SSK451 Multi-Signaling Accessory

SSK451
Multi-Signaling Accessory
Features
• Key-activated test and reset functions
• Sounder horn can be wired for periodic or temporal tone
The System Sensor SSK451 multi-signaling accessory is designed for
use with System Sensor DH100ACDC and DH400ACDC duct smoke
detector models. The accessory installs easily to a double-gang
electrical box.
• Power (green), trouble (amber) and alarm (red) LEDs
• Design permits easy installation to a double-gang electrical box
• Constructed to allow simple addition of PS24LOW strobe and
PS12/24SLENSW “SMOKE” lens for visual alarm signaling to meet
special code requirements in certain jurisdictions
• Compatible with all System Sensor DH100ACDC and DH400ACDC
duct smoke detectors
Agency Listings
S2522
3004795
7300-1653:140
The SSK451 combines a horn feature with the key-activated test and
reset functions. Green, amber and red LEDs provide visual indication
of power, trouble and alarm conditions, respectively.
To meet special code requirements in certain jurisdictions, the
optional PS24LOW strobe and the PS12/24LENSW “SMOKE” lens can
be added without difficulty for visual alarm signaling.
SSK451 Specifications
Physical Specifications
Dimensions
Weight
Electrical/Operating Specifications
Operating Voltage
Power Requirements
Connections
Sounder
Operating Temperature Range
Operating Humidity Range
Listing
4.8˝ W × 4.7˝ H × 1.5˝ D (12.2cm W × 11.9cm H × 3.8cm D
0.35 lb. (160 g)
15–35 VDC
Standby: 5 mA max.
Trouble: 9 mA max.
Alarm: 30 mA max.
Strip terminal, 14 AWG to 22 AWG wire
87 dBA minimum at ten feet
14° F to 140° F (–10° C to 60° C)
95% RH, noncondensing
UL 268A
SSK451 with Innovair™ DH100ACDC Duct Smoke Detector Wiring Diagram
FIELD INSTALLED JUMPER
FOR TEMPORAL PATTERN
COMMON
3
TEMPORAL SELECT
2
15
ALARM SIGNAL
1
3
SUPERVISORY SIGNAL
4
14
RESET
7
2
TEST
8
11
POWER (–)
6
20
AUX. POWER (–)
POWER (+)
5
19
AUX. POWER (+)
ALARM SIGNAL
SUPERVISORY
CONTACT
NO
RESET
TEST
DH100ACDC
SSK451
FIELD INSTALLED JUMPER
SSK451 with DH400ACDC Duct Smoke Detector Wiring Diagram and Test Coil Installation
FIELD INSTALLED JUMPER
FOR TEMPORAL PATTERN
COMMON
3
TEMPORAL SELECT
2
5
ALARM SIGNAL
1
10
SUPERVISORY SIGNAL
4
11
RESET
7
3
RESET
TEST
8
4
TEST
POWER (–)
6
6
AUX. POWER (–)
POWER (+)
5
7
AUX. POWER (+)
SSK451
ALARM SIGNAL
NO
SUPERVISORY
CONTACT
Note: When the SSK451 is used with a DH400ACDC duct smoke detector
with 2451 head, a test coil, part number COIL, must be ordered separately.
When the SSK451 is used with a DH400ACDC duct smoke detector with 2151
head, a test coil, part number COIL400, must be ordered separately. When
the SSK451 is used with a DH100ACDC duct smoke detector, a test coil is
not required. The COIL is installed in the DH400ACDC duct smoke detector
housing as shown below.
DH400ACDC
TEST COIL
DETECTOR
HEAD
FIELD INSTALLED JUMPER
Ordering Information
Part No.
SSK451
Accessories
PS24LOW
PS12/24SLENSW
Description
Innovair Multi-Signaling Accessory
Add-on Strobe
Lens for PS24LOW with “SMOKE” Lettering
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
©2006 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-1021-005 • 11/06 • #1676