MEANWELL DR-120

120W Single Output Industrial DIN RAIL Power Supply
DR-120
series
Features :
AC input range selectable by switch
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
LED indicator for power on
100% full load burn-in test
Fixed switching frequency at 55KHz
3 years warranty
SPECIFICATION
MODEL
OUTPUT
INPUT
DR-120-12
DR-120-24
DR-120-48
DC VOLTAGE
12V
24V
48V
RATED CURRENT
10A
5A
2.5A
CURRENT RANGE
0 ~ 10A
0 ~ 5A
0 ~ 2.5A
RATED POWER
120W
120W
120W
RIPPLE & NOISE (max.) Note.2 80mVp-p
80mVp-p
100mVp-p
VOLTAGE ADJ. RANGE
24 ~ 28V
1.0%
48 ~ 53V
1.0%
12 ~ 14V
VOLTAGE TOLERANCE Note.3 2.0%
LINE REGULATION
0.5%
0.5%
0.5%
LOAD REGULATION
1.0%
1.0%
1.0%
SETUP, RISE TIME
500ms, 70ms/230VAC
HOLD UP TIME (Typ.)
VOLTAGE RANGE
36ms/230VAC
32ms/115VAC at full load
88 ~ 132VAC/176 ~ 264VAC by switch
248 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
80%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
2.6A/115VAC
LEAKAGE CURRENT
OVERLOAD
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
SAFETY &
EMC
(Note 4)
85%
COLD START 20A/115VAC
40A/230VAC
<3.5mA / 240VAC
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
29 ~ 33V
58 ~ 65V
15 ~ 16.5V
Protection type : Shut down o/p voltage, re-power on to recover
90
5 (TSW1)
90
5 (TSW1)
85
5 (TSW1)
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
-10 ~ +60 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-20 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
EMI CONDUCTION & RADIATION Compliance to EN55011,EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
HARMONIC CURRENT
DIMENSION
PACKING
NOTE
84%
1.6A/230VAC
ISOLATION RESISTANCE
EMS IMMUNITY
MTBF
OTHERS
500ms, 70ms/115VAC at full load
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
136.8Khrs min. MIL-HDBK-217F (25
65.5*125.2*100mm (W*H*D)
0.79Kg; 20pcs/16.5Kg/1.29CUFT
)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
File Name:DR-120-SPEC 2008-04-07
DR-120
120W Single Output Industrial DIN RAIL Power Supply
Mechanical Specification
Case No. 921A
series
Unit:mm
100
125.2
+V ADJ.
230VAC
65.5
1
2
3
115VAC
TB1
TB2
1
2
3
4
LED
Terminal Pin No. Assignment (TB1)
35
Pin No.
1
2
3
ADMISSIBLE DIN-RAIL: TS35/7.5 OR TS35/15
Terminal Pin No. Assignment (TB2)
Pin No.
1,2
3,4
Block Diagram
Assignment
DC OUTPUT +V
DC OUTPUT -V
fosc : 55KHz
230
115
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
Assignment
FG
AC/N
AC/L
RECTIFIERS
&
FILTER
POWER
SWITCHING
+V
-V
DETECTION
CIRCUIT
FG
O.L.P.
O.T.P.
Derating Curve
PWM
CONTROL
O.V.P.
Static Characteristics (24V)
48V
OUTPUT VOLTAGE (V)
100
80
LOAD (%)
60
12V,24V
40
20
350
28
300
24
250
20
200
16
150
12
100
80
8
-10
0
10
20
30
45
50
AMBIENT TEMPERATURE ( )
60 (VERTICAL)
OUTPUT RIPPLE (mVp-p)
Ta=25
32
80
160
85
170
90
180
95
190
100
200
105
210
110
220
115
230
120
240
125
250
130
260
INPUT VOLTAGE (V) 60Hz
File Name:DR-120-SPEC 2008-04-07