D-TRIP CHARACTERISTICS ONE POLE ONE POLE PLUS NEUTRAL 1D 2DN Application Examples: High inrush motors, transformers, power supplies, heaters and reactive loads. Relatively long thermal trip delay and very high magnetic trip point. Prototype testing is recommended in motor applications where the relatively long thermal trip delay may not provide adequate motor overload protection. Motor-integral overload protectors are recommended, with the V-EA-D providing disconnect, backup thermal protection and additional short circuit and energy let-through protection. Type Designation 2 D N U — — — — (a) (b) (c) (d) 60 — (e) (a) = Number of Poles (b) = Trip Characteristic (c) = Blank: without neutral pole = N: with neutral pole (d) = U: UL/CSA version = R: ring tongue terminals, UL/CSA version = Blank: European version (e) = Rated Current Approvals: UL508 Listed Rated Current 0.3A 0.5A 0.75A 0.8A❶ 1.0A 1.6A 2.0A 2.5A 3.0A 3.5A 4.0A 5.0A 6.0A 8.0A 10A 12A❶ 12.5A 13A 15A❶ 16A 20A 25A 30A❶ 32A 40A 50A 60A❶ 63A Type/ Cat. No. Approvals 1DU03 1DU05 1DU075 NA 1DU1 1DU1.6 1DU2 1DU2.5 1DU3 1DU3.5 1DU4 1DU5 1DU6 1DU8 1DU10 NA NA 1DU13 1DU15 1DU16 1DU20 1DU25 1DU30 1DU32 1DU40 1DU50 1DU60 1DU63 UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL * * * UL * Type/ Cat. No. 2DNU03 2DNU05 2DNU075 NA 2DNU1 2DNU1.6 2DNU2 2DNU2.5 2DNU3 2DNU3.5 2DNU4 2DNU5 2DNU6 2DNU8 2DNU10 NA NA 2DNU13 2DNU15 2DNU16 2DNU20 2DNU25 2DNU30 2DNU32 2DNU40 2DNU50 2DNU60 2DNU63 Approvals UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL * * * UL * Voltage Rating❸ 277VAC 277VAC Interrupting Capacity (UL/CSA - Ratings) 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB Group Short Circuit (UL/CSA - Ratings) 0.3-10A (RC): 10kA; 13-60A (RC): 5kA no branch circuit protection required 0.3-10A (RC): 10kA; 13-60A (RC): 5kA no branch circuit protection required Interrupting Capacity (VDE - Ratings) 0.3-63A (RC): 10kA 0.3-63A (RC): 10kA Mechanical Endurance 10000 ON/OFF operations❷ 10000 ON/OFF operations❷ Calibration Temperature 40°C (104°F) 40°C (104°F) Standard Pack and Weight 10/0.3A - 32A = 1.4kg (3.1 lb.) 40A - 63A = 1.6kg (3.5 lb.) 5/0.3A - 32A = 1.3kg (2.9 lb.) 40A - 63A = 1.45kg (3.2 lb.) Terminal Size Acceptability Top: 18-3 AWG; Bottom: 18-2 AWG Top: 18-3 AWG; Bottom: 18-2 AWG Terminal Torque 20 lb.in. 20 lb.in. Basic Dimensions (Elevation View) ❶ Not European standard rating. ❷ Please refer to page 21 for specific applications. ❸ DC rating (Manufacturer’s self certification): One pole 48VDC, two pole series 125VDC * VDE pending 91.5 mm (3.60 in.) 17.5 mm (0.69 in.) 91.5 mm (3.60 in.) 35 mm (1.38 in.) Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com 12 TWO POLE THREE POLE Basic Dimensions (side view) 35 mm (1.38 in.) 2D Rated Current Type/ Cat. No. 3D Type/ Cat. No. Approvals 70mm (2.76 in.) Approvals V-EA-D Trip 0.3A Through 10A Rated Current 1.13-1.45xIN UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL * * * UL * Minutes UL UL UL UL UL UL 10 4 1 0.4 UL 10-1 UL 4x10-2 UL UL UL 10-2 4x10-3 10-3 1 UL 2 3 4 5 6 8 10 16 20 40 100 Multiple of Rated Current UL V-EA-D Trip 13A Through 63A Rated Current UL UL 1.13-1.45xIN 60 40 UL UL UL UL UL * * * 10 Thermal Overload “Must Trip” < 1 hr = 145% RC “Must Not Trip” > 1 hr = 113% RC 4 1 UL * 480Y/277VAC 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB 0.3-10A (RC): 10kA; 13-60A (RC): 5kA no branch circuit protection required 0.3-10A (RC): 10kA; 13-60A (RC): 5kA no branch circuit protection required 0.3-63A (RC): 10kA 0.3-63A (RC): 10kA 10000 ON/OFF operations❷ 10000 ON/OFF operations❷ 40°C (104°F) 40°C (104°F) 5/1.4kg (3.1 lb.) 4/1.68kg (3.7 lb.) Top: 18-3 AWG; Bottom: 18-2 AWG Top: 18-3 AWG; Bottom: 18-2 AWG 20 lb.in. 20 lb.in. 35 mm (1.38 in.) Thermal Overload “Must Trip” < 1 hr = 145% RC “Must Not Trip” > 1 hr = 113% RC 4 UL 480Y/277VAC 91.5 mm (3.60 in.) 10 1 UL Tripping time t UL Seconds UL 60 40 UL Minutes 3DU03 3DU05 3DU075 NA 3DU1 3DU1.6 3DU2 3DU2.5 3DU3 3DU3.5 3DU4 3DU5 3DU6 3DU8 3DU10 NA NA 3DU13 3DU15 3DU16 3DU20 3DU25 3DU30 3DU32 3DU40 3DU50 3DU60 3DU63 UL Tripping time t 2DU03 2DU05 2DU075 NA 2DU1 2DU1.6 2DU2 2DU2.5 2DU3 2DU3.5 2DU4 2DU5 2DU6 2DU8 2DU10 NA NA 2DU13 2DU15 2DU16 2DU20 2DU25 2DU30 2DU32 2DU40 2DU50 2DU60 2DU63 10 4 1 0.4 10-1 4x10-2 Seconds 0.3A 0.5A 0.75A 0.8A❶ 1.0A 1.6A 2.0A 2.5A 3.0A 3.5A 4.0A 5.0A 6.0A 8.0A 10A 12A❶ 12.5A 13A 15A❶ 16A 20A 25A 30A❶ 32A 40A 50A 60A❶ 63A 10-2 4x10-3 10-3 1 2 3 4 5 6 8 10 16 20 40 100 Multiple of Rated Current 91.5 mm (3.60 in.) 52.5 mm (2.07 in.) “D” Magnetic Trip Parameters Rated current 0.3A to 63A. 1. Hold for a minimum of 100ms at surge of 10 times rated current. 2. Trip in under 100ms at 16 times rated current. NB: Trip curves shown comply with North American standards. For trip curves according to European standards please consult Altech. Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com 13 Mouser Electronics Authorized Distributor Click to View Pricing, Inventory, Delivery & Lifecycle Information: Altech: 1DU1.6 2DU1.6 1DR5 1DR3 1DR4 1DR8 1DR2 1DR6 1DR1 2DR3 2DR8 2DR6 2DR1 2DU2 2DU4 2DU8 2DU3 2DU6 2DU1 2DU5 1DR1.6 1DR3.5 4DNU50 4DNU20 2DN63 2DNU6 2DNU3 2DNU5 2DNU8 2DNU2 2DNU4 2DNU1 1DU2.5 2DU2.5 2DR05 2DR16 2DR15 2DR50 2DR30 2DU075 1DU075 2DU15 2DU10 2DU16 2DU13 2DU50 2DU63 2DU03 2DU25 2DU32 2DU30 2DU60 2DU20 2DU40 2DU05 2DU3.5 1DU3.5 3DU10 3DU13 3DU15 3DU16 3DU2 3DU20 3DU25 3DU3 3DU30 3DU32 3DU4 3DU40 3DU5 3DU50 3DU6 3DU60 3DU8 3DU05 3DU075 3DU1.6 2DR075 3DR10 3DR20 3DR30 3DR40 1DU5 1DU1 1DU3 1DU6 1DU2 1DU4 1DU8 4DU32 4DU30 4DU35 4DU20 4DU25 2DNU25 2DNU60 2DNU63 2DNU20 2DNU40 2DNU03