LEM HY50-P_06

Current Transducers HY 50-P
IPN
=
50 A
For the electronic measurement of currents : DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
Electrical data
Primary nominal
current rms
IPN (A)
Primary current,
measuring range
IPM (A)
50
± 150
VC
IC
ÎP
Vd
Vb
R IS
VOUT
ROUT
RL
Primary
conductor
(mm)
Type
RoHS since
date code
1.6 x 3.5
HY 50-P
45259
Features
Supply voltage (± 5 %)
Current consumption
Overload capability (1 ms)
Rms voltage for AC isolation test, 50 Hz, 1 min
Rated isolation voltage rms
Isolation resistance @ 500 VDC
Output voltage (Analog) @ ± IPN, RL = 10 kΩ, TA = 25°C
Output internal resistance
Load resistance
± 15
± 10
50 x IPN
2.5
500 1)
> 1000
±4
100
>1
V
mA
kV
V
MΩ
V
Ω
kΩ
• Hall effect measuring principle
• Galvanic isolation between primary
and secondary circuit
• Isolation voltage 2500 V~
• Compact design for PCB mounting
• Low power consumption
• Extended measuring range (3 x IPN)
• Insulated plastic case recognized
according to UL 94-V0.
Advantages
Accuracy - Dynamic performance data
X
ε
Accuracy @ IPN, TA = 25°C (excluding offset)
Linearity error 2) (0 .. ± IPN)
Electrical offset voltage @ TA = 25°C
Hysteresis offset voltage @ IP = 0,
after an excursion of 1 x IPN
Temperature coefficient of VOE
L
VOE
VOH
<±1
<±1
< ± 40
< ± 15
typ. ± 1.5
max. ± 3
Temperature coefficient of VOUT (% of reading)
< ± 0.1
Response time to 90% of IPN step
<3
di/dt accurately followed
> 50
3)
Frequency bandwidth (- 3 dB)
DC .. 50
TCVOE
TCVOUT
tr
di/dt
BW
%
% of IPN
mV
mV
mV/K
mV/K
%/K
µs
A/µs
kHz
General data
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
Standards 4)
- 10 .. + 80 °C
- 25 .. + 85 °C
< 14
g
EN 50178: 1997
• Easy mounting
• Small size and space saving
• Only one design for wide current
ratings range
• High immunity to external
interference.
Applications
• General purpose inverters
• Switched-Mode Power Supplies
(SMPS)
• AC motor speed control
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Power supplies for welding
applications.
Application domain
Notes :
1)
2)
3)
4)
Pollution class 2, overvoltage category III.
Linearity data exclude the electrical offset.
Please refer to derating curves in the technical file to avoid excessive
core heating at high frequency.
Please consult characterisation report for more technical details and
application advice.
• Industrial
Page 1/2
061027/5
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Dimensions HY 50-P (in mm. 1 mm = 0.0394 inch)
HY 50-P
PRELIMINARY
36.0 Max.
32.0 Max.
JAPAN
18.0
12 Max.
12.0
HY 50-P
45059
HY 50 - P
JP2
9708
1.6
(0.5)
3.0±0.5
3.5
(0.3)
5.5±0.2
7.0±0.2
17.5±0.3
3 x 2.54
1 2 3 4
5
PCB MOUNTING DIMENSIONS
1.6±0.3
3.9±0.3
6
(in mm ±0.1, hole -0, +0.2)
3.5
HY 50-P
holes dia 2.2
4 holes dia 1
PIN ARRANGEMENT
1
2
3
4
3 x 2.54
5.5
+15V
--15V
OUTPUT
0V
5 PRIMARY IN
6 PRIMARY OUT
17.5
97/02B
Safety
This transducer must be used in electric/electronic equipment
with respect to applicable standards and safety requirements
in accordance with the following manufacturer's operating
instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can
carry hazardous voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious
damage.
This transducer is a built-in device, whose conducting parts
must be inaccessible after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 2/2
061027/5
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com