ALTECH 3DU5

D-TRIP
CHARACTERISTICS
ONE POLE
ONE POLE PLUS NEUTRAL
1D
2DN
Application Examples:
High inrush motors, transformers,
power supplies, heaters and reactive
loads. Relatively long thermal trip
delay and very high magnetic trip
point.
Prototype testing is recommended in
motor applications where the relatively
long thermal trip delay may not
provide adequate motor overload
protection. Motor-integral overload
protectors are recommended, with the
V-EA-D providing disconnect, backup
thermal protection and additional short
circuit and energy let-through
protection.
Type Designation
2
D
N
U
—
—
—
—
(a) (b) (c) (d)
60
—
(e)
(a) = Number of Poles
(b) = Trip Characteristic
(c) = Blank: without neutral pole
= N:
with neutral pole
(d) = U:
UL/CSA version
= R:
ring tongue terminals,
UL/CSA version
= Blank: European version
(e) = Rated Current
Approvals:
UL508 Listed
Rated
Current
0.3A
0.5A
0.75A
0.8A❶
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A❶
12.5A
13A
15A❶
16A
20A
25A
30A❶
32A
40A
50A
60A❶
63A
Type/
Cat. No.
Approvals
1DU03
1DU05
1DU075
NA
1DU1
1DU1.6
1DU2
1DU2.5
1DU3
1DU3.5
1DU4
1DU5
1DU6
1DU8
1DU10
NA
NA
1DU13
1DU15
1DU16
1DU20
1DU25
1DU30
1DU32
1DU40
1DU50
1DU60
1DU63
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
*
*
*
UL
*
Type/
Cat. No.
2DNU03
2DNU05
2DNU075
NA
2DNU1
2DNU1.6
2DNU2
2DNU2.5
2DNU3
2DNU3.5
2DNU4
2DNU5
2DNU6
2DNU8
2DNU10
NA
NA
2DNU13
2DNU15
2DNU16
2DNU20
2DNU25
2DNU30
2DNU32
2DNU40
2DNU50
2DNU60
2DNU63
Approvals
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
*
*
*
UL
*
Voltage Rating❸
277VAC
277VAC
Interrupting Capacity
(UL/CSA - Ratings)
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
Group Short Circuit
(UL/CSA - Ratings)
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
Interrupting Capacity (VDE - Ratings)
0.3-63A (RC): 10kA
0.3-63A (RC): 10kA
Mechanical Endurance
10000 ON/OFF operations❷
10000 ON/OFF operations❷
Calibration Temperature
40°C (104°F)
40°C (104°F)
Standard Pack and Weight
10/0.3A - 32A = 1.4kg (3.1 lb.)
40A - 63A = 1.6kg (3.5 lb.)
5/0.3A - 32A = 1.3kg (2.9 lb.)
40A - 63A = 1.45kg (3.2 lb.)
Terminal Size Acceptability
Top: 18-3 AWG; Bottom: 18-2 AWG
Top: 18-3 AWG; Bottom: 18-2 AWG
Terminal Torque
20 lb.in.
20 lb.in.
Basic Dimensions (Elevation View)
❶ Not European standard rating.
❷ Please refer to page 21 for specific
applications.
❸ DC rating (Manufacturer’s self certification):
One pole 48VDC, two pole series 125VDC
* VDE pending
91.5 mm
(3.60 in.)
17.5 mm (0.69 in.)
91.5 mm
(3.60 in.)
35 mm (1.38 in.)
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
12
TWO POLE
THREE POLE
Basic Dimensions (side view)
35 mm
(1.38 in.)
2D
Rated
Current
Type/
Cat. No.
3D
Type/
Cat. No.
Approvals
70mm (2.76 in.)
Approvals
V-EA-D Trip
0.3A Through 10A Rated Current
1.13-1.45xIN
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
*
*
*
UL
*
Minutes
UL
UL
UL
UL
UL
UL
10
4
1
0.4
UL
10-1
UL
4x10-2
UL
UL
UL
10-2
4x10-3
10-3
1
UL
2
3 4 5 6 8 10 16 20
40
100
Multiple of Rated Current
UL
V-EA-D Trip
13A Through 63A Rated Current
UL
UL
1.13-1.45xIN
60
40
UL
UL
UL
UL
UL
*
*
*
10
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
4
1
UL
*
480Y/277VAC
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
0.3-63A (RC): 10kA
0.3-63A (RC): 10kA
10000 ON/OFF operations❷
10000 ON/OFF operations❷
40°C (104°F)
40°C (104°F)
5/1.4kg (3.1 lb.)
4/1.68kg (3.7 lb.)
Top: 18-3 AWG; Bottom: 18-2 AWG
Top: 18-3 AWG; Bottom: 18-2 AWG
20 lb.in.
20 lb.in.
35 mm (1.38 in.)
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
4
UL
480Y/277VAC
91.5 mm
(3.60 in.)
10
1
UL
Tripping time t
UL
Seconds
UL
60
40
UL
Minutes
3DU03
3DU05
3DU075
NA
3DU1
3DU1.6
3DU2
3DU2.5
3DU3
3DU3.5
3DU4
3DU5
3DU6
3DU8
3DU10
NA
NA
3DU13
3DU15
3DU16
3DU20
3DU25
3DU30
3DU32
3DU40
3DU50
3DU60
3DU63
UL
Tripping time t
2DU03
2DU05
2DU075
NA
2DU1
2DU1.6
2DU2
2DU2.5
2DU3
2DU3.5
2DU4
2DU5
2DU6
2DU8
2DU10
NA
NA
2DU13
2DU15
2DU16
2DU20
2DU25
2DU30
2DU32
2DU40
2DU50
2DU60
2DU63
10
4
1
0.4
10-1
4x10-2
Seconds
0.3A
0.5A
0.75A
0.8A❶
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A❶
12.5A
13A
15A❶
16A
20A
25A
30A❶
32A
40A
50A
60A❶
63A
10-2
4x10-3
10-3
1
2
3 4 5 6 8 10 16 20
40
100
Multiple of Rated Current
91.5 mm
(3.60 in.)
52.5 mm (2.07 in.)
“D” Magnetic Trip Parameters
Rated current 0.3A to 63A.
1. Hold for a minimum of 100ms at
surge of 10 times rated current.
2. Trip in under 100ms at 16 times
rated current.
NB: Trip curves shown comply with North
American standards. For trip curves
according to European standards please
consult Altech.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
13
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Altech:
1DU1.6 2DU1.6 1DR5 1DR3 1DR4 1DR8 1DR2 1DR6 1DR1 2DR3 2DR8 2DR6 2DR1 2DU2 2DU4 2DU8
2DU3 2DU6 2DU1 2DU5 1DR1.6 1DR3.5 4DNU50 4DNU20 2DN63 2DNU6 2DNU3 2DNU5 2DNU8 2DNU2
2DNU4 2DNU1 1DU2.5 2DU2.5 2DR05 2DR16 2DR15 2DR50 2DR30 2DU075 1DU075 2DU15 2DU10
2DU16 2DU13 2DU50 2DU63 2DU03 2DU25 2DU32 2DU30 2DU60 2DU20 2DU40 2DU05 2DU3.5 1DU3.5
3DU10 3DU13 3DU15 3DU16 3DU2 3DU20 3DU25 3DU3 3DU30 3DU32 3DU4 3DU40 3DU5 3DU50 3DU6
3DU60 3DU8 3DU05 3DU075 3DU1.6 2DR075 3DR10 3DR20 3DR30 3DR40 1DU5 1DU1 1DU3 1DU6
1DU2 1DU4 1DU8 4DU32 4DU30 4DU35 4DU20 4DU25 2DNU25 2DNU60 2DNU63 2DNU20 2DNU40
2DNU03