XPPOWER DNR960TS24-I

AC-DC
960 Watts
xppower.com
DNR960 Series
•
Rugged Design for Industrial Applications
•
Up to 93% Typical Efficiency
•
Wide Adjustment Range
•
Full Power to 60 ºC
•
Three Phase Operation
•
Single Phase Operation
•
70 ºC Convection Operation.
Specification
Input
General
Input Voltage
• 340-575 VAC 3Ø (1Ø operation with 75%
output derating), 480-820 VDC
Input Frequency
• 47-63 Hz
Input Current
• 1.6 A at 500 VAC
Inrush Current
• 30 A typical at 500 VAC, cold start
Power Factor
• 0.7 at 500 VAC input and nominal load
Earth Leakage Current • 0.32 mA
Output
Efficiency
Isolation
Switching Frequency
Signals
MTBF
Output Voltage
Output Voltage Trim
Initial Set Accuracy
Minimum Load
Start Up Delay
Start Up Rise Time
Hold Up Time
Line Regulation
Load Regulation
Transient Response
•
•
•
•
•
•
•
•
•
•
Ripple & Noise
Overvoltage Protection
Overload Protection
Temperature
Coefficient
Current Share
•
•
•
•
See table
See table
±1%
No minimum load required
<150 ms
<50 ms
20 ms min at 400 VAC
±1%
±1% (±5% for units in parallel)
4% max deviation recovering to within 1%
in 200 µs for 50% load change
80 mV pk-pk 20 MHz BW
125-140%, recycle input to reset
Continuous current limit
±0.02%/°C
• 2 units can be paralleled.
Total output derates by 10%
• See table
• 3000 VAC Input to Output
1500 VAC Input to Ground
500 VAC Output to Ground
• 25 KHz typical
• DC ON indicator LED Green,
DC LOW indicator LED Red
DC OK: normally open relay on
24 V models
• 370 Khrs to Bellcore, SR-332 issue 6,
Model 3
Environmental
Operating Temperature • -25 ºC to 70 ºC, derate linearly from 60 ºC
at 3.5%/ºC (see derating curve)
Cooling
• Convection-cooled
Operating Humidity
• 20-95% RH, non-condensing
Storage Temperature
• -25 °C to +85 °C
Shock
• 4 g peak, 22 ms on X, Y and Z axis
Vibration
• 10 to 500 Hz, 1 g rms on X, Y and Z axis
EMC & Safety
Emissions
Harmonic Currents
Voltage Flicker
ESD Immunity
Radiated Immunity
EFT/Burst
Surge
Conducted Immunity
Magnetic Field
Dips & Interruptions
Safety Approvals
•
•
•
•
•
•
•
•
•
•
EN55022, class B conducted & radiated
EN61000-3-2, class A
EN61000-3-3
EN61000-4-2, level 4 perf criteria A
EN61000-4-3, level 3 perf criteria A
EN61000-4-4, level 4 perf criteria A
EN61000-4-5, level 3 perf criteria A
EN61000-4-6, level 3 perf criteria A
EN61000-4-8, level 4 perf criteria A
EN61000-4-11, 30% 10 ms,
60% 100 ms, 100% 5000 ms
Perf Criteria A, B, B
• EN60950-1:2001, UL508, UL60950-1
Output Voltage
24 V
48 V
AC-DC
DNR960
Models and Ratings
Output Voltage Trim
22.5-28.5 V
47.0-56.0 V
Output Current(1)
40.0 A
20.0 A
Typical Efficiency
92%
91%
Model Number
DNR960TS24-I
DNR960TS48-I
Notes
1. Reduce by 25% for single phase input operation.
Mechanical Details
10.86 (275.7)
0.3
(7.0)
4.39 (111.3)
4.96
(125.9)
1
AC Input
4
DC
LO
1
DC
ON
DC Output
10
Voltage Adj. on underside
Pin Connections - AC Input
Pin
Designation
1
Ground
2
L1
3
L2
4
L3
Pin
1
2
3
4
5
6
7
8
9
10
Notes
1. All dimensions in inches (mm).
2. Weight 7.05 lb (3200 g) approx.
3. Screw terminal: 10-24AWG cable size.
4. DC OK Relay 60 VDC at 300 mA
Pin Connections - DC Output
Designation
DC OK*
DC OK*
+Is
-Is
+V
+V
+V
-V
-V
-V
* Not available on 48 V versions.
Derating Curves
DNR48
DNR960
100
100
65
Load (%)
Load (%)
80
60
40
20
0
-25
0
60
70
-25 -20
-10
0
Ambient Temp (˚C)
10
Ambien
01-Feb-08