SP1650 & SP1660 Celab CATV Uninterruptible Power Supply MAINS AC SUPPLY Input Voltage 230V AC +15% -10%, Single Phase Input Frequency 50Hz +/- 6% Input Current 8A rms Inrush Current 30A Max for <10mS Power Factor >0.95 Insulation to earth and to outputs to the requirements of EN60950 ■ ■ ■ ■ Occupies same volume as non battery backed CVT power system. Integral battery management with 10A charging facility. Operation Configurable by microprocessor controller. Remote monitor and control facility by RS232 interface. BATTERY MANAGEMENT Float Voltage Charging Current Protection Battery Good Test Battery Present Test SYSTEM MANAGEMENT Alarms AC OUTPUT Output Voltage 56 to 63VAC rms Adjustable, Factory set to 60VAC rms Output Frequency 50Hz +/- 6%, Quasi-square Output Current Range 0 - 15A rms Line Regulation +/- 1% Short Circuit Current <25A (before unit shuts down) Output Over Voltage 70V +/- 2VAC Trip & Reset Output Voltage Drift <20mV/°C 55.8V +/- 0.3V at 20°C, temperature compensated 0 - 10A Max, depending on battery charge state. Current limit field selectable, 5A or 10A Low Battery Detection, Invertor Shutdown, Battery Input, Fuse 30A Automatically check battery condition on load every 7 days for 10 minutes Automatically check every hour if the battery is present. Alarm 1: AC Input Mains Good Alarm 3: AC/DC Convertor Good Alarm 5: Alarms 1-4 in series Alarm 2: AC Output Good Alarm 4: Battery Good Alarm 6: Battery Present Alarm 7: Battery Charger Good Alarm 8: Alarms 1-4 & 6-7 Six Green LED’s All alarms are available via 37 way D type socket and are isolated relay contacts Analogue Outputs PSU Heatsink Temperature: 50 mV/°C CATV Output VAC: 0.1 VDC/Vrms CATV AC Output Current 0.1 VDC/Arms Battery Voltage 0.1 VDC/VDC Battery Charging Current 1 VDC/ADC All analogue outputs are available via 37 way D type socket Serial Interface An RS232 serial communications interface will be provided. The output information that will be available from this port will include the alarm status and the analogue signals as defined above. The interface will also enable the activation of the Battery Good Test and the Battery Present Test. Thermal Protection Heatsink temperature 80°C, internal fan operation Heatsink temperature 100°C the system will switch to battery backup operation until heatsink has fallen to normal level. ENVIRONMENTAL CONDITIONS AND STANDARDS MECHANICAL FORMAT OPTIONS Working Temperature Storing Temperature Enclosure Safety The SP1650 is housed in a backboard mounting enclosure Height: 410mm Depth: 210mm Width: 170mm Weight: <10Kg The SP1660 is housed in a 19” rack mounting enclosure Height: 3U(133mm) Depth: 210mm Width: 405mm Weight: <10Kg Electrical Connection SP1650 on front & RH panels SP1660 on front panel only EMC -20 to +65°C -25 to +85°C To IP20 EN60950 (Class 1 Equipment) CE Marked LVD Compliant EN50081-1 (emissions) EN50082-1 (immunity) EN6100-3-2 (mains harmonics) EN61003-3 (mains fluctuatuions) Mains Input AC Output Battery Input Temperature Sensor Alarms, Remote Enable Serial Interface RS232 Murata Power Solutions (Celab) Ltd, 25 Woolmer Way, Bordon, Hampshire, GU35 9QE www.murata-ps.com/celab Fused IEC connector Screw Terminals rising clamp type 4 way Beau Type 2 way Molex Mini - Fit JNR 37 way D type socket 9 way D type socket Tel: +44 (0) 1420 477011 Fax: +44 (0)1420 487476