XPPOWER DMA21248S12

DC-DC
212 Watts
xppower.com
DMA Series
•
Open Frame Telecom DC-DC Converter
•
-48 VDC Input
•
ETSI Compliant
•
NEBS Compliant
•
5 V Standby & 12 V Fan Outputs
•
Remote On/Off & Power Good Signal
•
AC Input Version Available (EMA212)
Specification
Input
Input Voltage Range
Input Current
Input Reverse Voltage
Protection
Input Transient
Undervoltage Lockout
Protection
Fusing
General
• 48 VDC nominal (36 - 75 VDC).
Can be configured as -48 VDC input
• 5 A typical. 7 A max.
• Continuous protection with
automatic recovery
• Compliant with ETSI EN300 132:2003
• 32 - 35V DC
Efficiency
Isolation Voltage
Switching Frequency
Power Density
Signals
• 15 A F rated in -ve line
Output
Output Voltage
Output Voltage Trim
Minimum Load
• V1: 12 V, see table
• Not fitted
• 10% minimum load required on V1 to
meet all specification parameters of V2 &
V3.
Line Regulation
• V1:±0.5%, V2: ±5%, V3:±3% of nominal
with input variation of 36-75 VDC
Load Regulation
• V1:±1%, V2: ±5%, V3:±3% of nominal
with load variation 10-100%
Setpoint Accuracy
• V1:±1%, V2: ±5%, V3:±3% of nominal
with 48V DC input and 50% load
Turn-on Time
• 2 s typical from application of DC input
Transient Response
• <4% deviation with a 50-75-50% load
change at 1 A/µs. Output returns to within
1% in less than 500 µs
Ripple & Noise
• 1% max pk-pk 20MHz bandwidth
Overvoltage Protection • V1:115-140% of nominal, recycle input
DC to reset
Overload Protection
• V1:110-125% of max current
Short Circuit Protection • Continuous protection, trip and restart
(hiccup mode) characteristic
Temperature
• 0.02%/°C (after 20 minute warm up)
Coefficient
MTBF
Environmental
Operating Temperature • 0 °C to +50 °C with full load, derate
linearly to 50% load at 70 °C with force
cooling 10CFM minimum
Cooling
• Forced cooled (see operating temperature)
Operating Humidity
• 0 to 95% RH non condensing. (1,3)
Storage Temperature
• -40 °C to +80 °C. (2,3)
Storage Humidity
• 0 to 95% RH non condensing.(2,3)
Operating Altitude
• 3000m.(3)
Shock
• ±3 shocks in each axis (total 18 shocks)
30g 11ms (half sine). (1,4)
Vibration
• 2g, 10 - 500Hz 10 sweeps. (1,5)
EMC & Safety
Emissions
EFT/Burst
Surge
Conducted Immunity
Notes
1. Compliant with ETS 300 019-1-3 May 1992 + ammendment 1 June 1997 class 3.1.
2. Compliant with ETS 300 019-1-1 Feb 1992 class 1.1, ETS 300 019-1-2 Feb 1992 class 2.2.
3. Compliant with NEBS GR-63-Core issue 3.
4. Compliant with EN60068-2-27.
5. Compliant with EN60068-2-6.
• 88% typical
• 1500 VDC Input to Output (basic
insulation), 1000 VDC Input to Ground,
500 VDC Output to Ground.
• 60 kHz typical
• 11 W/In3
• Combined input & DC OK - Open collector
referenced to output 0 V, transistor
normally off when input & output good.
Input fail provides ≥5 ms warning of loss
of output from input failure. DC OK
provides warning of DC output failure.
• 550 kHrs per MIL-HDBK-217F
Narrow & Wide
Band Noise
Safety Approvals
• EN61204-3 2000, EN55022 class A
conducted & radiated, ETSI EN 300 132-2
2003, ETSI 300 386-1 1994, NEBS GR1089-CORE issue 4
• EN61000-4-4 level 1 Perf Criteria A, ETSI
300 386-1 1994
• EN61000-4-5 level 1 Perf Criteria A,
• EN61000-4-6 level 2 Perf Criteria A, ETSI
300 386-1 1994, NEBS GR-1089-Core
issue 4
• ETSI EN 300 132-2 2003
• EN60950-1:2006, CSA-C22.2 No. 609501-03, CB Report IEC60950-1:2005,
CE Marked to LVD
Max Output Power
(10 CFM Air Flow)
Output Voltage
V1
Output Current
(10 CFM Airflow)
Fan Output
V2
Standby Supply
V3
Model
Number
212 W
12.0 VDC
16.7 A
12.0 V/1.0 A
5.0 V/0.1 A
DMA21248S12
Mechanical Details
5.00
(127.0)
0.22
(5.7)
0.22
(5.7)
4.55
(115.6)
4 X ø 0.14 (3.5) MOUNTING HOLES
CN2
AIR FLOW
12 CFM
2.55
(64.8)
CN2
CN3
(SCREW TYPE)
CN1
(SCREW TYPE)
1.14
(28.9)
0.23
(5.7)
0.62
(15.8)
1.28
(32.6)
0.23
(5.7)
SAFETY EARTH - 4.8 mm Faston
0.06
(1.6)
PIN CONNECTIONS - CN1
0.08
(2.0)
PIN CONNECTIONS - CN2
PIN CONNECTIONS - CN3
1
-Vin
1
+V2
1
+V1
2
+Vin
2
V2 Return
2
V1 Return
0.25” Faston
Earth
3
V2 Return
4
ROF
5
ROF Return
6
Input Fail/DC OK
7
Current Share
8
+V3
9
-V3
10
+V2
Mating Connectors:
CN2: Molex housing 511101050 and crimp 503948100.
Notes
1.
2.
3.
4.
All dimensions in inches (mm). Tolerance .xx = ±0.02 (0.50); .xxx = ±0.01 (0.25)
Units supplied with screw terminal (CN2) as standard. For faston type, add suffix ‘-F’ to the part number.
All 4 mounting positions should be connected to safety earth.
The air flow needs to be directed through the power supply within the end application.
01-Aug-08
DC-DC
DMA