XPPOWER DRF50US24-N1

AC-DC DIN Rail
50-200 Watts
THE XPERTS IN POWER
DRF Series
Input 187-528 VAC 1Ø
•
•
Adjustable Output
•
High Peak Current Capability
•
Overvoltage Protection
•
Overcurrent Protection
•
International Safety Approvals
Specification
Input
Input Voltage
•
Input Frequency
Input Current
Inrush Current
•
•
•
Power Factor
•
Leakage Current
•
187-528 VAC single phase
(264-746 DC)
47-63 Hz
1.1 A max @ 240 VAC
25/50 A typical @ 240/480 VAC
cold start +25 °C
0.98/0.93 typical at 240/480 VAC
for DRF200
0.75 mA max (1.5 mA DRF200)
Output Voltage
Output Voltage
Adjustment
Minimum Load
Start Up Time
Hold Up Time
•
•
24 VDC nominal
±10%
•
•
•
Drift
Line Regulation
Load Regulation
•
•
•
Ripple & Noise
•
Overvoltage
Protection
•
Overcurrent
Protection
Temperature
Coefficient
Thermal Protection
•
•
No minimum load required
800 ms max with 240 VAC
10 ms (100 ms DRF200) typical at
240 VAC & 100% load
±100 mV max
96 mV max
150 mV 0-100% load,
480 mV max 0-peak load
680 mV pk-pk max 20 MHz bandwidth
& 100% load
115-150% of nominal rating,
recycle input to reset
240 VAC & 100% load
>105% of peak current,
auto recovery
0.04%/°C
•
Recycle input to reset
Output
General
Efficiency
Isolation
•
•
Switching Frequency •
82% typical at 240 VAC
3000 VAC Input to Output
2000 VAC Input to Ground
500 VAC Output to Ground
120 kHz PWM, 50 kHz PFC (DRF200)
Environmental
Operating
Temperature
Storage
Temperature
Humidity
Shock
Vibration
•
•
-10 °C to +70 °C (+60 °C DRF200)
Contact Technical Sales for derating
-20 °C to +75 °C
•
•
•
20-90% non condensing
20 G, 11 ms once on the X axis
2 G 10-55 Hz 3 axis
Emissions
•
ESD Susceptability
Radiated
Susceptibility
EFT/Burst
Surge
Safety Approvals
•
•
EN55022 Level A conducted
EN55022 Level A radiated
EN61000-4-2 Level 2 (Level 4 DRF200)
EN61000-4-3 Level 3
•
•
•
EN61000-4-4 Level 4
EN61000-4-5 Level 3
UL1950, cUL, EN60950, EN50178
EMC & Safety
•
•
www.xpplc.com
[email protected]
OUTPUT VOLTAGE & CURRENT RATINGS
Output
Voltage
21.6 - 26.4 V
21.6 - 26.4 V
21.6 - 26.4 V
DRF
Output Current
Nominal
2.1 A
3.1 A
8.4 A
Model
Number
DRF50US24-N1
DRF75US24-N1
DRF200PS24-N1
Peak(1)
6.7 A
10.0 A
42.0 A
Notes
1. Peak current for 150 ms in every 30 second period. Only available with an input voltage of 240 to 528 VAC.
•
Mechanical Details
DRF50 Model
Weight: <630g
DRF200 Model
Weight: <1700g
DRF75 Model
Weight:<750g
Peak Loading Curves
NOTE: ( ) for DRF200 models
www.xpplc.com
t ≤ 150 ms, 30 s ≤ T
(t ≤ 50 ms, 30 s ≤ T DRF200)
[email protected]
Rev 3.0