LEM HAZ4000

Current Transducers HAZ 4000..20000-SB
IPN = 4000..20000 A
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
VOUT= ± 10 V
Electrical data
Primary nominal
DC current or AC peak
IPN (A)
4000
6000
10000
12000
14000
20000
VC
IC
ÎP
RIS
VOUT
ROUT
RL
Primary current
measuring range
IPM (A)
±
±
±
±
±
±
4000
6000
10000
12000
14000
20000
Type
RoHS since
date code
Features
HAZ
HAZ
HAZ
HAZ
HAZ
HAZ
4000-SB
6000-SB
10000-SB
12000-SB
14000-SB
20000-SB
46177
46177
46177
planned
planned
planned
Supply voltage (± 5 %)
± 15
Current consumption
± 30
Overload capability
30,000
Isolation resistance @ 500 VDC
> 1000
Output voltage (Analog) @ ± IPN, RL = 10 kΩ, TA = 25°C ± 10
Output internal resistance
approx.100
Load resistance
> 10
• Hall effect measuring principle
• Galvanic isolation between primary
and secondary circuit
V
mA
A
MΩ
V
Ω
kΩ
Accuracy - Dynamic performance data
X
ε
Accuracy @ IPN, TA = 25°C (excluding offset)
Linearity error 1) (0 .. ± IPN)
Electrical offset voltage @ TA = 25°C, IP = 0
Hysteresis offset voltage @ IP = 0;
after an excursion of 1 x IPN
Temperature coefficient of VOE
Temperature coefficient of VOUT (% of reading)
Response time to 90% of IPN step
Reaction time @ 10% of IPN
di/dt accurately followed
Frequency bandwidth, ± 3 dB, small signal 2)
L
VOE
VOH
TCVOE
TCVOUT
tr
tra
di/dt
BW
<±1
%
< ± 0.5 % of IPN
< ± 50
mV
< ± 12.5
<±1
< ± 0.05
< 10
<2
> 50
DC .. 3
mV
mV/K
%/K
µs
us
A/µs
kHz
General data
TA
TS
Notes :
1)
2)
3)
/1min
• Low power consumption
• Package in PBT meeting UL 94-V0
• Instantaneous voltage output
Advantages
• Easy installation
• Small size and space savings
• Only one design for wide current
ratings range
• High immunity against external
interference
Applications
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Power supplies for welding and
telecom applications.
Application domain
Ambient operating temperature
Ambient storage temperature
Housing PBT 30% glassfiber
Mass
Standard 3)
m
• Instantaneous voltage output
• Isolation voltage 12kV Rms /50 Hz
- 25 .. + 85
- 30 .. + 90
°C
°C
• Industrial
approx. 6
kg
EN 50178:1997
Linearity data exclude the electrical offset.
To avoid excessive core heating
Please consult characterisation report for more technical details and
application advice.
Page 1/3
070219/8
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Current Transducer HAZ 4000..20000-SB
Isolation characteristics
Vb
Vb
Vd
Ve
Vw
dCp
dCl
CTI
Rated isolation voltage rms
with IEC 61010-1 standard and following conditions
- Single insulation
- Over voltage category III
- Pollution degree 2
- Heterogeneous field
Rated isolation voltage rms
with EN 50178 standard and following conditions
- Reinforced insulation
- Over voltage category III
- Pollution degree 2
- Heterogeneous field
Rms voltage for AC isolation test, 50 Hz, 1 min
Partial discharge extinction voltage rms @ 10pC
Impulse withstand voltage 1.2/50 µs
Creepage distance
Clearance distance
Comparative Tracking Index (Group IIIa)
2000
V
2000
V
12
>3
27
> 45
> 45
220
kV
kV
kV
mm
mm
Page 2/3
070219/8
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Dimensions HAZ 4000..20000-SB (in mm. 1 mm = 0.0394 inch)
FUJICON F2023A
6
48
50
6
N.C.
5
4
3
GND OUTPUT
Connection Circuit
1
2
0V -Vc
1
+Vc
HAZxxx-SB
HAZ 10000-SB
250 +/-1.5
1
+Vc
2
-Vc
3
0V
235
4-D6
OUTPUT
5
GND
6
42
41.5
±2
1.5
42+/-1
125
160 +/-1.5
65
4
RL=10K ohm
N.C.
162
161 ± 12
162+/-1
75
Operation Principle
7.5
+Vc
50
48
35
200
Terminal
M5
1...+Vc
2...-Vc
3...0V
4...OUTPUT
5...GND
6...N.C.
General tolerance +/-0.5
Mechanical characteristics
• General tolerance
• Aperture for primary conductor
± 0.5 mm
162 mm x 42 mm
(± 2 mm)
• Transducer fastening
4 x M5
(not supplied)
• Recommended fastening torque < 5 Nm
• Connection of secondary
Fujicon F2023A
(6 terminals)
Remarks
• Temperature of the primary conductor should not exceed
120°C.
• VOUT is positive when IP flows in the direction of the arrow.
Output
0V
Ip
-Vc
Safety
This transducer must be used in electric/electronic equipment
with respect to applicable standards and safety requirements
in accordance with the following manufacturer's operating
instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can
carry hazardous voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious
damage.
This transducer is a built-in device, whose conducting parts
must be inaccessible after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 3/3
070219/8
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com