LEM HX06-P

Current Transducer HX 02..06-P
IPN = 2 .. 6 A
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
Electrical data
Primary nominal Primary current
r.m.s. current
measuring range
IPN (A)
IP (A)
2
3
4
6
VOUT
ROUT
RL
VC
IC
Vd
Ve
±6
±9
±12
±18
Primary Conductor
Diameter x Turns
(mm)
0.5d
0.6d
0.7d
1.0d
x
x
x
x
30T
20T
15T
10T
Type
Features
• Galvanic isolation between primary
HX 02-P
HX 03-P
HX 04-P
HX 06-P
Output voltage @ ± IPN, RL = 10 kΩ, TA = 25°C
Output impedance
Load resistance
Supply voltage (± 5 %)1)
Current consumption
R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn
R.m.s. voltage for partial discharge extinction
at 10pC
Impulse withstand voltage, 1.2/50µs
±4
< 50
≥ 10
± 15
< ± 15
>3
≥1
≥6
V
Ω
kΩ
V
mA
kV
kV
kV
•
•
•
•
•
•
and secondary circuit
Hall effect measuring principle
Isolation voltage 3000V
Low power consumption
Extended measuring range(3x IPN)
Power supply from ±12V to ±15V
Material according to UL94-V0
Advantages
• Low insertion losses
• Easy to mount with automatic
handling system
Accuracy-Dynamic performance data
X
ε
L
VOE
VOH
VOT
TCε G
tr
f
Accuracy @ IPN, TA = 25°C (without offset)
Linearity error (0 .. ± IPN)
Electrical offset voltage, TA = 25°C
Hysteresis offset voltage @ IP = 0;
after an excursion of 3 x IPN
Thermal drift of VOE
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
Frequency bandwidth (-3 dB) 2)
< ± 1 % of IPN
< ± 1 % of IPN
< ± 40
mV
< ± 15
max. ± 1.5
± 0.1
≤ 3
50
mV
mV/K
%/K
µs
kHz
Ambient operating temperature
Ambient storage temperature
Mass
Min. internal creepage distance/clearance
Isolation material group
Standards
ratings range
• High immunity to external
interference.
Applications
• Switched Mode Power Supplies
(SMPS)
• AC variable speed drives
• Uninterruptible Power Supplies
General data
TA
TS
m
• Small size and space saving
• Only one design for wide current
- 25 .. + 85 °C
- 25 .. + 85 °C
8
g
≥ 5.5
mm
I
EN50178
(UPS)
• Electrical appliances
• Battery supplied applications
• DC motor drives
Application Domain
• Industrial
Notes : 1) Also operate at ±12V power supplies, measuring range reduced to ±2.5x IPN
2)
Small signal only to avoid excessive heating of the magnetic cores
Page 1/2
060920/1
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Dimensions HX 02..06-P (in mm. 1 mm = 0.0394 inch)
HX
02..06-P
HX03...25-P
02..25-P
HX
50-P
HXHX50-P
Terminal Pin Identification
19 Max.
19 Max.
20 Max.
3
3
8.8
6
6
3-P=2.54
03-P
0.6
04-P
0.7
06-P
1.0
5
3Secondary
+V
pins dimension
2 0
0.5 x 0.25
1 -V or 0
1.3
3.5
6
5
4.5
2 0
1 -V or 0
02-P
0.6
0.5
4 OUT
3 +V
15.4 Max.
3.5 3-P=2.54
4 OUT
5.4
HX
d
d
15.4 Max.
10.85
Primary conductor diameter
5
3
3.5
3.5
3.5
0.5
0.5
20 Max.
1 ..... -15 V
2 ..... 0 V
3 ..... +15 V
4 ..... Output
5 ..... Primary input Current (+)
6 ..... Primary input Current (-)
1.2
3
10.85
3
8.8
Top view
5.4
HX
HX 05-P
02-P
41123
Lot No.
Terminal Pin Identification
1.....-15V
2.....0V
3.....+15V
4.....Output
5.....Primary input Current(+)
6.....Primary input Current(-)
Primary conductor diameter
/ dimension
HX
Safety
03-P 05-P 10-P
15-P 20-P 25-P 50-P
d
0.6
1.4
0.8
1.1
1.6
1.6
1.2x6.3
Secondary pins dimension
This transducer must be used in electric/electronic equipment
with respect to applicable standards and safety requirements
in accordance with the following manufacturer's operating
instructions.
0.5x0.25
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can
carry hazardous voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious
damage.
This transducer is a built-in device, whose conducting parts
must be inaccessible after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 2/2
060920/1
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com