MEANWELL SCN-1K2-24

1200W Single Output With Parallel Function
SCN-1K2
series
Features :
AC input 200~260V only
Protections: Short circuit / Overload / Over voltage / Over temp.
High reliability/ Low ripple noise
Built-in remote sense function
Built-in remote ON-OFF control
Built-in parallel operation function
Can adjust from 20~100% output voltage by external control 1-5V
Forced air cooling by built-in DC fan
Case coating with paint
2 years warranty
SPECIFICATION
ORDER NO.
SCN-1K2-05
SCN-1K2-12
SCN-1K2-15
SCN-1K2-24
SCN-1K2-48
1K2S-N012
1K2S-N015
1K2S-N024
1K2S-N048
DC VOLTAGE
1K2S-N005
5V
12V
15V
24V
48V
RATED CURRENT
180A
100A
80A
50A
24A
CURRENT RANGE
0 ~ 180A
0 ~ 100A
0 ~ 80A
0 ~ 50A
0 ~ 24A
RATED POWER
900W
1200W
1200W
1200W
1152W
120mVp-p
150mVp-p
240mVp-p
480mVp-p
SAFETY MODEL NO.
OUTPUT
RIPPLE & NOISE (max.) Note.2 100mVp-p
VOLTAGE ADJ. RANGE
5.0% typical adjustment by potentiometer
1.0%
VOLTAGE TOLERANCE Note.3 2.5%
20 ~ 100% adjustment by 1 ~ 5VDC external control
1.0%
1.0%
1.0%
LINE REGULATION
0.5%
0.5%
0.5%
0.5%
0.5%
LOAD REGULATION
2.0%
0.5%
0.5%
0.5%
0.5%
SETUP, RISE, HOLD UP TIME 800ms, 50ms, 16ms at full load
INPUT
VOLTAGE RANGE
200 ~ 260VAC 290 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
77%
11A / 230VAC
AC CURRENT
INRUSH CURRENT (max.)
OVERLOAD
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
(Note. 4)
OTHERS
NOTE
120A / 230VAC
3.5mA / 240VAC
WORKING TEMP.
WORKING HUMIDITY
ISOLATION RESISTANCE
87%
85%
101 ~ 115%
110 ~ 135% rated output power
Protection type : Current limiting, delay shut down o/p voltage, re-power on to recover
OVER TEMPERATURE
EMC
85%
LEAKAGE CURRENT (max.)
PROTECTION OVER VOLTAGE
SAFETY &
83%
110 ~ 135% follow to output set up point
Protection type : Shut down o/p voltage, re-power on to recover
>100
/ measure by heat sink, near transformer
Protection type : Shut down o/p voltage, re-power on to recover
-10 ~ +65 (Refer to output load derating curve)
20% ~ 90% RH non-condensing
-20 ~ +85
0.04% /
, 10 ~ 95% RH
(0 ~ 50 )
10 ~ 200Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
UL60950-1, CSA22.2, IEC60950 approved
I/P-O/P, I/P-FG :1500VAC
I/P-O/P, I/P-FG, >100M Ohms / 500VDC / 25
/ 70% RH
EMI CONDUCTION & RADIATION Compliance to FCC part 15 class A
---HARMONIC CURRENT
EMS IMMUNITY
MTBF
---60Khrs min. MIL-HDBK-217F (25
DIMENSION
PACKING
SPECIAL FUNCTION
291*132*132mm (L*W*H)
4.75kg ; 4pcs/20kg/CARTON
DC voltage adj., Remote sensing, remote control, parallel operation (refer to terminal instruction manual)
)
1.All parameters are specified at 230VAC input, rated load, 25 70% RH ambient.
2.Tolerence: includes set up tolerance, line regulation, load regulation.
3.Ripple & noise are measured at 20MHz by using a 12" twisted pair terminated with a 0.1uf & 47uf capacitor.
4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
File Name:SCN-1K2-SPEC 2008-05-06
SCN-1K2
1200W Single Output With Parallel Function
Mechanical Specification
series
Unit:mm
291
200
199.5
L N FG
#6-32-4
M3(NUT).x3H-4
30
132
AC INPUT
VS+
VSVCI
VCD
GND
PAR
GND
INH
14.5
50.5
41
V ADJ
LED
15
POS+
291
250
32
POS
M6
7.5
AC INPUT
BUTTON SIDE
NEG
DC OUTPUT
Air flow
direction
132
9.5
M3(NUT)x3H-4
115
9
NEG-
Terminal Pin No. Assignment
Pin No.
1
2
3
Control terminal Pin No. Assignment (CN1) : Dinkle 51HDBC-O8P or equivalent
Assignment
AC/L
AC/N
FG
Pin No.
1
2
3
4
Assignment
VS+
VSVCI
VCO
Assignment
Mating With
GND
PAR
Dinkle 51SDB-O8P
or equivalent
GND
INH
Pin No.
5
6
7
8
External DC Control VS Output Voltage
Derating Curve
O.V.P.
Vout
100
OUTPUT VOLTAGE (%)
LOAD (%)
100
50
-10
0
10
20
30
Ta (
40
)
50
60
80
non-linear
60
40
20
V
1
2
3
4
5
EXTERNAL VOLTAGE(Typical)
File Name:SCN-1K2-SPEC 2008-05-06
SCN-1K2
1200W Single Output With Parallel Function
series
Control terminal instruction manual
LOAD
LOAD
VS+
VSVCI
VCO
GND
PAR
GND
INH
VS+
VSVCI
VCO
GND
PAR
GND
INH
USING INTERNAL VOLTAGE CONTROL
LOAD
VS+
VSVCI
VCO
GND
PAR
GND
INH
ON/OFF SWITCH
ON/OFF CONTROL BY SWITCH
REMOTE SENSING
LOAD
LOAD
VS+
VSVCI
VCO
GND
PAR
GND
INH
VS+
VSVCI
VCO
GND
PAR
GND
INH
H:ON
L:OFF
DC 1-5V
OUTPUT VOLTAGE ADJUST WITH DC 1-5V
ON/OFF CONTROL BY TRANSISTOR
LOAD
VS+
VSVCI
VCO
GND
PAR
GND
INH
VS+
VSVCI
VCO
GND
PAR
GND
INH
VS+
VSVCI
VCO
GND
PAR
GND
INH
PARALLEL OPERATION WITH REMOTE SENSING
LOAD
VS+
VSVCI
VCO
GND
PAR
GND
INH
VS+
VSVCI
VCO
GND
PAR
GND
INH
VS+
VSVCI
VCO
GND
PAR
GND
INH
PARALLEL OPERATION
File Name:SCN-1K2-SPEC 2008-05-06