ETC 2002ALMHL-AXXX-6

Dual Trip Amplifiers
2002ALM
The 2002ALM family of trip-amplifiers can accept a wide
range of inputs including 4-20mA, thermocouple, RTD and
voltage types
■
Wide range of configurable inputs
■
Configurable trip action and failsafe mode
■
Isolated input stage
■
Setpoints available on front panel
See 4002ALM for mains version
Options and ordering codes
2002ALM HL – A
XXX
–
6
Input type
4-20mA
HL
A
0-20mA
HL
B
0-30mA 2 sec delay
HL
C
0-1mA
HL
D
0-5Vdc
HL
E
1-5Vdc
HL
F
0-10Vdc
HL
G
18-26Vdc
HL
H
0-1A rms
HL
M
0-5A rms
HL
N
Type K 0-150˚C
TC
P
Type K 0-200˚C
TC
Q
Type K 0-250˚C
TC
R
Type K 0-500˚C
TC
S
Type K 0-600˚C
TC
T
Type K 0-1200˚C
TC
U
Type J 0-250˚C
TC
W
Pt100 3 wire ±100˚C
RTD
Y
Pt100 3 wire ±50˚C
RTD
Z
Pt100 3 wire ±30˚C
RTD
1
Pt100 3 wire 0-50˚C
RTD
2
Pt100 3 wire 0-100˚C
RTD
3
Pt100 3 wire 0-150˚C
RTD
4
Pt100 3 wire 0-200˚C
RTD
5
Pt100 3 wire 0-250˚C
RTD
6
Pt100 3 wire 0-400˚C
RTD
7
6
24Vdc/
24Vac
Other ranges and thermocouple types are available as detailed in the product
description, please contact our sales department.
PRICE
INFORMATION
AND ORDERING
Description
The 2002ALM family of trip-amplifiers can accept a wide
range of inputs including 4-20mA, thermocouple, RTD
and voltage types. The unit can have up to two relay
outputs and each can operate as a high or a low trip.
The relay outputs are single pole change-over relays
with mains voltage rating. Each trip can be configured
so that the alarm condition can be above or below
setpoint. The relays can be energised or de-energised in
the alarm condition, satisfying fail-safe and non-fail-safe
applications. In addition the alarm LEDs can be selected
to light when the relay is either on or off. All these
options may be specified at point or order but are user
configurable using internal link selectors. This
minimises the number of spare units required.
The input stage is fully isolated as an option and the
input type can be user-configured. For the current and
voltage input version the range may also be reconfigured. For the thermocouple the RTD input
versions the device type and range are selectable. Again
these can also be specified at point of order.
It is also possible to specify a latching function on the
relay outputs, making the unit ideal for lock-out
applications. The unit can be powered from a wide range
of power supplies, ranging from 12Vdc to 24Vac, please
specify with order.
2002ALM
Description
Inputs
The input types and ranges included below are our standard ones
only. Contact sales for others.
2002ALMTC for Thermocouples
Types E, J, K, N, R, S and T non-linearised
Ranges 0-250, 0-500, 0-1200˚C (Others available)
Auto cold junction compensation. Open cct t/c can drive either
upscale or downscale.
2002ALMHL and DC current and voltage
0-20mA, 4-20mA, 0-10mA into 15Ω/30Ω
0-1V, 0-10V, 1-5V into 100kΩ/1MΩ
Min and Max full scale ranges:
DC current
0 to 50µA
0 to 10A
DC voltage
0 to 100mV
0 to 300V
Note: For input voltages greater than 30Vac or 60Vdc a divider unit
must be specified.
2002ALMRTD for Resistance Thermometers
2 or 3 wire Pt100 or other, linearised output
Ranges 0-250, 0-500, -100-100˚C (others available)
Outputs
Mains rated relays are 3A resistive at 240Vac.
Note: If one relay is switching >115Vac the isolation between the two
relay outputs is not safety isolation.
The default setting on the relay operation is set to Hi/Lo. The LED is
set on when energised.
Please specify the correct operation when ordering, if different from
above.
Specifications
Parameter
Supply voltage
Supply current
Input impedance (volt)
Input impedance (mA)
Volt drop (mA input)
Trip point accuracy
Temperature coefficient
Trip point drift
Time constant (10-90%)
Operating ambient
Relative humidity
Isolation voltage
Surge voltage
Notes
Min
Typ
24Vdc
100kΩ
0.02Ω
1MΩ
15Ω
0.3
Max
45mA
10MΩ
5kΩ
0.35
±0.25%
±100ppm/˚C
-100ppm/˚C
Comments
Options: 12, 24Vdc or 24Vac
24V supply, both relays energised
Dependent on range (Typ=10V)
Dependent on range (Typ=20mA)
At 20mA input
10ms
0˚C
0%
1kV
55˚C
90%
2.5kV for 50µS
Transient of 10kV/µS
Setpoints are adjusted by 20 turn potentiometers on the front panel.
Setpoints can be checked by measuring the 0-1V (0-100%) voltage on the front panel terminals.
H/H, H/L, L/H, LL, fail-safe, non-fail-safe and LED options are user selectable using internal links.
Hysteresis is set at 1.0% but other values are possible, please specify if required.
The process input level is available as 0-1V (0-100%) on terminal 9.
Figures based on HL version, 24Vdc supply, 20˚C ambient.
▲
104.5mm
98mm
▲▲
▲
Dimensions and connections
123
Connection details
▲
456
10. Power input -ve
11. Power input +ve
75mm
7. Process input -ve T/C -ve
8. Process input +ve T/C +ve
9. Signal O/p (0-1V)
12. Setpoint -ve
▲
▲
22.5mm
▲
789
10 11 12
1.
2.
3.
4.
5.
6.
Relay
Relay
Relay
Relay
Relay
Relay
1
1
1
2
2
2
T/C shield
common
N/C
N/O
common
N/C
N/O
PRICE
INFORMATION
AND ORDERING
RTD -ve
RTD +ve
RTD 3rd wire