch
voltage to its starting point, the opposite rail.
Additionally, this off period varies with line and
load changes.
Examples of this are demonstrated in Figs.
14 and 15. To guarantee true zero voltage
switching, it is recommended that the necessary
sense circuitry be incorporated.
3-341
Fig. 14 -- Clamped ZVS Configuration
APPLICATION NOTE
ZVS Half Bridge: The same
turns ratio, N, relationship
applies to the half bridge topology when & in the previous equations is considered to
be one-half of the bulk rail-torail voltage. V’& is the voltage
across the transformer primary
when either switch is on.
Refer to the circuit and
waveforms of Figs. 14 and 15.
CR, the resonant capacitor
becomes the parallel combination of the two resonant capacitors, the ones across each
switch. Although the resonant
inductor value is unaffected, all
series leakage and wiring inductance must be taken into
account.
U-138
Fig. 16 -- ZVS Half Bridge Circuit
The off state voltages of the
switches will try to exceed the
input bulk voltage during the
resonant stages. Automatic
clamping to the input bulk
rails occurs by the MOSFET
body diode, which can be
externally shunted with a higher performance variety. Unlike
the forward converter which
requires a core reset equal to
the applied volt second product, the bidirectional switching
of the half (and full) bridge
topology facilitate automatic
core reset during consecutive
switching cycles [ll,l2].
Fig. 17 -- ZVS Half Bridge Wavefoms
3-342
U-138
APPLICATION NOTE
ZVS Full Bridge: The equations represented for the forward topology apply equally
well for one conversion cycle
of the full bridge topology,
including the transformer turns
ratio. Since the resonant capacitors located at each switch
are “in-circuit” at all times,
the values should be adjusted
accordingly. As with the half
bridge converter, the resonant
capacitors’ voltage will exceed
the bulk rails, and clamping via
the FET body diodes or external diodes to the rails is common [13].
Fig. 18 -- ZVS Full Bridge Circuit
Fig. 19 -- ZVS Full Bridge Wavefoms
3-343
U-138
APPLICATION NOTE
ZVS Design Procedure
Buck Derived Topologies -- Continuous
output Current:
1. List all input/output specs and ranges.
VrN min & max ; Vo ; I, min & max
2. Estimate the maximum switch voltages. For
unclamped applications (buck and forward):
VDSmru
Note: Increase IO,,,,.,, if V’s= is too high if
possible).
applications
9. Debug and modify the circuit as required to
accommodate component parasitics, layout
concerns or packaging considerations.
Avoiding Parasitics
= J%hltLz(l + (lomru/lomin)
For
clamped
VDSnw = bvnuu
8. Breadboard the circuit carefully using RF
techniques wherever possible. Remember -parasitic inductances and capacitances prefer
to resonate upon stimulation, and quite
often, unfavorably.
(bridges):
3. Select a resonant tank frequency, OR
(HINT: OR = 2x&).
4. Calculate the resonant tank impedance and
component values.
Ringing of the catch diode junction capacitance with circuit inductance (and package
leads) will significantly degrade the circuit
performance. Probably the most common
solution to this everyday occurrance in square
wave converters is to shunt the diode with an
R-C snubber. Although somewhat dissipative,
a compromise can be established between
snubber losses and parasitic overshoot caused
by the ringing. Unsnubbed examples of various
applicable diodes are shown in Fig. 20 below.
5. Calculate each of the interval durations (toI
thru fM) and their ranges as a function of all
line and load combinations.
(See Appendix
for a sample computer
program written in BASIC)
Additionally, summarize the results to establish the range of conversion frequencies,
peak voltages and currents, etc.
6. Analyze the results. Determine if the frequency range is suitable for the application.
If not, a recommendation is to limit the load
range by raising rod,, and start the design
procedure again. Verify also that the design
is feasible with existing technology and
components.
7. Finalize the circuit specifics and details.
0 Derive the transformer turns ratio. (nonbuck applications)
0 Design the output filter section based upon
the lowest conversion frequency and output
ripple current&(
0 Select applicable components; diode,
MOSFET etc.
3-344
Fig. 20 -- Catch Diode Ringing
l
APPLICATION NOTE
U-138
Multiresonant ZVS Conversion
Another technique to avoid the parasitic
resonance involving the catch diode capacitance
is to shunt it with a capacitor much larger than
the junction capacitance. Labelled CD, this
element introduces favorable switching characteristics for both the switch and catch diode.
The general circuit diagram and associated
waveforms are shown below, but will not be
explored further in this presentation [14,15].
Fig. 22 -- Multiresonant Waveforms
Fig. 21 -- Multiresonant ZVS Circuit
Current Mode Controlled
ZVS Conversion
Variable frequency power converters can
also benefit from the use of current mode
control. Two loops are used to determine the
precise ON time of the power switch -- an
“outer” voltage feedback loop, and an “inner”
current sensing loop. The advantage to this
approach is making the power stage operate as
a voltage controlled current source. This eliminates the two pole output inductor characteristics in addition to providing enhanced dynamic
transient response.
Principles of operation. Two control ICS are
utilized in this design example. The UC3843A
PWM performs the current mode control by
providing an output pulse width determined by
the two control loop inputs. This pulse width,
or repetition rate is used to set the conversion
period of the UC3864 ZVS resonant controller.
Rather than utilize its voltage controlled oscillator to generate the conversion period, it is
determined by the UC3843A output pulse
width.
Zero voltage switching is performed by the
UC3864 one-shot timer and zero crossing
detection circuitry. When the resonant capacitor voltage crosses zero, the UC3864 output
goes high. This turns ON the power switch and
recycles the UC3843A to initiate the next
current mode controlled period. The UC3864
fault circuitry functions, but its error amplifier
and VCO are not used.
3-345
387
U-138
APPLICATION NOTE
ZVS Forward Converter -- Design
Example
Table VI - Interval Durations vs. Line & Load
1. List circuit specifications:
&N
= 18 to 26 V
vo = 5.0 V ;
I, = 2.5 to 10 A
2. Estimate the maximum voltage across the
switch:
=26•(1+(10/2.5)) = 26•5 = 130 V
3. Select a resonant tank frequency, oR’
A resonant tank period frequency of 500KHz
will be used. It was selected as a compro-
mise between high frequency operation and
low parasitic effects of the components and
layout.
4. Calculate the resonant tank impedance and
component values.
Resonant tank impedance, ZR > VIN,,,Joti,,
Fig. 23 - Switch Times vs. Line & Load
To accommodate the voltage drop across the
MOSFET, calculate VDs(on~min, which equals
5. Calculate each of the interval durations @,,
thru f& and ranges as they vary with line
and load changes.
The zero voltage switched buck converter
“gain” in kiloHertz per volt of V,N and kHz
per amp of IO can be evaluated over the
specified ranges. A summary of these follows:
3-346
It may be necessary to use the highest gain
values to design the control loop compensation
for stability over all operating conditions. While
this may not optimize the loop transient response for all operating loads, it will guarantee
stability over the extremes of line and load.
l
APPLICATION NOTE
U-138
A. Output Filter Section: Select L, and CO
for operation at the lowest conversion
frequency and designed ripple current.
B. Heatsink Requirements: An estimate of
the worst case power dissipation of the
power switch and output catch diode can be
made over line and load ranges.
C. Control Circuit: The UC3861-64 series of
controllers will be examined and programmed per the design requirements.
Programming the Control Circuit
Fig. 24 - Conversion Freq. vs. Line & Load
6. Analyze the results.
The resonant component values, range of
conversion frequencies, peak voltage and
current ratings seem well within the practical
limits of existing components and technology.
7. Finalize the circuit specifics and details
based on the information obtained above.
One-shot= Accommodating Off-time Variations. The switch off-time varies with line and
load by == ± 35% in this design example using
ideal components. Accounting for initial tolerances and temperature effects results in an
much wider excursion. For all practical purposes, a true fixed off-time technique will n o t
work.
Incorporated into the UC3861 family of ZVS
controllers is the ability to modulate this off-
Fig. 25 -- The UC3861-64 ZVS Controllers -- Block Diagram
3-347
APPLICATION NOTE
U-138
lated range of conversion frequencies spans 87
to 310 kHz. These values will be used for this
“first cut” draft of the control circuit programming. Due to the numerous circuit specifics omitted from the computer program for
simplicity, the actual range of conversion frequencies will probably be somewhat wider than
planned. Later, the actual timing component
values can be adjusted to accommodate these
differences.
First, a minimum fc o f 7 5 k H z h a s b e e n
selected and programmed according to the
following equation:
Fig. 26 -- CR Volts & Off-time vs. Line & Load
time. Initially, the one-shot is programmed for
the maximum off-time, and modulated via the
ZERO detection circuitry. The switch drainsource voltage is sensed and scaled to initiate
turn-on when the precision 0.5V threshold is
crossed. This offset was selected to accommodate propogation delays between the instant the
threshold is sensed and the instant that the
switch is actually turned on. Although brief,
these delays can become significant in high
frequency applications, and if left unaccounted,
can cause NONZERO switching transitions.
Referring to Fig. 26, in this design, the offtime varies between 1.11 and 1.80 microseconds, using ideal components and neglecting
temperature effects on the resonant components. Since the ZERO detect logic will facilitate “true” zero voltage switching, the off-time
can be set for a much greater period.
The one-shot has a 3:1 range capability
and will be programmed for 2.2 U S
( m a x ) , c o n t r o l l a b l e d o w n t o 0 . 7 5 U S.
Programming of the one-shot requires
a single R-C time constant, and is
straightforward using the design information and equations from the data
sheet. Implementation of this feature is
shown in the control circuit schematic.
The maximumfc of 350 kHZ is programmed
by:
Numerous values of Rti,, and C,, will satisfy
the equations. The procedure can be simplified
by letting Rtin equal 100K.
The VCO gain in frequency per volt from
the error amplifier output is approximated by:
with an approximate 3.6 volt delta from the
error amplifier.
VOLTAGE CONTROLLED OSCILLATOR
Programming the VCO. The calcu-
Fig. 27 -- E/A - VCO Block Diagram
3-348
U-138
APPLICATION NOTE
Fault Protection - Soft Start & Restart
Delay One of the unique features of the UC
3861 family of resonant mode controllers can
be found in its fault management circuitry. A
single pin connection interfaces with the soft
start, restart delay and programmable fault
mode protection circuits. In most applications,
one capacitor to ground will provide full protection upon power-up and during overload
conditions. Users can reprogram the timing
relationships or add control features (latch off
following fault, etc) with a single resistor.
Selected for this application is a 1 uF softrestart capacitor value, resulting in a soft-start
duration of 10 ms and a restart delay of approximately 200 ms. The preprogrammed ratio
of 19:l (restart delay to soft start) will be utilized, however the relevant equations and
relationships have also been provided for other
applications. Primary current will be utilized as
the fault trip mechanism, indicative of an
overload or short circuit current condition. A
current transformer is incorporated to maximize efficiency when interfacing to the three
volt fault threshold.
Optional Programming of Tss and Tm :
Soft Start: Tss = CSR. 10K
Restart Delay: Tm = CsR. 1 9 O K
Timing Ratio: Tm:Tss = 1 9 : l
Gate Drive: Another unique feature of the
UC 3861-64 family of devices is the optimal
utilization of the silicon devoted to output
totem pole drivers. Each controller uses two
pins for the A and B outputs which are internally configured to operate in either unison or
in an alternating configuration. Typical performance for these 1 Amp peak totem pole outputs shows 30 ns rise and fall times into 1 n F .
Loop Compensation -- General Information.
The ZVS technique is similar to that of conventional voltage mode square wave conversion
which utilizes a single voltage feedback loop.
Unlike the dual loop system of current mode
control, the ZVS output filter section exhibits
3-349
Fig. 28 -- Programming Tss and TRD
FAULT
Fig. 29 -- Fault Operational Waveforms
a two pole-zero pair and is compensated accordingly. Generally, the overall loop is designed to cross zero dB at a frequency below
one-tenth that of the switching frequency. In
this variable frequency converter, the lowest
conversion frequency will apply, corresponding
to approximately 85 KHz, for a zero crossing of
8.5 KHz. Compensation should be optimized
for the highest low frequency gain in addition
to ample phase margin at crossover. Typical
examples utilize two zeros in the error amplifier compensation at a frequency equal to that of
the output filter’s two pole break. An additional high frequency pole is placed in the loop to
combat the zero due to the output capacitance
ESR, assuming adequate error amplifier gainbandwidth.
A noteworthy alternative is the use of a two
loop approach which is similar to current mode
control, eliminating one of the output poles.
One technique known as Multi-Loop Control
for Quasi-Resonant Converters [18] has been
APPLICATION NOTE
U-138
developed. Another, called Average Current
Mode Control is also a suitable candidate,
Fig. 30 - Error Amplifier Compensation
Summary
The zero voltage switched quasi-resonant
technique is applicable to most power conversion designs, but is most advantageous to those
operating from a high voltage input. In these
applications, losses associated with discharging
of the MOSFET output capacitance can be
significant at high switching frequencies, impairing efficiency. Zero voltage switching avoids
this penalty by negating the drain-to-source,
“off-state” voltage via the resonant tank.
A high peak voltage stress occurs across the
switch during resonance in the buck regulator
and single switch forward converters. Limiting
this excursion demands limiting the useful load
range of the converter as well, an unacceptable
solution in certain applications. For these
situations, the zero voltage switched multiresonant approach [14,15] could prove more
beneficial than the quasi-resonant ZVS variety.
Significant improvements in efficiency can be
obtained in high voltage, half and full bridge
ZVS applications when compared to their
square wave design complements. Clamping of
Fig. 31 - Zero Voltage Switched Forward Converter
3-350
APPLICATION NOTE
U-138
the peak resonant voltage to the input rails
avoids the high voltage overshoot concerns of
the single switch converters, while transformer
reset is accomplished by the bidirectional
switching. Additionally, the series transformer
primary and circuit inductances can beneficial,
additives in the formation of the total resonant
inductor value. This not only reduces size, but
incorporates the detrimental parasitic generally
snubbed in square wave designs, further enhancing efficiency.
A new series of control ICs has been developed specifically for the zero voltage switching
techniques with a list of features to facilitate
lossless switching transitions with complete
fault protection. The multitude of functions and
ease of programmability greatly simplify the
interface to this new generation of power
conversion techniques; those developed in
response to the demands for increased power
density and efficiency.
Fig. 32 -- Zero Voltage Switched Half-Bridge Converter
3-351
U-138
APPLICATION NOTE
References
“Forward Converter
Vinciarelli,
[1] P.
Switching At Zero Current,” U.S. Patent
# 4,415,959 (1983)
[2]
K. H. Liu and F. C. Lee, “Resonant
Switches - a U n i f i e d A p p r o a c h t o I m proved Performances of Switching Converters,” International Telecommunications Energy Conference; New Orleans, 1984
[3]
K. H. Lieu, R. Oruganti, F. C. Lee, “Resonant Switches - Topologies and Characteristics,” IEEE PESC 1985 (France)
[4]
M. Jovanovic, D. Hopkins, F. C. Lee,
“Design Aspects For High Frequency
Off-line Quasi-resonant Converters,” High
Frequency Power Conference, 1987
[12] R. Steigerwald, “A Comparison of HalfBridge Resonant Converter Topologies,”
IEEE 1987
[13] J. Sabate, F. C. Lee, “Offline Application
of the Fixed Frequency Clamped Mode
Series-Resonant Converter,” IEEE APEC
Conference, 1989
[14] W . T a b i s z , F . C . L e e , “ Z e r o V o l t a g e Switching Multi-Resonant Technique - a
Novel Approach to Improve Performance
of High Frequency Quasi-Resonant Converters,” IEEE PESC, 1988
[15] W. Tabisz, F. C. Lee, “A Novel, ZeroVoltage Switched Multi-Resonant Forward
Converter,” High Frequency Power Conference, 1988
D. Hopkins, M. Jovanovic, F. C. Lee, F.
Stephenson, “ T w o M e g a h e r t z O f f - L i n e
Hybridized Quasi-resonant Converter,”
IEEE APEC Conference, 1987
[16] L. Wofford, “A New Family of Integrated
Circuits Controls Resonant Mode Power
Converters,” Power Conversion and
[6]
W. M. Andreycak, “1 Megahertz 150
Watt Resonant Converter Design Review,
Unitrode Power Supply Design Seminar
Handbook SEM-600A, 1988
[17] W. Andreycak, “Controlling Zero Voltage
Switched Power Supplies,” High Frequency Power Conference, 1990
[7]
A. Heyman, “Low Profile High Frequency Off-line Quasi Resonant Converter,”
IEEE 1987
[5]
[8]
W. M. Andreycak, UC3860 Resonant
Control IC Regulates Off-Line 150 Watt
Converter Switching at 1 MHz,” H i g h
Frequency Power Conference 1989
[9]
M. Schlect, L. Casey, “Comparison of the
Square-wave and Quasi-resonant Topologies,” IEEE APEC Conference, 1987
[10] M. Jovanovic, R. Farrington, F. C. Lee,
“Comparison of Half-Bridge, ZCS-QRC
and ZVS-MRC For Off-Line Applications,” IEEE APEC Conference, 1989
[11] M. Jovanovic, W. Tabisz, F. C. Lee, “ Zero Voltage-Switching Technique in HighFrequency Off-Line Converters,” I E E E
PESC, 1988
3-352
Intelligent Motion Conference, 1989
[18] R. B. Ridley, F. C. Lee, V. Vorperian,
“Multi-Loop Control for Quasi-Resonant
Converters,” High Frequency Power Conference Proceedings, 1987
Additional References:
l “High Frequency Resonant, Quasi-Resonant
and Multi-Resonant Converters,” Virginia
Power Electronics Center, (Phone # 703-9614536), Edited by Dr. Fred C. Lee
l “Recent Developments in Resonant Power
Conversion,” Intertec Communication Press
(Phone # 805-658-0933), Edited by K Kit
Sum
U-138
APPLICATION NOTE
10 ' Zero Voltage Switching Calculations and Equations
20 ' Using the Continuous Current Buck Topology
30 ' in a Typical DC/DC Converter Power Supply Application
40 '
50 PRINTER$ = "lptl:": ' Printer at parallel port #l **********
60 '
70 ' Summary of Variables and Abbreviations
80 '
90 ' Cr = Resonant Capacitor
100 ' Lr = Resonant Inductor
110 ' Zr = Resonant Tank Impedance
120 ' Fres = Resonant Tank Frequency (Hz)
130 '
140 ' VImin = Minimum DC Input Voltage
150 ' VImax = Maximum DC Input Voltage
160 ' Vdson = Mosfet On Voltage = Io*Rds
170 ' Rds = Mosfet On Resistance
180 ' Vdsmax = Peak MOSFET Off State Voltage
190 ’ Vo = DC Output Voltage
200 ' Vdo = Output Diode Voltage Drop
210 ' Iomax = Maximum Output Current
220 ' Iomin = Minimum Output Current
230 '
240 ' Start with parameters for low voltage dc/dc buck regulator
250 '
260 ' ****Define 5 Vi and 5 Io data points ranging from min to max*****
270 ' (Suggestion: With broad ranges, use logarithmic spread)
280 DATA 18,20,22,24,27 : 'Vi data
290 DATA 2.5,4,6,8,10 : ‘Io data
300 FRES = 500000!
310 VO = 5!
320 VDO = .8
330 RDS = .8
340 SAFT = .95
350 '
360 FOR J = 1 TO 5: READ VI(J): NEXT
370 FOR K = 1 TO 5: READ IO(K): NEXT
380 CLS
390 PRINT "For output to screen, enter 'S' or 'S'."
400 INPUT "Otherwise output will be sent to printer : ", K$
410 IF K$ = "S" OR K$ = "s" THEN K$ = "scrn:" ELSE K$ = PRINTER$
420 OPEN K$ FOR OUTPUT AS #1: CLS
430 PRINT #1, "================================================"
440 PRINT #1, "Zero Voltage Switching Times (uSec) vs. Vi, I O ”
450 PRINT #1,"=========================================================="
460 '
3-353
APPLICATION NOTE
U-138
470 ' '========HERE GOES========
480 '
490 VIMAX = VI(5): IOMIN = IO(1): IOMAX = IO(5)
500 ZR = (VIMAX - (RDS * IOMIN)) / (IOMIN * SAFT)
510 WR = 6.28 * FRES
520 CR = 1 / (ZR * WR)
530 LR = ZR / WR
540 '
550 FOR J = 1 TO 5: VI = VI(J)
Input Voltage = ###.## V"; VI
560
PRINT #l, USING "
570
FOR K = 1 TO 5: IO = IO(K)
580
RSIN = (VI / (IO * ZR)):
VDSON = RDS * IO
590 '
600
D(0, K) = IO * .00000l: ' Compensate for later mult. by 10^6
610
D(l, K) = (CR * VI) / IO: 'dtO1
620
D(2, K) = (3.14 / WR) + (1 / WR) * ATN(RSIN / (1 - RSIN ^ 2)): ‘dt12
630
D(3, K) = (2 * LR * IO) / VI: 'dt23
640
D(6, K) = D(1, K) + D(2, K) + D(3, K): ' dt03
650
D(4, K) = ((VO + VDO) * D(6, K)) / ((VI - VDSON) - (VO + VDO)): 'dt34
660
D(5, K) = D(1 K) + D(2, K) + D(3, K) + D(4, K): 'Tconv
670 NEXT K
680 '
690 PAR$(0) = “Io (A) ="
700 PAR$(l) = “dt01 ="
710 PAR$(2) = “dt12 ="
720 PAR$(3) = "dt23 ="
730 PAR$(4) = "dt34 ="
740 PAR$(5) = "Tconv ="
750 PAR$(6) = "dt03 ="
760 '
FOR P = 0 TO 6
770
780
PRINT #1, PAR$(P);
790
FOR K = 1 TO 5
800
PRINT #l, USING " ####.###"; D(P, K) * l000000!;
NEXT K: PRINT #l,
810
820
NEXT P
830 PRINT #l,
840 NEXT J
850 '
860 PRINT #l, "Additional Information:”
870 PRINT #l, “Zr(Ohms) =“; INT(l000! * ZR) / 1000
880 PRINT #l, “wR(KRads)=“; INT(WR / 1000)
890 PRINT #l. "Cr(nF)
=“; INT((l000 * CR) / 10 ^ -9) / 1000
900 PRINT #l, “Lr(uH)
="; INT((1000 * LR) / 10 ^ -6) / 1000
910 PRINT #l, “Vdsmax
="; VIMAX * (1 + IOMAX / IOMIN)
920 END
3-354
APPLICATION NOTE
U-138
I O (A)
dt01
dt12
dt23
dt34
Tconv
dt03
=
=
=
=
=
=
=
Input Voltage
2.500
4.000
0.218
0.136
1.290
1.153
0.931
1.490
1.791
1.387
4.571
3.825
2.439
2.780
= 18.00
6.000
0.091
1.096
2.235
2.682
6.103
3.421
I O (A)
dt01
dt12
dt23
dt34
Tconv
dt03
=
=
=
=
=
=
=
Input Voltage
2.500
4.000
0.242
0.151
1.339
1.175
0.838
1.341
1.150
1.406
3.569
4.074
2.419
2.667
= 20.00 V
8.000
6.000
0.076
0.101
1.079
1.108
2.011
2.682
1.987
2.852
5.207 6.688
3.220
3.836
10.000
0.061
1.062
3.352
4.186
8.661
4.475
I O (A)
dt01
dt12
dt23
dt34
Tconv
dt03
=
=
Input Voltage
2.500
4.000
0.266
0.166
1.390
1.198
0.762
1.219
1.153
0.988
3.406
3.737
2.418
2.584
= 22.00
6.000
0.111
1.120
1.829
1.557
4.616
3.060
V
8.000
0.083
1.087
2.438
2.136
5.744
3.608
10.000
0.067
1.069
3.048
2.958
7.141
4.183
Io (A)
dt01
dt12
dt23
dt34
Tconv
dt03
=
=
=
=
=
=
=
Input Voltage
2.500
4.000
0.290
0.182
1.442
1.223
0.698
1.117
0.870
0.975
3.498
3.301
2.431
2.522
= 24.00
6.000
0.121
1.133
1.676
1.268
4.199
2.930
V
8.000
0.091
1.096
2.235
1.682
5.103
3.421
10.000
0.073
1.075
2.794
2.241
6.183
3.941
I O (A)
dt01
dt12
dt23
dt34
Tconv
dt03
=
=
=
=
=
=
=
Input Voltage
2.500
4.000
0.204
0.327
1.264
0.516
0.993
0.621
0.442
0.793
1.906
3.254
1.464
2.461
= 27.00
6.000
0.136
1.153
1.490
0.983
3.763
2.780
V
8.000
0.102
1.109
1.987
1.253
4.451
3.198
10.000
0.082
1.085
2.483
1.604
5.254
3.650
=
=
=
=
=
V
8.000 10.000
0.068
0.054
1.070
1.056
2.980
3.725
4.118
6.677
8.236 11.511
4.118
4.835
Additional Information:
Zr(Ohms) = 10.526
wR(KRads)= 3140
Cr(nF)
= 30.254
= 3.352
Lr(uH)
Vdsmax
= 135
UNITRODE CORPORATION
7 CONTINENTAL BLVD.. MERRIMACK, NH 03054
TEL. (603) 424-2410. FAX (603) 424-3460
3-355
IMPORTANT NOTICE
Texas Instruments and its subsidiaries (TI) reserve the right to make changes to their products or to discontinue
any product or service without notice, and advise customers to obtain the latest version of relevant information
to verify, before placing orders, that information being relied on is current and complete. All products are sold
subject to the terms and conditions of sale supplied at the time of order acknowledgement, including those
pertaining to warranty, patent infringement, and limitation of liability.
TI warrants performance of its semiconductor products to the specifications applicable at the time of sale in
accordance with TI’s standard warranty. Testing and other quality control techniques are utilized to the extent
TI deems necessary to support this warranty. Specific testing of all parameters of each device is not necessarily
performed, except those mandated by government requirements.
CERTAIN APPLICATIONS USING SEMICONDUCTOR PRODUCTS MAY INVOLVE POTENTIAL RISKS OF
DEATH, PERSONAL INJURY, OR SEVERE PROPERTY OR ENVIRONMENTAL DAMAGE (“CRITICAL
APPLICATIONS”). TI SEMICONDUCTOR PRODUCTS ARE NOT DESIGNED, AUTHORIZED, OR
WARRANTED TO BE SUITABLE FOR USE IN LIFE-SUPPORT DEVICES OR SYSTEMS OR OTHER
CRITICAL APPLICATIONS. INCLUSION OF TI PRODUCTS IN SUCH APPLICATIONS IS UNDERSTOOD TO
BE FULLY AT THE CUSTOMER’S RISK.
In order to minimize risks associated with the customer’s applications, adequate design and operating
safeguards must be provided by the customer to minimize inherent or procedural hazards.
TI assumes no liability for applications assistance or customer product design. TI does not warrant or represent
that any license, either express or implied, is granted under any patent right, copyright, mask work right, or other
intellectual property right of TI covering or relating to any combination, machine, or process in which such
semiconductor products or services might be or are used. TI’s publication of information regarding any third
party’s products or services does not constitute TI’s approval, warranty or endorsement thereof.
Copyright  1999, Texas Instruments Incorporated