LEM HTA1000-S

IPN = 100..1000 A
Current Transducer HTA 100..1000-S
For the electronic measurement of DC, AC and pulsed currents,
with a galvanic isolation between the primary (high power) circuit
and the secondary (electronic) circuit.
Electrical data
Primary nominal
current rms
IPN (A)
Primary current
measuring range
IPM (A)
100
200
300
400
500
600
1000
ÎP
VOUT
RL
±
±
±
±
±
±
±
300
600
900
1000
1000
1000
1000
Type
HTA
HTA
HTA
HTA
HTA
HTA
HTA
100-S
200-S
300-S
400-S
500-S
600-S
1000-S
Overload capability
Output voltage (Analog) @ ± IPN
Load resistance TA = 0 .. + 70°C
TA = - 25 .. + 85°C
Supply voltage (± 5 %)
Current consumption
Rated isolation voltage rms1)
Rms voltage for AC isolation test, 50 Hz, 1 min
Isolation resistance @ 500 VDC
VC
IC
Vb
Vd
Ris
RoHS since
date code
• Open loop transducer using
46179
46170
46097
46100
46083
46222
46118
Hall Effect
• Panel mounting - Horizontal or
Vertical
• Insulated plastic case recognized
according to UL 94-V0
30,000
±4
>1
>3
± 15
< 25
500
3
> 500
A
V
kΩ
kΩ
V
mA
V
kV
MΩ
±1
± 0.5
< ± 10
%
%
mV
Accuracy - Dynamic performance data
Accuracy 2) @ IPN, TA = 25°C, @ ± 15 V
Linearity error 2) (0 .. ± IPN)
Electrical offset voltage @ IP = 0, TA = 25°C
Hysteresis offset voltage @ IP = 0,
after an excursion of 3 x IPN
Temperature coefficient of VOE TA = - 25 .. + 85°C
Temperature coefficient of VOUT TA = - 25 .. + 85°C
Response time to 90 % of IPN step
di/dt accurately followed
Frequency bandwidth (- 3 dB) 3)
X
ε
L
VOE
VOH
TCVOE
TCVOUT
tr
di/dt
BW
< ± 10
mV
<±1
mV/K
< ± 0.05 %/K
<3
µs
> 50
A/µs
DC .. 50
kHz
General data
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
Standards Safety
EMC
Deviation in output when tested to EN 61000-4-3
Notes :
1)
Features
Advantages
•
•
•
•
•
•
Very good linearity
Very good accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external
interference
• Current overload capability
• Low power consumption
• Wide dynamic range, 100 to 1000 A
in one package.
Applications
• AC variable speed drives and servo
motor drives
• Static converters for DC motor drives
• Battery supplied applications
• Uninterruptable Power Supplies
(UPS)
- 25 .. + 85
- 25 .. + 85
230
°C
°C
g
EN50178 (1994)
EN50082-2(1992)
EN50081-1(1992)
< 25
% of IPN
Overvoltage Category III, Pollution Degree 2
Excludes the electrical offset
3)
Refer to derating curves in the technical file to avoid excessive core
heating at high frequency
• Switched Mode Power Supplies
(SMPS)
• Power supplies for welding
applications.
Application domain
• Industrial
2)
Page 1/2
070110/4
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Dimensions HTA 100..1000-S (in mm. 1 mm = 0.0394 inch)
Bottom view
Left view
Secondary terminals
Terminal
Terminal
Terminal
Terminal
1
2
3
4
: supply voltage + 15 V
: supply voltage - 15 V
: output
: 0V
Front view
Mechanical characteristics
• General tolerance
• Primary through-hole
• Connection of secondary
± 0.5 mm
Ø 32 mm
Molex 5045-04A
Safety
This transducer must be used in electric/electronic equipment
with respect to applicable standards and safety requirements
in accordance with the following manufacturer's operating
instructions.
Remarks
• VOUT is positive when IP flows in the direction of the arrow.
• Temperature of the primary conductor should not exceed
Caution, risk of electrical shock
90°C.
• This is a standard model. For different versions (supply
voltages, secondary connections, unidirectional measurements, operating temperatures, etc.) please contact us.
When operating the transducer, certain parts of the module can
carry hazardous voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious
damage.
This transducer is a built-in device, whose conducting parts
must be inaccessible after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 2/2
070110/4
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com