ASTRODYNE OFM15

1 5 W U l t r a m i n i a t ure Open Frame Switching Power Supplies
OFM15
Universal 85-265VAC Input
High Efficiency
Regulated Outputs
3000V Isolation
Single and Dual Outputs
UL60950-1, EN60950-1 & IEC60950-1 Approved
1.89”W x 2.76”L x 0.98”H
Model Number
Output Voltage
Output Amps(max)
(pk)
SINGLE OUTPUT
OFM-1500
OFM-1501
OFM-1502
OFM-1503
OFM-1505
3.3 VDC
5 VDC
12 VDC
15VDC
24VDC
3.5A
3A
1.25A
1A
0.63A
3.8A
3.6A
1.5A
1.25A
0.75A
DUAL OUTPUT
OFM-1506
OFM-1507
+/-12VDC
+/-15VDC
+/-0.63A
+/-0.5A
+/-0.8A
+/-0.65A
Order On-Line!
astrodyne.com
series
OFM15/M
1 5 W U l t r a m i n i a t ure Medical Grade Switching Power Supplies
series
Universal 85-265VAC Input
High Efficiency
Regulated Outputs
4000V Isolation
Single and Dual Outputs
UL60601-1, EN60601-1, & IEC60601 Approved
1.89”W x 2.76”L x 0.98”H
Model Number
Output Voltage
Output Amps(max)
(pk)
SINGLE OUTPUT
OFM-1500/M
OFM-1501/M
OFM-1502/M
OFM-1503/M
OFM-1505/M
3.3 VDC
5 VDC
12 VDC
15VDC
24VDC
3.5A
3A
1.25A
1A
0.63A
3.8A
3.6A
1.5A
1.25A
0.75A
DUAL OUTPUT
OFM-1506/M
OFM-1507/M
+/-12VDC
+/-15VDC
+/-0.63A
+/-0.5A
+/-0.8A
+/-0.65A
Order On-Line!
WWW.ASTRODYNE.COM
astrodyne.com
300 Myles Standish Blvd., Taunton, MA 02780
Ph: 1-800-823-8082
Fax: 508-823-8181
1 5 W U l t r a m i n i a t ure Open Frame Switching Power Supplies
INPUT SPECIFICATIONS
Input Voltage Range
Frequency Range
Inrush Current, typ:
series
GENERAL SPECIFICATIONS
85-265 VAC
47-440 Hz
20A@100V, 40A@200V Input *
Input-Out Isolation
I/P-Ground
O/P-Ground
Efficiency
Switching Frequency
See Selection Chart
Singles: +/- 3%, Duals: +/- 3%
Singles +/- 0.1~1%, typ
Duals +/- 0.3~1%, typ
2%
1%
+/- 6% of FS (Primary)
+/-0.03%/°C
100mV Pk-Pk, typ Clamp, 130-150% *
Latching, Cool and Repower
Continuous, self-recovering
20 mS, typ
PHYSICAL SPECIFICATIONS
OUTPUT SPECIFICATIONS
Voltage and Current
Load Regulation (20%-FL)
Line Regulation
Cross Regulation (Duals)
Preset Accuracy
DC Voltage Adjust (typ)
Temperature Coefficient
Ripple/Noise
Over Voltage Protection
Over Temp. Protection
Short Circuit Protection
Hold Up Time
OFM15
All specifications are typical at nominal input, full load, and 25°C unless otherwise noted
* These are stress ratings. Exposure of the devices to any of these conditions
may adversely affect long term reliability. Proper operation under conditions
other than the standard operating conditions is neither warranteed nor implied.
Size
Construction
Weight
3KVAC, (4KVAC Medical)
2500VAC
1000VAC
75%~78%, typ
100Khz, (fixed, typical)
1.89” x 2.75” x 0.98”
Open Frame
2.5oz (70g)
ENVIRONMENTAL SPECIFICATIONS
Oper. Temperature
Storage Temperature
Relative Humidity
EMC
MTBF 0 to +70°C (See Derate)
-25 to +71°C *
0 to + 95%, non-cond *
FCC/A, VDE 0871/A (Mil Std 217, 25°C)
559,000 Hrs
Astrodyne products are not authorized or warranteed for use
as critical components in life support systems, equipment used
in hazardous environments, nuclear controls systems, or other
mission-critical applications.
OFM15
1 5 W U l t r a m i n i a t ure Open Frame Switching Power Supplies
OUTPUT DERATING CURVE
100
90
Load, %
80
70
60
50
40
30
20
0
10
20
30
40
50
60
70
Ambient Temperature, °C
MECHANICAL DIMENSIONS
.83 (21.0)
.070 (1.78)
.040 (1.02)
.150 (3.81)
(-)
(-)
(-)
(-)
(-)
(-)
C3
C2
D3
C5
9
D4
L2
C4
ACL
1
C6
F1
U2
.16 (4.00)
6
1.398 (35.51)
B1
C9
.945 (24.00)
.157 (4.00)
L1
C8
DS1
T1
2
.945 (24.00)
8
U1
C7
1.89 (48.0)
C11
ACN
B2
.492 (12.50)
2.441 (62.00)
2.75 (69.9)
Pin #
Single Outputs Dual Outputs
1
2
6
8
9
AC Line
AC Neutral
+ Output
NC
- Output
AC Line
AC Neutral
+Output
Common
- Output
series