LEM LA205-S_02

Current Transducer LA 205-S
IPN
=
200 A
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
Electrical data
IPN
IP
ÎP max
RM
Primary nominal r.m.s. current
Primary current, measuring range
Measuring overload 1)
Measuring resistance @
with ± 12 V
with ± 15 V
ISN
KN
VC
IC
Vb
200
0 .. ± 300
600
TA = 70°C
TA = 85°C
RM min RM max RM min RM max
@ ± 200 A max
@ ± 300 A max
@ ± 200 A max
@ ± 300 A max
0
0
5
5
68
33
95
50
Secondary nominal r.m.s. current
Conversion ratio
Supply voltage (± 5 %)
Current consumption
R.m.s rated voltage 2), safe separation
basic isolation
0
0
5
5
A
A
A
ε
transducer using the Hall effect
Ω
Ω
Ω
Ω
66
30
93
49
100
mA
1 : 2000
± 12 .. 15
V
20 (@ ± 15 V) + IS mA
1625
V
3250
V
Overall accuracy @ IPN , TA = 25°C
Linearity
L
± 0.8
< 0.1
IO
IOM
IOT
Offset current @ IP = 0, TA = 25°C
Residual current 3) @ IP = 0, after an overload of 3 x IPN
Thermal drift of IO
- 10°C .. + 85°C
Max
± 0.15
± 0.50
± 0.15 ± 0.30
tra
tr
di/dt
f
Reaction time @ 10 % of IPN
Response time 4) @ 90 % of IPN
di/dt accurately followed
Frequency bandwidth (- 3 dB)
< 500
<1
> 100
DC .. 100
• Closed loop (compensated) current
• Insulated plastic case recognized
Accuracy - Dynamic performance data
XG
Features
%
%
according to UL 94-V0
• Patent pending.
Advantages
•
•
•
•
•
•
•
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
• Current overload capability.
Applications
Typ
mA
mA
mA
ns
µs
A/µs
kHz
• AC variable speed drives and servo
motor drives
• Static converters for DC motor drives
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Switched Mode Power Supplies
(SMPS)
• Power supplies for welding
General data
TA
TS
RS
Ambient operating temperature
Ambient storage temperature
Secondary coil resistance @
m
TA = 70°C
TA = 85°C
- 10 .. + 85
- 40 .. + 90
35
37
110
EN 50178
Mass
Standards 5)
Notes : 1) 3 mn/hour @ VC = ± 15 V, R M = 5 Ω
2)
Pollution class nr 2. W ith a non insulated primary bar which fills the
through-hole
3)
The result of the coercive field of the magnetic circuit
4)
With a di/dt of 100 A/µs
5)
A list of corresponding tests is available
LEM Components
°C
°C
Ω
Ω
g
applications.
020711/6
w w w .lem.com
Dimensions LA 205-S
(in mm. 1 mm = 0.0394 inch)
Front view
Left view
Connection
Top view
Mechanical characteristics
•
•
•
•
General tolerance
Fastening
Primary through-hole
Connection of secondary
Remarks
± 0.5 mm
2 holes ∅ 5.5 mm
23 x 18 mm
Molex 5046-04/AG
• IS is positive when IP flows in the direction of the arrow.
• Temperature of the primary conductor should not exceed
100°C.
• Dynamic performances (di/dt and response time) are best
with a single bar completely filling the primary hole.
• This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.