LEM HAT800-S

Current Transducer HAT 200..1500-S
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
IPN = 200..1500 A
VOUT = ± 4 V
Electrical data
Primary nominal
r.m.s. current
IPN (A)
Primary current
measuring range 4)
IP (A)
200
400
500
600
750
800
1000
1200
1500
VC
IC
R IS
VOUT
ROUT
RL
±
±
±
±
±
±
±
±
±
600
1200
1500
1800
2250
2400
3000
3000
3000
Supply voltage (± 5 %) 4)
Current consumption
Isolation resistance @ 500 VDC
Output voltage @ ± IPN, RL = 10 kΩ, TA = 25°C
Output internal resistance
Load resistance
Type
HAT
HAT
HAT
HAT
HAT
HAT
HAT
HAT
HAT
Features
200-S
400-S
500-S
600-S
750-S
800-S
1000-S
1200-S
1500-S
± 15
± 15
> 1000
±4
100
> 10
• Hall effect measuring principle
• Galvanic isolation between primary
V
mA
MΩ
V
Ω
kΩ
Accuracy-Dynamic performance data
X
ε
L
VOE
VOH
VOT
TCε G
tr
f
Accuracy @ IPN, TA = 25°C (without offset)
Linearity error 1) (0 .. ± IPN)
Electrical offset voltage, TA = 25°C
Hysteresis offset voltage @ IP = 0;
after an excursion of 1 x IPN
Thermal drift of VOE
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
Frequency bandwidth 2) (- 3 dB)
m
Notes :
and secondary circuit
Isolation voltage 3000 V
Low power consumption
Extended measuring range(3 x IPN)
Insulated plastic case recognized
according to UL 94-V0
Advantages
• Easy mounting
• Small size and space saving
• Only one design for wide current
ratings range
< ± 1 % of IPN
< ± 1 % of IPN
< ± 20
mV
• High immunity to external
< ± 10
mV
<±1
mV/K
< ± 0.1
%/K
<5
µs
DC .. 25
kHz
Applications
Ambient operating temperature
- 10 .. + 80
Ambient storage temperature HAT 200-S, HAT 500..1500-S - 15 .. + 85
HAT 400-S
- 25 .. + 85
Mass
300
UL94 classification
V0
interference.
• DC motor drives
• Switched Mode Power Supplies
(SMPS)
• AC variable speed drives
• Uninterruptible Power Supplies
General data
TA
TS
•
•
•
•
°C
°C
°C
g
(UPS)
• Battery supplied applications
• Power supplies for welding
applications
1)
Linearity data exclude the electrical offset.
Please refer to derating curves in the technical file to avoid excessive
core heating at high frequency.
3)
Please consult characterisation report for more technical details and
application advice.
4)
Operating at ±12V ≤ Vc < ±15V will reduce the measuring range.
2)
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM Industrial
051011/9
Page 1/3
www.lem.com
Current Transducer HAT 200..1500-S
Isolation characteristics
Vd
dCp
dCl
CTI
Rated Voltage
with IEC 61010-1 standards and following conditions
- Reinforced insulation
- Over voltage category III
- Pollution degree 2
- Heterogeneous field
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
Creepage distance
Clearance distance
Comparative Tracking Index (Group IIIa)
1000
3
> 11
> 11
275
V
kV
mm
mm
Notes :
051011/9
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM Industrial
Page 2/3
www.lem.com
Dimensions HAT 200..1500-S (in mm. 1 mm = 0.0394 inch)
Top view
HAT-S SERIES
(unit = mm)
=
=
46 Max.
=
38
=
5
12
24
HAT 500-S to 1500-S
12
29
12
Positive curren
currentt flow
65
10
70
30
30.5 x 40.5
10
15.5
1
4
4
Molex 5045-04A
4
6
Pins arrangement
2
3
(-)
Output
1
78
1
(+)
90
Front view
4
0V
All holes O 4.5mm
HAT 200-S
Fixation by base-plate or on bus bar
Mechanical characteristics
• General tolerance
• Transducer fastening
• Connection of secondary
30.5 x 40.5
± 1 mm
By base-plate
or on
432 1
bus bar Molex
with5045-04A
M4
screws.
All slots ∅ 4.5 mm
Molex 5045-04A
Safety
with M4 screws
Pins arrangement:
1
2
3
4
(+)
(-)
Output
0V
This transducer must be used in electric/electronic equipment
with respect to applicable standards
and safety requirements
99/05
in accordance with the following manufacturer's operating
instructions.
Caution, risk of electrical shock
Remarks
• IS is positive when IP flows in the direction of the arrow.
• Temperature of the primary conductor should not exceed
100°C.
When operating the transducer, certain parts of the module can
carry hazardous voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious
damage.
This transducer is a built-in device, whose conducting parts
must be inaccessible after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
051011/9
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM Industrial
Page 3/3
www.lem.com