SYSTEMSENSOR SP3R1224MC

Selectable Output
Wall Speaker/Strobes
SP2 and SP3 Series Speaker/Strobes offer enhanced
features that include the widest range of candela
options available, the capability to self-adjust for 12
or 24 volt operation, and the fidelity sound quality
expected from SpectrAlert speaker technology.
Performance. SpectrAlert® Selectable Output Speaker/Strobes offer
average current draws that are not only lower than conventional
fixed-candela SpectrAlert products, but also lower than similar
selectable candela products. In addition, the broad frequency
response range and low harmonic distortion provided by SpectrAlert
speaker technology provides an accurate and intelligible broadcast
of evacuation messages.
Installation. SpectrAlert Selectable Output Speaker/Strobes offer a
variety of installation-friendly features, such as the ability to mount to
a 4˝ × 4˝ × 21⁄8˝ back box without the need for an extension ring. Also,
with the field-reversible strobe, the speaker/strobe may be either
left- or right-mounted to avoid potential obstructions.
Flexibility. SpectrAlert Selectable Output Speaker/Strobes offer
the broadest range of candela options. In addition, the 15 cd and
15/75 cd options can operate on either 12V or 24V, with no setting
required; the device recognizes the applied voltage and self-adjusts
to the correct setting automatically. The speaker voltage, either 25.0
or 70.7, and power tap settings, ¼, ½, 1, or 2 watt, are field-selectable.
Features
• Fidelity sound quality (SP2)
• Enhanced SPL (SP3)
• Operates on either 12V or 24V
• Widest range of candela options:
12V: 15 and 15/75 candela options
24V: 15, 15/75, 30, 75, and 110 candela options
• Easy candela selection
• 25.0 and 70.7 volt speaker with four field-selectable power taps
• Field-reversible strobe for left- or right-mounting
• Synchronizable with MDL Sync•Circuit™ Module
• Optional surface-mount back box skirt available
Aesthetics. SpectrAlert Selectable Output Speaker/Strobes
incorporate the same stylish, low profile design as the conventional
SpectrAlert products, for a consistent and aesthetically pleasing
appearance across the entire product line.
Agency Listings
S4048
Selectable Output Speaker/Strobe Specifications
Architectural/Engineering Specifications
Speaker/Strobe shall be a System Sensor Model _____________ listed to UL 1480 and UL 1971 and be approved for fire protective signaling systems. Speaker
shall be capable of operating at 25.0 or 70.7 nominal Vrms, and shall have a frequency range of 400 – 4000 Hz. Speaker shall have power taps that are selected
by shunts. The strobe shall consist of a xenon flash tube with associated lens/reflector system and operate on either 12V or 24V. The strobe shall also feature
selectable candela output, providing options for 15 or 15/75 candela when operating on 12V and 15, 15/75, 30, 75, or 110 when operating on 24V. The strobe
shall comply with the Americans with Disabilities Act requirement for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range.
Physical Specifications
Dimensions
47⁄8˝ × 8¼˝ × 2¼˝
Mounting
4˝ × 4˝ × 21⁄8˝ back box
Indoor Operating Temperature
32°F to 120°F (0°C to 49°C)
Strobe Specifications
Strobe Operating Voltage
12 or 24 VDC and FWR unfiltered
Input Terminals
12 to 18 AWG
Operating Voltage Range
12V: 8–17.5V; 24V: 16–33V
Operating Voltage Range w/Sync•Circuit™ Module 12V: 9–17.5V; 24V: 17–33V
Speaker Specifications
Input Voltage
25.0 or 70.7 Vrms (nominal)
Input Terminals
12 to 18 AWG
Frequency Range
400–4000 Hz
The SP2 and SP3 Series are UL listed from 400 to 4000Hz. The SP2 Series will provide a flat (±10dB)
output from 100 to 15,000Hz. The SP3 Series will provide a flat (±10dB) output from 500 to 13,000 Hz.
Power Taps
¼, ½, 1 and 2 watts
U.S. Patent No.
6,049,446; 6,127,935
Sound Output (UL Reverberant @ 10ft.)
2 Watts
1 Watt
½ Watt
¼ Watt
SP2
84
81
78
75
SP3
89
87
84
81
Reversible Strobe Feature
Removing the strobe screw and lifting the strobe assembly out of the rib slot
allows the strobe to be rotated 180° and remounted to the base resulting in a
left-mounted strobe configuration.
INSERT SCREWDRIVER
TO REMOVE
Explanation of Published Strobe
Specifications
In May 2004, Underwriters Laboratories changed standard UL 1971 to
require that operating current measurements are made using RMS (root
mean square) instead of peak or average values. RMS measurements more
accurately predict the power consumption of a device since they take into
account the entire current draw profile including surge, repetitive surge, and
peak values. The published RMS current is the maximum operating current of
that device within its operating voltage range. This current maximum may or
may not occur at the endpoints of the voltage range.
In May 2004, UL also changed the way they list the voltage range of a device.
All 12V products will be listed between 8–17.5V and all 24V products will
be listed between 16–33V. These devices are considered “regulated.” Any
product that does not operate within these ranges will be listed as a “special
application” with its operating voltage specified on the device.
LOCKING RIB
Ordering Information/Current Draw
Model No.
Description
Wall Speaker/Strobe
Accessories
BBS-SP2R
BBS-SP2W
Red
SP2R1224MC
SP3R1224MC
White
SP2W1224MC
SP3W1224MC
Candela Setting
15
15/75
30
75
110
UL Max. FWR Operating
Current–Strobe (mA RMS)
8–17.5V
16–33V
112
64
135
74
n/a
93
n/a
158
n/a
208
UL Max. DC Operating
Current–Strobe (mA RMS)
8–17.5V
16–33V
127
59
127
69
n/a
90
n/a
160
n/a
209
Surface-mount back box skirt, red
Surface-mount back box skirt, white
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
©2006 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-0339-007 • 7/06 • #1676