MURATA-PS SP1490

SP1490
Celab
Telephony / CATV Uninterruptible Power Supply
Specification
■
■
■
■
■
■
■
4U high, including telephony distribution module.
Designed for street cabinet applications.
Non latching thermal protection.
10A Telephony output, 15A CATV output.
Separate 4A battery charging current.
Automatic and remote controlled battery condition testing.
Comprehensive management alarms.
Protective Features
Insulation - Input to Chassis
Insulation - Input to Output
Safety Standards
Telco Current Limit
CATV Current Limit
Telco Overvoltage Protection
CATV Overvoltage Protection
Telco Low Battery Disconnect
CATV Low Battery Disconnect
Auto Battery Test Feature
Input Voltage
230VAC, +15% - 10% Single Phase
Input Frequency
47 to 64Hz
Input Filtering
EMC meets requirement of EN50081-1 & EN55022
Inrush Current
Typically 30A peak for <10ms
Telco Output Voltage
56VDC +/- 0.5V
Telco Output Current
10A DC
Telco Output Regulation
Load +/- 1%, Line +/- 0.2%
Telco Output Noise & Ripple
100mV peak to peak, 0 to 20 MHz
CATV Output Voltage
60VAC rms (Quasi Squarewave)
CATV Output Current
0-15A
CATV Output Regulation
Load +/- 2%, Line +/- 0.2%
Battery Charging Current
4A DC
Efficiency
>85% at full load
Operating Temperature
-20°C to +65°C
Storage Temperature
-20°C to +100°C
Temperature Coefficient
0.02% per °C
1500Vrms
Insulation - Output to Chassis
100Vrms
3750Vrms
Insulation - Output to Output
100Vrms
Meets BSEN60950
Trip and restart, 20A +/- 1A
Onset and foldback, 25A +/- 1A
64V +/- 1V
70V +/- 1V
42V +/- 0.5V
46V +/- 0.5V or higher by manual intervention
The power supply will automatically load check the battery condition approximately every 20 days (or longer if required) for approximately 20 minutes to establish the connection of the battery.
Provision is made in the alarm connector for this test to be overridden and initiated remotely.
Alarms
The following alarms are isolated and are available as N/O or N/C relay contacts. In normal running conditions, the alarm relays are energised.
Those marked * have an additional Green LED indicator, lit when ‘good’.
Input Mains*
Telco Output*
Power Supply*
CATV Output*
Battery*
Over-Temperature
Displays
Array’s for Current Outputs 2 x 8 LED (6 Green, 1 Amber, 1 Red) Alarm Indicators
5 LED (Green)
Connectors
Mains Input
Telco Output
CATV Output
Battery Input
Alarms
Size
Weight
IEC 320 connector with 10A fusing
See Telco Distribution Module
2 connectors each rated at 15A
See Telco Distribution Module
37 way D type
19” rack x 4U high x 280mm deep behind panel, 40mm max. in front of mounting rail.
15kg
Telco Distribution Module (TDM)
This is a separate module which forms part of the power supply front panel. It contains fused telco outlets plus the battery input connector (30A). Should it be
necessary to change the power supply this module can be detached and still maintain battery support for telco operation.
Alternative distribution configurations can be provided in the TDM according to particular user needs.
Murata Power Solutions (Celab) Ltd, 25 Woolmer Way, Bordon, Hampshire, GU35 9QE
www.murata-ps.com/celab
Tel: +44 (0) 1420 477011
Fax: +44 (0)1420 487476