ETC 2116

2132
2116
d
e
v
MODELS
o
r
p
m r
i
th me
i
i
w
t
.
.
.
Model 2132
1/32 DIN (48 x 24mm)
EUROTHERM
ON TROL S
Model 2116
1/16 DIN (48 x 48mm)
PID Temperature Controllers
Ideal for:
• Ovens
• Chillers
• Sterilisers
• Trace heating
• Heat sealing
Available in compact 1/32 and 1/16 DIN panel sizes, the 2132 and
2116 temperature controllers are designed for accurate, trouble free
control of ovens, chillers, sterilisers and other simple heating and
cooling processes. Two outputs are configurable for heating, cooling
and alarms.
Eurotherm’s advanced control techniques give stable “straight-line”
temperature control. Self tuning is included to optimise the control
performance without the need for specialist knowledge or training.
Heater failure can be detected when the controller is used with a
Eurotherm TE10S Solid State Relay (requires PDSIO mode 1).
Three internal alarm setpoints are provided, configurable as latching
or non-latching. Alarms can be “blocked” on start-up to prevent
unnecessary operator alerts.
Calibration accuracy is maintained with a self-correcting input
circuit. User calibration allows offsets to be applied to compensate
for sensor and other system errors.
Improved timer
An improved timer can apply heating (and cooling) for a pre-set
period, or delay heating to come on after a set time. The latter is
useful for over-night batch processing.
Features:
• Universal input
Covers a wide range of temperature and process inputs
• Self tuning
Easy commissioning
• In-built timer
Sets heating/cooling times
• Setpoint rate limit
Provides ramp-dwell heat treatment profile
• Tactile buttons
Friendly to use
• Wide-range 85-264V ac,
or 20-29Vac/dc supply
Can be installed world-wide
• Plug-in from front
Rapid replacement - reducing downtime
• IP65 and NEMA 4X
panel sealing
Can be used in wet and dusty atmospheres
• Three year warranty
Low ownership cost
PID
Temperature
Controllers
Dimensions
2132
2116
103 mm (4.01in)
48 mm (1.89in)
- 0.0
+ 0.3
22.2
2132
24 mm
(0.95in)
Panel cut-out
Panel cut-out
103 mm (4.01in)
48 mm (1.89in)
2116
- 0.0
- 0.0
+ 0.6
45 x 45 mm + 0.6
OP1
x 45 mm
OP1
OP2
48 mm
(1.89in)
OP2
- 0.00
+ 0.02
1.77 x 1.77in
- 0.0
+ 0.01
0.88
- 0.0
+ 0.02
x 1.77in
Electrical connections
2132
Low voltage supply
2116
External
Relay
Module
24
20-29Vac/dc
L
Line
85-264Vac
Neutral
N
1B
1A
AA
External
Relay
Module
24
Output 2
(Relay)
AB
OR
1A
Solid
State
Relay
OR
1B
V+
+
Output 1 1A
(Logic)
1B -
Solid
State
Relay
T/C
Output 1
(Logic)
1B
-
1A
+
V-
V+
AA
Outpt 2
(Relay)
T/C
Supply voltage:
85-264Vac, 48-62Hz, or 20-29Vac/dc, 5watts max
Operating ambients:
0-55°C, 5-95%RH non-condensing
Output ratings:
Logic: 9Vdc, 12mA (non-isolated)
(Can also be used as alarm acknowledge, keylock
and timer start/stop input)
Relay: 2A, 264V ac resistive
Calibration accuracy:
± 1°C or ± 0.25% of reading whichever is greater
Cold junction compensation:
>15 to 1 rejection of ambient temperature change
Input filtering:
Off to 999.9 seconds
L
N
Neutral Line
85-264Vac
PT100
20-29Vac/dc
24
24
mA Input
2.49Ω
Low voltage supply
Sensor inputs
Ordering Code
Model
Number
Model Number
2132 48 x 24mm unit
2116 48 x 48mm unit
Function
CC
NF
TC
TN
PID Controller
ON/Off Controller
PID Controller + Timer
ON/Off Contr’ + Timer
Supply Voltage
VH 85-264Vac
VL 20-29V dc or ac
Function
Supply
Voltage
Output 1 (Logic)
XX No function
Logic output
LH Heating
LC Cooling
M1 PDS heater break
detect (note 1)
FH High alarm 1
FL Low alarm 1
DB Dev. band alarm 1
DL Dev. low larm 1
DH Dev. high alarm 1
NW New alarm
Logic input
AC Alarm ack/reset
KL Keylock
TM Timer Off/On
Manual
Output 2 (Relay)
XX
RH
RC
FH
FL
AL
DB
DL
DH
NW
No function
Heating
Cooling
High alarm 2
Low alarm 2
High alarm 2 & low
alarm 3
Dev. band alarm 2
Dev. low larm 2
Dev. high alarm 2
New alarm
Manual
XXX
ENG
FRA
GER
NED
SPA
SWE
ITA
No manual
English
French
German
Dutch
Spanish
Swedish
Italian
Note 1. PDS heater
break detect will transmit
the power demand to a
TE10S Solid State Relay
and read beck a heater
break alarm.
EUROTHERM CONTROLS LIMITED
http://www.eurotherm.co.uk
Output 1
(Logic)
Output 2
(Relay)
Sensor Input
Sensor
Input
Setpoint
Min.
Setpoint
Max.
note 2
note 2
Sales and support in over 30 countries worldwide
Enquiries/orders to: Eurotherm Controls Limited Export Dept., Faraday Close, Durrington, Worthing. West Sussex BN13 3PL.
Telephone (01903) 268500, Fax (01903) 265982
Units
Ext. Relay
Module
Setpoint Min/Max
Thermocouples
J
Type J
K
Type K
T
Type T
L
Type L
N
Type N
R
Type R
S
Type S
B
Type B
P
Platinell II
Resistance thermometer
Z
Pt100
Custom downloaded inputs
C
Type C - W5%Re/W26%Re
(default custom sensor)
D
Type D - W3%Re/W25%Re
E
E Thermocouple
1
Ni/Ni18%Mo
2
Pt20%Rh/Pt40%Rh
3
W/W26%Re (Englehard)
4
W/W26%Re (Hoskins)
5
W5%Re/W26%Re (Englehard)
6
W5%Re/W26%Re (Bucose)
7
Pt10%Rh/Pt40%Rh
8
Exegen K80 I.R. pyrometer
Process inputs (linear)
M
-9.99 to +80mV
Y
0 to 20mA (note 3)
A
4 to 20mA (note 3)
V
0 to 10Vdc (input adapter required)
UK SALES OFFICE
Eurotherm Controls Limited. Faraday Close, Durrington, Worthing, West Sussex BN13 3PL
Telephone Sales: (01903) 695888; Technical: (01903) 695777; Service: (01903) 695444
Fax (01903) 695666
PT100
Timer range:
0-9999 minutes
Setpoint rate limit adjustment:
0-999.9 least significant display unit per minute.
Adjustable hysteresis
Alarm configuration:
High, low, deviation band, deviation high and low
EMC standards:
Meets generic emissions standard EN50081-2 and
immunity standard EN50082-2 for industrial
environments
Safety standard:
Meets EN61010, installation category II. Pollution
degree 2
Atmospheres:
Not suitable for use above 2000m or in explosive or
corrosive atmospheres
Specifications
AB
2.49Ω Sensor
inputs
mA Input
V-
Units
Min °C Max
-210 to 1200
-200 to 1372
-200 to 400
-200 to 900
-200 to 1300
-50 to 1768
-50 to 1768
0 to 1820
0 to 1369
-200
0
Input
Adaptor
to
C
F
K
X
°C
°F
Kelvin
Linear input
External Relay Module
XX Not fitted
R7 Fitted (Operated by the
logic output)
850
to 2319
0
-200
0
0
0
0
10
0
200
-45
to
to
to
to
to
to
to
to
to
to
2399
999
1399
1870
2000
2010
2300
2000
1800
650
-1999
-1999
-1999
-1999
to
to
to
to
9999
9999
9999
9999
Input Adaptor
XX Not fitted
V1 0-10Vdc
A1 0-20mA or 4-20mA
0.1% current sense
resistor (2.49Ω)
Note 2. Setpoint min and
max: include the decimal
position required in the
display value; up to one for
temperature input, up to two
for process inputs.
Note 3. An external 1%
current sense resistor is
supplied as standard. If
greater accuracy is required
specify ‘A1’ in the Input
Adaptor field.
© Copyright Eurotherm Controls Limited 1997
All rights strictly reserved. No part of this document may be stored in a retrieval system, or any form or by any means without prior written permission from Eurotherm Controls Limited. Every effort has been
taken to ensure the accuracy of this specification. However in order to maintain our technological lead we are continuously improving our products which could, without notice, result in amendments or
omissions to this specification. We cannot accept responsibility for damage, injury, loss or expenses resulting therefrom.
Part No. HA026158 Issue 2