V-EA Miniature Circuit Breakers/Manual Motor Controllers
UL listed and CSA certified V-EA
Manual Motor Controllers are horsepower
rated and suitable as Motor Disconnect. They
can also be used for AC General Use, AC
Resistance, AC Discharge Lamps and
AC Incandescent Lamps.
Miniature Circuit Breaker/Manual Motor
Controller Trip Curve Selection Guide . . . .6-7
B-Trip Characteristics . . . . . . . . . . . . . . . . .8-9
C-Trip Characteristics . . . . . . . . . . . . . . .10-11
D-Trip Characteristics . . . . . . . . . . . . . . .12-13
E-Trip Characteristics . . . . . . . . . . . . . . .14-15
G-Trip Characteristics . . . . . . . . . . . . . .16-17
Z-Trip Characteristics . . . . . . . . . . . . . . .18-19
Horsepower Rating Tables . . . . . . . . . . . . .20
V-EA Internal Resistance . . . . . . . . . . . . . .21
Line Current Frequency Effects
on Trip Curve . . . . . . . . . . . . . . . . . . . . . . . .21
Mechanical Endurance Ratings . . . . . . . . .21
Short Circuit Ratings for V-EA
Manual Motor Controllers . . . . . . . . . . . . . .22
Temperature Effects on Trip Curves . . . . . .22
Installation Recommendations . . . . . . . . . .24
V-EA Dimensions . . . . . . . . . . . . . . . . . . . .25
Nonmetallic Enclosure for MCBs . . . . . . . .25
MA Three Phase Adjustable Trip
Miniature Circuit Breakers/Manual Motor Controllers
UL listed MA Three Phase Adjustable
Manual Motor Controllers have an adjustable
thermal trip unit and are especially suitable
for high inrush applications, such as
transformers, motors, etc.
Ordering and Technical Information . . . .26-27
MS Three Phase Adjustable Trip
Economy Manual Motor Controller
UL listed MS Three Phase Adjustable
Manual Motor Controller is an economical
alternative to the MA series. A wide range of
accessories which includes: door mounting kit
and enclosure, emergency stop attachments, etc.
Ordering and Technical Information . . . .28-29
FI Earth Leakage Circuit Breakers
Ordering and Technical Information . . . .30-31
Compact DIN Rail mount FI Earth Leakage
Circuit Breakers detect and interrupt ground
faults. They are VDE approved for the
European system of protecting people, animals,
equipment and property from dangerous line-toground and shock hazard currents.
US applications include ground fault protection
of equipment (GFPE), especially when high
distributed capacitance or other leakages cause
excessive nuisance trips at lower fault currents.
V-EA and MA Miniature Circuit Breaker Accessories
Expand control and monitoring capabilities.
• Shunt Trip
• Undervoltage Trip
• Auxiliary Switch
• Lock-Out
• Cooling Spacer
• Busbar Systems
Accessories . . . . . . . . . . . . . . . . . . . . . .32-33
Busbars . . . . . . . . . . . . . . . . . . . . . . . .34-37
The Altech UL508 Solution . . . . . . . . . .4-5
Standard Terms and Conditions of Sale . . .38
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
3
Competitors
UL1077 Offering
Single Motor Installation
Single Motor Installation
UL489
UL489
Branch circuit
protector/ fuse
Branch circuit
protector/ fuse
NEC Requirement
for Motor Protection
UL508
UL508
Panel
Panel
Disconnecting
means
Motor
controller
Competitor’s
UL1077
Supplementary
Protector
UL Recognized
Overload
Altech’s UL508
Manual Motor Controller
Motor
Altech’s UL Listed Manual Motor Contr ollers
General
Altech’s manual motor controller is UL listed. The UL Listed mark on the
MCB is the manufacturer’s representation that samples of the complete
product have been tested by UL to be used for most common industrial
applications. This superior UL mark allows for field installation without the
need for UL investigation.
A competitor’s UL recognized component mark on the MCB means that
the component alone meets the requirements for a limited, specific use.
These MCBs are not intended for separate installation in the field, they
are intended for use as a component of complete equipment submitted to
UL for investigation.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
4
The
UL508 Solutions
Save money and panel space!
Motor Group Installation
Sizing of main branch circuit protector
• Maximum Circuit Breaker =
largest motor FLA x 250% + FLA of all other motor
and general loads in group
• Maximum Fuses =
largest motor FLA x 175% + FLA of all other motor
and general loads in group
UL489
Branch circuit
protector/ fuse
Altech's
Manual Motor Controllers
are approved for
Group Installations
UL508
Panel
Altech’s UL508 Manual Motor Controller
(shown with a 3 phase, 2 phase and single phase MMC)
&
Field Installations
A licensed electrician can install UL508 Manual Motor
Controllers for the following uses:
• AC Motor Starting (Across the line)
• AC General Use
• AC Resistance
• AC Discharge Lamps (Ballast)
• AC Incandescent Lamps (Tungsten)
General
Load
&
Lamps
Interchangeability
A UL Listed Manual Motor Controller can be used in place
of UL 1077 Recognized supplementary protector, where UL
allowed to use a supplementary protector for a specific
application.
However a UL Recognized supplementary protector cannot
be used in place of UL Listed Manual Motor Controller for a
specific application.
Motor Branch Circuit Uses
(in accordance with NEC ® Section 430)
UL508 Manual Motor Controller
• Disconnect Means/ Disconnect Switch
• Controller and Overload Protection Combination
• Controller and Disconnect Means Combination
UL 1077 supplementary protector
• None
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
5
V-EA MINIATURE CIRCUIT BREAKER/MANUAL MOTOR CONTROLLER
TRIP CURVE SELECTION GUIDE
Warning!
This information should only be used as a selection guide. The use of a Miniature Circuit Breaker/Manual Motor Controller
in an application with a certain Trip-Characteristic always requires prototype testing! It is the responsibility of the circuit
design engineer to select the appropriate Miniature Circuit Breaker/Manual Motor Controller for his specific application.
Trip-Characteristics*
Applications
Characteristic Trip Boundaries
Thermal Trip
Magnetic Trip
Must not
Trip>100ms
Must Trip
<1hr
Must not
Trip>100ms
Lighting
Wiring
Protection
Business
Equipment
Appliances
Control
Circuits
1.45xRC
3xRC
5xRC
Pages
8-9
Pages
8-9
Pages
8-9
Pages
8-9
Pages
8-9
10xRC
Pages
10-11
Pages
10-11
Pages
10-11
Pages
10-11
Pages
10-11
C-Characteristics
1.13xRC
1.45xRC
5xRC
D-Characteristics
1.13xRC
1.45xRC
10xRC
Power
Supplies
Pages
12-13
Pages
12-13
Must Trip
at 100ms
B-Characteristics
1.13xRC
Transformers
16xRC
E-Characteristics
1.05xRC
1.35xRC
14xRC
18xRC
G-Characteristics
1.05xRC
1.35xRC
8xRC
10xRC
Pages
16-17
Pages
16-17
Pages
16-17
Pages
16-17
Z-Characteristics
1.05xRC
1.35xRC
2xRC
3xRC
*The value of each characteristic is shown vertically beneath its corresponding heading.
TIME VERSUS CURRENT TRIP CURVE
Minutes
60
40
10
4
1
10
For the exact trip curve, please refer
to appropriate catalog pages.
Time t
4
1
0.4
Z
B
CG DE
10-1
Seconds
4x10-2
10-2
4x10-3
10-3
2
3 4
6 8 10 16 20
Multiple of Rated Current
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
6
Approvals/Standards:
USA
Canada
Germany
Europe
International
Applications
Heaters
General
Electronics
Motors
General
Low
Inrush
High
Inrush
Solenoid
High
Efficiency
SemiComponents/
conductors devices with
low surgecurrent and
short circuit
withstand
capabilities
Reactive
Load
Pages
8-9
Pages
10-11
Pages
12-13
Pages
12-13
Pages
12-13
Pages
14-15
Pages
16-17
Pages
16-17
Pages
16-17
Pages
18-19
Pages
18-19
Pages
18-19
508 listed
C22.2 No.14 certified
UL file E137938
CSA file LR104391
Manual Motor Controller
“Suitable as Motor Disconnect”
• AC Motor Starting, Across the Line
• AC General Use
• AC Resistance
• AC Discharge Lamps (Ballast)
• AC Incandescent Lamps (Tungsten)
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
7
ONE POLE
B-TRIP
CHARACTERISTICS
ONE POLE PLUS NEUTRAL
Application Examples:
Business
equipment,
wiring
protection, lighting, appliances, control
circuits, some motors and some
electronic applications. Relatively long
thermal trip delay but low magnetic trip
point.
1B
Type Designation
2
—
(a)
B
—
(b)
N
—
(c)
U
—
(d)
60
—
(e)
(a) = Number of Poles
(b) = Trip Characteristic
(c) = Blank: without neutral pole
= N:
with neutral pole
(d) = U:
UL/CSA version
= R:
ring tongue terminals,
UL/CSA version
= Blank: European version
(e) = Rated Current
Approvals:
UL508 Listed
Rated
Current
Type/
Cat. No.
0.3A
0.5A
0.75A
0.8A❶
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A❶
12.5A
13A
15A❶
16A
20A
25A
30A❶
32A
40A
50A
60A❶
63A
NA
NA
NA
NA
1BU1
1BU1.6
1BU2
1BU2.5
1BU3
1BU3.5
1BU4
1BU5
1BU6
NA
1BU10
NA
NA
1BU13
1BU15
1BU16
1BU20
1BU25
1BU30
1BU32
1BU40
1BU50
1BU60
1BU63
2BN
Approvals
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
*
*
*
UL
*
Type/
Cat. No.
NA
NA
NA
NA
2BNU1
2BNU1.6
2BNU2
2BNU2.5
2BNU3
2BNU3.5
2BNU4
2BNU5
2BNU6
NA
2BNU10
NA
NA
2BNU13
2BNU15
2BNU16
2BNU20
2BNU25
2BNU30
2BNU32
2BNU40
2BNU50
2BNU60
2BNU63
Approvals
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
*
*
*
UL
*
Voltage Rating❸
277VAC
277VAC
Interrupting Capacity
(UL/CSA - Ratings)
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
Group Short Circuit
(UL/CSA - Ratings)
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
Interrupting Capacity (VDE - Ratings)
0.3-63A (RC): 10kA
0.3-63A (RC): 10kA
10000 ON/OFF operations❷
10000 ON/OFF operations❷
40°C (104°F)
40°C (104°F)
10/0.3A - 32A = 1.4kg (3.1 lb.)
40A - 63A = 1.6kg (3.5 lb.)
5/0.3A - 32A = 1.3kg (2.9 lb.)
40A - 63A = 1.45kg (3.2 lb.)
Terminal Size Acceptability
Top: 18-3 AWG; Bottom: 18-2 AWG
Top: 18-3 AWG; Bottom: 18-2 AWG
Terminal Torque
20 lb.in.
20 lb.in.
Mechanical Endurance
Calibration Temperature
Standard Pack and Weight
Basic Dimensions (Elevation View)
❶ Not European standard rating.
❷ Please refer to page 21 for specific
applications.
❸ DC rating (Manufacturer’s self certification):
One pole 48VDC, two pole series 125VDC
* VDE pending
91.5 mm
(3.60 in.)
17.5 mm (0.69 in.)
91.5 mm
(3.60 in.)
35 mm (1.38 in.)
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
8
TWO POLE
THREE POLE
Basic Dimensions (side view)
35 mm
(1.38 in.)
3B
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
*
*
*
UL
*
V-EA-B Trip
6.0A Through 10A Rated Current
Minutes
1.13-1.45xIN
60
40
10
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
4
UL
1
UL
UL
UL
Tripping time t
UL
NA
NA
NA
NA
3BU1
3BU1.6
3BU2
3BU2.5
3BU3
3BU3.5
3BU4
3BU5
3BU6
NA
3BU10
NA
NA
3BU13
3BU15
3BU16
3BU20
3BU25
3BU30
3BU32
3BU40
3BU50
3BU60
3BU63
Approvals
UL
UL
UL
10
4
1
0.4
UL
10-1
UL
4x10-2
Seconds
NA
NA
NA
NA
2BU1
2BU1.6
2BU2
2BU2.5
2BU3
2BU3.5
2BU4
2BU5
2BU6
NA
2BU10
NA
NA
2BU13
2BU15
2BU16
2BU20
2BU25
2BU30
2BU32
2BU40
2BU50
2BU60
2BU63
70 mm (2.76 in.)
UL
10-2
4x10-3
10-3
UL
1
2
UL
UL
1.13-1.45xIN
UL
60
40
UL
UL
20
40
100
V-EA-B Trip
13A Through 63A Rated Current
UL
UL
3 4 5 6 8 10
Multiple of Rated Current
UL
*
*
*
Minutes
0.3A
0.5A
0.75A
0.8A❶
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A❶
12.5A
13A
15A❶
16A
20A
25A
30A❶
32A
40A
50A
60A❶
63A
Approvals
Type/
Cat. No.
10
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
4
1
UL
*
480Y/277VAC
480Y/277VAC
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
0.3-63A (RC): 10kA
0.3-63A (RC): 10kA
10000 ON/OFF operations❷
10000 ON/OFF operations❷
40°C (104°F)
40°C (104°F)
5/1.4kg (3.1 lb.)
4/1.68kg (3.7 lb.)
Top: 18-3 AWG; Bottom: 18-2 AWG
Top: 18-3 AWG; Bottom: 18-2 AWG
20 lb.in.
20 lb.in.
Tripping time t
Type/
Cat. No.
10
4
1
0.4
10-1
4x10-2
Seconds
2B
Rated
Current
10-2
4x10-3
10-3
1
2
3 4 5 6 8 10
20
40
100
Multiple of Rated Current
“B” Magnetic Trip Parameters
Rated current 0.3A to 63A.
1. Hold for a minimum of 100ms at surge
of 3 times rated current.
2. Trip in under 100ms at 5 times rated
current.
91.5 mm
(3.60 in.)
35 mm (1.38 in.)
91.5 mm
(3.60 in.)
NB: Trip curves shown comply with North
American standards. For trip curves
according to European standards please
consult Altech.
52.5 mm (2.07 in.)
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
9
C-TRIP
CHARACTERISTICS
ONE POLE
ONE POLE PLUS NEUTRAL
1C
2CN
Application Examples:
Low inrush motors, lighting, wiring
protection, appliances, business
equipment, and control circuit
applications. Relatively long thermal
trip delay and medium magnetic trip
point.
Type Designation
2
—
(a)
C
—
(b)
N
—
(c)
U
—
(d)
60
—
(e)
(a) = Number of Poles
(b) = Trip Characteristic
(c) = Blank: without neutral pole
= N:
with neutral pole
(d) = U:
UL/CSA version
= R:
ring tongue terminals,
UL/CSA version
= Blank: European version
(e) = Rated Current
Approvals:
UL508 Listed
Rated
Current
Type/
Cat. No.
0.3A
0.5A
0.75A
0.8A❶
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A❶
12.5A
13A
15A❶
16A
20A
25A
30A❶
32A
40A
50A
60A❶
63A
1CU03
1CU05
1CU075
NA
1CU1
1CU1.6
1CU2
1CU2.5
1CU3
1CU3.5
1CU4
1CU5
1CU6
1CU8
1CU10
NA
NA
1CU13
1CU15
1CU16
1CU20
1CU25
1CU30
1CU32
1CU40
1CU50
1CU60
1CU63
Approvals
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
*
*
*
UL
*
Type/
Cat. No.
2CNU03
2CNU05
2CNU075
NA
2CNU1
2CNU1.6
2CNU2
2CNU2.5
2CNU3
2CNU3.5
2CNU4
2CNU5
2CNU6
2CNU8
2CNU10
NA
NA
2CNU13
2CNU15
2CNU16
2CNU20
2CNU25
2CNU30
2CNU32
2CNU40
2CNU50
2CNU60
2CNU63
Approvals
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
*
*
*
UL
*
Voltage Rating❸
277VAC
277VAC
Interrupting Capacity
(UL/CSA - Ratings)
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
Group Short Circuit
(UL/CSA - Ratings)
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
Interrupting Capacity (VDE - Ratings)
0.3-63A (RC): 10kA
0.3-63A (RC): 10kA
Mechanical Endurance
10000 ON/OFF operations❷
10000 ON/OFF operations❷
Calibration Temperature
40°C (104°F)
40°C (104°F)
Standard Pack and Weight
10/0.3A - 32A = 1.4kg (3.1 lb.)
40A - 63A = 1.6kg (3.5 lb.)
5/0.3A - 32A = 1.3kg (2.9 lb.)
40A - 63A = 1.45kg (3.2 lb.)
Terminal Size Acceptability
Top: 18-3 AWG; Bottom: 18-2 AWG
Top: 18-3 AWG; Bottom: 18-2 AWG
Terminal Torque
20 lb.in.
20 lb.in.
Basic Dimensions (Elevation View)
❶ Not European standard rating.
❷ Please refer to page 21 for specific
applications.
❸ DC rating (Manufacturer’s self certification):
One pole 48VDC, two pole series 125VDC
* VDE pending
91.5 mm
(3.60 in.)
17.5 mm (0.69 in.)
91.5 mm
(3.60 in.)
35 mm (1.38 in.)
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
10
TWO POLE
THREE POLE
Basic Dimensions (side view)
35 mm
(1.38 in.)
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
*
*
*
UL
*
60
40
UL
UL
UL
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
4
1
UL
UL
UL
UL
UL
UL
10
4
1
0.4
10-1
UL
4x10-2
UL
UL
UL
10-2
4x10-3
10-3
1
2
3 4 5 6 8 10
20
40
100
Multiple of Rated Current
UL
UL
V-EA-C Trip
13A Through 63A Rated Current
UL
UL
1.13-1.45xIN
60
40
UL
UL
UL
UL
UL
*
*
*
10
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
4
1
UL
*
480Y/277VAC
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
0.3-63A (RC): 10kA
0.3-63A (RC): 10kA
10000 ON/OFF operations❷
10000 ON/OFF operations❷
40°C (104°F)
40°C (104°F)
5/1.4kg (3.1 lb.)
4/1.68kg (3.7 lb.)
Top: 18-3 AWG; Bottom: 18-2 AWG
Top: 18-3 AWG; Bottom: 18-2 AWG
20 lb.in.
20 lb.in.
35 mm (1.38 in.)
10
UL
480Y/277VAC
91.5 mm
(3.60 in.)
1.13-1.45xIN
Minutes
3CU03
3CU05
3CU075
NA
3CU1
3CU1.6
3CU2
3CU2.5
3CU3
3CU3.5
3CU4
3CU5
3CU6
3CU8
3CU10
NA
NA
3CU13
3CU15
3CU16
3CU20
3CU25
3CU30
3CU32
3CU40
3CU50
3CU60
3CU63
UL
V-EA-C Trip
0.3A Through 10A Rated Current
Tripping time t
2CU03
2CU05
2CU075
NA
2CU1
2CU1.6
2CU2
2CU2.5
2CU3
2CU3.5
2CU4
2CU5
2CU6
2CU8
2CU10
NA
NA
2CU13
2CU15
2CU16
2CU20
2CU25
2CU30
2CU32
2CU40
2CU50
2CU60
2CU63
Approvals
Seconds
Type/
Cat. No.
Approvals
Minutes
0.3A
0.5A
0.75A
0.8A❶
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A❶
12.5A
13A
15A❶
16A
20A
25A
30A❶
32A
40A
50A
60A❶
63A
Type/
Cat. No.
70 mm (2.76 in.)
Tripping time t
Rated
Current
3C
10
4
1
0.4
10-1
4x10-2
Seconds
2C
10-2
4x10-3
10-3
1
2
3 4 5 6 8 10
20
40
100
Multiple of Rated Current
“C” Magnetic Trip Parameters
Rated current 0.3A to 63A.
1. Hold for a minimum of 100ms at
surge of 5 times rated current.
91.5 mm
(3.60 in.)
52.5 mm (2.07 in.)
2. Trip in under 100ms at 10 times rated
current.
NB: Trip curves shown comply with North
American standards. For trip curves
according to European standards please
consult Altech.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
11
D-TRIP
CHARACTERISTICS
ONE POLE
ONE POLE PLUS NEUTRAL
1D
2DN
Application Examples:
High inrush motors, transformers,
power supplies, heaters and reactive
loads. Relatively long thermal trip
delay and very high magnetic trip
point.
Prototype testing is recommended in
motor applications where the relatively
long thermal trip delay may not
provide adequate motor overload
protection. Motor-integral overload
protectors are recommended, with the
V-EA-D providing disconnect, backup
thermal protection and additional short
circuit and energy let-through
protection.
Type Designation
2
D
N
U
—
—
—
—
(a) (b) (c) (d)
60
—
(e)
(a) = Number of Poles
(b) = Trip Characteristic
(c) = Blank: without neutral pole
= N:
with neutral pole
(d) = U:
UL/CSA version
= R:
ring tongue terminals,
UL/CSA version
= Blank: European version
(e) = Rated Current
Approvals:
UL508 Listed
Rated
Current
0.3A
0.5A
0.75A
0.8A❶
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A❶
12.5A
13A
15A❶
16A
20A
25A
30A❶
32A
40A
50A
60A❶
63A
Type/
Cat. No.
Approvals
1DU03
1DU05
1DU075
NA
1DU1
1DU1.6
1DU2
1DU2.5
1DU3
1DU3.5
1DU4
1DU5
1DU6
1DU8
1DU10
NA
NA
1DU13
1DU15
1DU16
1DU20
1DU25
1DU30
1DU32
1DU40
1DU50
1DU60
1DU63
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
*
*
*
UL
*
Type/
Cat. No.
2DNU03
2DNU05
2DNU075
NA
2DNU1
2DNU1.6
2DNU2
2DNU2.5
2DNU3
2DNU3.5
2DNU4
2DNU5
2DNU6
2DNU8
2DNU10
NA
NA
2DNU13
2DNU15
2DNU16
2DNU20
2DNU25
2DNU30
2DNU32
2DNU40
2DNU50
2DNU60
2DNU63
Approvals
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
*
*
*
UL
*
Voltage Rating❸
277VAC
277VAC
Interrupting Capacity
(UL/CSA - Ratings)
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
Group Short Circuit
(UL/CSA - Ratings)
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
Interrupting Capacity (VDE - Ratings)
0.3-63A (RC): 10kA
0.3-63A (RC): 10kA
Mechanical Endurance
10000 ON/OFF operations❷
10000 ON/OFF operations❷
Calibration Temperature
40°C (104°F)
40°C (104°F)
Standard Pack and Weight
10/0.3A - 32A = 1.4kg (3.1 lb.)
40A - 63A = 1.6kg (3.5 lb.)
5/0.3A - 32A = 1.3kg (2.9 lb.)
40A - 63A = 1.45kg (3.2 lb.)
Terminal Size Acceptability
Top: 18-3 AWG; Bottom: 18-2 AWG
Top: 18-3 AWG; Bottom: 18-2 AWG
Terminal Torque
20 lb.in.
20 lb.in.
Basic Dimensions (Elevation View)
❶ Not European standard rating.
❷ Please refer to page 21 for specific
applications.
❸ DC rating (Manufacturer’s self certification):
One pole 48VDC, two pole series 125VDC
* VDE pending
91.5 mm
(3.60 in.)
17.5 mm (0.69 in.)
91.5 mm
(3.60 in.)
35 mm (1.38 in.)
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
12
TWO POLE
THREE POLE
Basic Dimensions (side view)
35 mm
(1.38 in.)
2D
Rated
Current
Type/
Cat. No.
3D
Type/
Cat. No.
Approvals
70mm (2.76 in.)
Approvals
V-EA-D Trip
0.3A Through 10A Rated Current
1.13-1.45xIN
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
*
*
*
UL
*
Minutes
UL
UL
UL
UL
UL
UL
10
4
1
0.4
UL
10-1
UL
4x10-2
UL
UL
UL
10-2
4x10-3
10-3
1
UL
2
3 4 5 6 8 10 16 20
40
100
Multiple of Rated Current
UL
V-EA-D Trip
13A Through 63A Rated Current
UL
UL
1.13-1.45xIN
60
40
UL
UL
UL
UL
UL
*
*
*
10
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
4
1
UL
*
480Y/277VAC
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
0.3-63A (RC): 10kA
0.3-63A (RC): 10kA
10000 ON/OFF operations❷
10000 ON/OFF operations❷
40°C (104°F)
40°C (104°F)
5/1.4kg (3.1 lb.)
4/1.68kg (3.7 lb.)
Top: 18-3 AWG; Bottom: 18-2 AWG
Top: 18-3 AWG; Bottom: 18-2 AWG
20 lb.in.
20 lb.in.
35 mm (1.38 in.)
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
4
UL
480Y/277VAC
91.5 mm
(3.60 in.)
10
1
UL
Tripping time t
UL
Seconds
UL
60
40
UL
Minutes
3DU03
3DU05
3DU075
NA
3DU1
3DU1.6
3DU2
3DU2.5
3DU3
3DU3.5
3DU4
3DU5
3DU6
3DU8
3DU10
NA
NA
3DU13
3DU15
3DU16
3DU20
3DU25
3DU30
3DU32
3DU40
3DU50
3DU60
3DU63
UL
Tripping time t
2DU03
2DU05
2DU075
NA
2DU1
2DU1.6
2DU2
2DU2.5
2DU3
2DU3.5
2DU4
2DU5
2DU6
2DU8
2DU10
NA
NA
2DU13
2DU15
2DU16
2DU20
2DU25
2DU30
2DU32
2DU40
2DU50
2DU60
2DU63
10
4
1
0.4
10-1
4x10-2
Seconds
0.3A
0.5A
0.75A
0.8A❶
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A❶
12.5A
13A
15A❶
16A
20A
25A
30A❶
32A
40A
50A
60A❶
63A
10-2
4x10-3
10-3
1
2
3 4 5 6 8 10 16 20
40
100
Multiple of Rated Current
91.5 mm
(3.60 in.)
52.5 mm (2.07 in.)
“D” Magnetic Trip Parameters
Rated current 0.3A to 63A.
1. Hold for a minimum of 100ms at
surge of 10 times rated current.
2. Trip in under 100ms at 16 times
rated current.
NB: Trip curves shown comply with North
American standards. For trip curves
according to European standards please
consult Altech.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
13
E-TRIP
CHARACTERISTICS
ONE POLE
ONE POLE PLUS NEUTRAL
1E
2EN
Application Examples:
High efficiency motors, which have
exceedingly high inrush currents.
Relatively short thermal trip delays
and very high magnetic trip points.
Prototype testing is recommended.
The V-EA-E is the result of continuous
research and improvement of our Gand D-Trip circuit breakers. It
combines the short thermal trip delay
of the G-Trip and an even higher
magnetic trip point than the D-Trip.
Therefore, the V-EA-E provides
adequate motor overload and short
circuit protection.
Type Designation
2
—
(a)
E
—
(b)
N
—
(c)
U
—
(d)
60
—
(e)
(a) = Number of Poles
(b) = Trip Characteristic
(c) = Blank: without neutral pole
= N:
with neutral pole
(d) = U:
UL/CSA version
= R:
ring tongue terminals,
UL/CSA version
= Blank: European version
(e) = Rated Current
Approvals:
UL508 Listed
Rated
Current
Type/
Cat. No.
0.3A
0.5A
0.75A
0.8A❶
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A❶
12.5A
13A
15A❶
16A
20A
25A
30A❶
32A
40A
50A
60A❶
63A
1EU03
1EU05
1EU075
NA
1EU1
1EU1.6
1EU2
1EU2.5
1EU3
1EU3.5
1EU4
1EU5
1EU6
1EU8
1EU10
1EU12
1EU125
1EU13
1EU15
1EU16
1EU20
1EU25
1EU30
1EU32
1EU40
1EU50
1EU60
1EU63
Approvals
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
Type/
Cat. No.
2ENU03
2ENU05
2ENU075
NA
2ENU1
2ENU1.6
2ENU2
2ENU2.5
2ENU3
2ENU3.5
2ENU4
2ENU5
2ENU6
2ENU8
2ENU10
2ENU12
2ENU125
2ENU13
2ENU15
2ENU16
2ENU20
2ENU25
2ENU30
2ENU32
2ENU40
2ENU50
2ENU60
2ENU63
Approvals
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
Voltage Rating❸
277VAC
277VAC
Interrupting Capacity
(UL/CSA - Ratings)
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
Group Short Circuit
(UL/CSA - Ratings)
0.3-10A (RC): 10kA; 12-60A (RC): 5kA
no branch circuit protection required
0.3-10A (RC): 10kA; 12-60A (RC): 5kA
no branch circuit protection required
Interrupting Capacity (VDE - Ratings)
0.3-63A (RC): 10kA
0.3-63A (RC): 10kA
Mechanical Endurance
10000 ON/OFF operations❷
10000 ON/OFF operations❷
Calibration Temperature
40°C (104°F)
40°C (104°F)
Standard Pack and Weight
10/0.3A - 32A = 1.4kg (3.1 lb.)
40A - 63A = 1.6kg (3.5 lb.)
5/0.3A - 32A = 1.3kg (2.9 lb.)
40A - 63A = 1.45kg (3.2 lb.)
Terminal Size Acceptability
Top: 18-3 AWG; Bottom: 18-2 AWG
Top: 18-3 AWG; Bottom: 18-2 AWG
Terminal Torque
20 lb.in.
20 lb.in.
Basic Dimensions (Elevation View)
❶ Not European standard rating.
❷ Please refer to page 21 for specific
91.5 mm
(3.60 in.)
91.5 mm
(3.60 in.)
applications.
❸ DC rating (Manufacturer’s self certification):
One pole 48VDC, two pole series 125VDC
17.5 mm (0.69 in.)
35 mm (1.38 in.)
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
14
TWO POLE
THREE POLE
Basic Dimensions (side view)
35 mm
(1.38 in.)
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
4
1
UL
UL
UL
UL
10
4
1
0.4
UL
10-1
UL
4x10-2
UL
UL
UL
UL
10-2
4x10-3
10-3
UL
1
UL
UL
40
100
1.05-1.35xIN
60
40
UL
UL
3 4 5 6 8 10 1418 20
V-EA-E Trip
12A Through 60A Rated Current
UL
UL
2
Multiple of Rated Current
E0.3A-E10A
UL
10
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
4
UL
1
UL
UL
UL
480Y/277VAC
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-10A (RC): 10kA; 12-60A (RC): 5kA
no branch circuit protection required
0.3-10A (RC): 10kA; 12-60A (RC): 5kA
no branch circuit protection required
0.3-63A (RC): 10kA
0.3-63A (RC): 10kA
10000 ON/OFF operations❷
10000 ON/OFF operations❷
40°C (104°F)
40°C (104°F)
5/1.4kg (3.1 lb.)
4/1.68kg (3.7 lb.)
Top: 18-3 AWG; Bottom: 18-2 AWG
Top: 18-3 AWG; Bottom: 18-2 AWG
20 lb.in.
20 lb.in.
35 mm (1.38 in.)
10
UL
480Y/277VAC
91.5 mm
(3.60 in.)
Minutes
3EU03
3EU05
3EU075
NA
3EU1
3EU1.6
3EU2
3EU2.5
3EU3
3EU3.5
3EU4
3EU5
3EU6
3EU8
3EU10
3EU12
3EU125
3EU13
3EU15
3EU16
3EU20
3EU25
3EU30
3EU32
3EU40
3EU50
3EU60
3EU63
UL
1.05-1.35xIN
60
40
Tripping time t
2EU03
2EU05
2EU075
NA
2EU1
2EU1.6
2EU2
2EU2.5
2EU3
2EU3.5
2EU4
2EU5
2EU6
2EU8
2EU10
2EU12
2EU125
2EU13
2EU15
2EU16
2EU20
2EU25
2EU30
2EU32
2EU40
2EU50
2EU60
2EU63
Approvals
Seconds
0.3A
0.5A
0.75A
0.8A❶
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A❶
12.5A
13A
15A❶
16A
20A
25A
30A❶
32A
40A
50A
60A❶
63A
Type/
Cat. No.
Approvals
Minutes
Type/
Cat. No.
70mm (2.76 in.)
V-EA-E Trip
0.3A Through 10A Rated Current
10
Tripping time t
Rated
Current
3E
4
1
0.4
10-1
4x10-2
Seconds
2E
10-2
4x10-3
10-3
1
2
3
4 5 6
8 10 14 18 20
40
“E” Magnetic Trip Parameters
Rated Current, 0.3A to 50A (
60/63A (- - - - -).
91.5 mm
(3.60 in.)
100
Multiple of Rated Current
),
Magnetic Trip:
1. Hold for a minimum of 100ms at
surge of 14 times (60A, 10 times)
rated current.
2. Trip in under 100ms at 18 times
(60A, 14 times) rated current.
NB: Trip curves shown comply with North
American standards. For trip curves
according to European standards please
consult Altech.
52.5 mm (2.07 in.)
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
15
G-TRIP
CHARACTERISTICS
ONE POLE
ONE POLE PLUS NEUTRAL
1G
2GN
Application Examples:
General industrial, including motors,
some transformers, solenoids, control
circuits, lighting and wiring. Meets the
US trip norms with relatively short
thermal trip delay and high magnetic
trip point.
Type Designation
2
—
(a)
G
—
(b)
N
—
(c)
U
—
(d)
60
—
(e)
(a) = Number of Poles
(b) = Trip Characteristic
(c) = Blank: without neutral pole
= N:
with neutral pole
(d) = U:
UL/CSA version
= R:
ring tongue terminals,
UL/CSA version
= Blank: European version
(e) = Rated Current
Approvals:
UL508 Listed
Rated
Current
Type/
Cat. No.
0.3A
0.5A
0.75A
0.8A❶
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A❶
12.5A
13A
15A❶
16A
20A
25A
30A❶
32A
40A
50A
60A❶
63A
1GU03
1GU05
NA
1GU08
1GU1
1GU1.6
1GU2
1GU2.5
1GU3
1GU3.5
1GU4
1GU5
1GU6
1GU8
1GU10
1GU12
1GU125
1GU13
1GU15
1GU16
1GU20
1GU25
1GU30
1GU32
1GU40
1GU50
1GU60
1GU63
Approvals
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
Type/
Cat. No.
2GNU03
2GNU05
NA
2GNU08
2GNU1
2GNU1.6
2GNU2
2GNU2.5
2GNU3
2GNU3.5
2GNU4
2GNU5
2GNU6
2GNU8
2GNU10
2GNU12
2GNU125
2GNU13
2GNU15
2GNU16
2GNU20
2GNU25
2GNU30
2GNU32
2GNU40
2GNU50
2GNU60
2GNU63
Approvals
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
Voltage Rating❸
277VAC
277VAC
Interrupting Capacity
(UL/CSA - Ratings)
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
Group Short Circuit
(UL/CSA - Ratings)
0.3-10A (RC): 10kA; 12-60A (RC): 5kA
no branch circuit protection required
0.3-10A (RC): 10kA; 12-60A (RC): 5kA
no branch circuit protection required
Interrupting Capacity (VDE - Ratings)
0.3-63A (RC): 10kA
0.3-63A (RC): 10kA
Mechanical Endurance
10000 ON/OFF operations❷
10000 ON/OFF operations❷
Calibration Temperature
40°C (104°F)
40°C (104°F)
Standard Pack and Weight
10/0.3A - 32A = 1.4kg (3.1 lb.)
40A - 63A = 1.6kg (3.5 lb.)
5/0.3A - 32A = 1.3kg (2.9 lb.)
40A - 63A = 1.45kg (3.2 lb.)
Terminal Size Acceptability
Top: 18-3 AWG; Bottom: 18-2 AWG
Top: 18-3 AWG; Bottom: 18-2 AWG
Terminal Torque
20 lb.in.
20 lb.in.
Basic Dimensions (Elevation View)
❶ Not European standard rating.
❷ Please refer to page 21 for specific
applications.
❸ DC rating (Manufacturer’s self certification):
91.5 mm
(3.60 in.)
91.5 mm
(3.60 in.)
One pole 48VDC, two pole series 125VDC
*
AC Motor Starting, Across-the-line approval
pending
17.5 mm (0.69 in.)
35 mm (1.38 in.)
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
16
TWO POLE
THREE POLE
Basic Dimensions (side view)
35 mm
(1.38 in.)
3GU03
3GU05
NA
3GU08
3GU1
3GU1.6
3GU2
3GU2.5
3GU3
3GU3.5
3GU4
3GU5
3GU6
3GU8
3GU10
3GU12
3GU125
3GU13
3GU15
3GU16
3GU20
3GU25
3GU30
3GU32
3GU40
3GU50
3GU60
3GU63
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
480Y/277VAC
*
*
*
*
*
*
*
*
*
*
*
*
1.05-1.35xIN
60
40
UL
UL
10
Thermal Overload
“Must Trip” = 125% Rated Current
“Must Not Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
“Must Not Trip” = Rated Current
4
UL
1
UL
UL
10
UL
UL
UL
UL
4
1
0.4
UL
10-1
UL
4x10-2
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
*
*
*
*
*
*
*
*
*
*
*
*
480Y/277VAC
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
V-EA-G Trip
0.3A Through 10A Rated Current
Minutes
2GU03
2GU05
NA
2GU08
2GU1
2GU1.6
2GU2
2GU2.5
2GU3
2GU3.5
2GU4
2GU5
2GU6
2GU8
2GU10
2GU12
2GU125
2GU13
2GU15
2GU16
2GU20
2GU25
2GU30
2GU32
2GU40
2GU50
2GU60
2GU63
Approvals
Tripping time t
0.3A
0.5A
0.75A
0.8A❶
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A❶
12.5A
13A
15A❶
16A
20A
25A
30A❶
32A
40A
50A
60A❶
63A
Type/
Cat. No.
Approvals
Seconds
Type/
Cat. No.
70mm (2.76 in.)
10-2
4x10-3
10-3
1
2
3 4 5 6 8 10
20
40
V-EA-G Trip
12A Through 63A Rated Current
1.05-1.35xIN
60
40
10
Thermal Overload
“Must Trip” = 125% Rated Current
“Must Not Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
“Must Not Trip” = Rated Current
4
1
10
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
4
1
0.4
10-1
4x10-2
0.3-10A (RC): 10kA; 12-60A (RC): 5kA
no branch circuit protection required
0.3-63A (RC): 10kA
0.3-63A (RC): 10kA
10000 ON/OFF operations❷
10000 ON/OFF operations❷
40°C (104°F)
40°C (104°F)
5/1.4kg (3.1 lb.)
4/1.68kg (3.7 lb.)
“G” Magnetic Trip Parameters
Rated Current, 0.3A to 63A.
Top: 18-3 AWG; Bottom: 18-2 AWG
Top: 18-3 AWG; Bottom: 18-2 AWG
20 lb.in.
20 lb.in.
Magnetic Trip:
1. Hold for a minimum of 100ms at
surge of 8 times rated current.
2. Trip in under 100ms at 10 times
rated current.
35 mm (1.38 in.)
Seconds
0.3-10A (RC): 10kA; 12-60A (RC): 5kA
no branch circuit protection required
91.5 mm
(3.60 in.)
100
Multiple of Rated Current
Minutes
Rated
Current
3G
Tripping time t
2G
10-2
4x10-3
10-3
1
2
3 4 5 6 8 10
20
40
100
Multiple of Rated Current
91.5 mm
(3.60 in.)
NB: Trip curves shown comply with North
American standards. For trip curves
according to European standards please
consult Altech.
52.5 mm (2.07 in.)
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
17
Z-TRIP
CHARACTERISTICS
ONE POLE
ONE POLE PLUS NEUTRAL
1Z
2ZN
Application Examples:
Semiconductors, components which
fail-short
(vs. fail-open),
and
components/devices with low surgecurrent and short circuit withstand
capabilities. Relatively short thermal
delay and very low magnetic trip point.
Type Designation
2
—
(a)
Z
—
(b)
N
—
(c)
U
—
(d)
30
—
(e)
(a) = Number of Poles
(b) = Trip Characteristic
(c) = Blank: without neutral pole
= N:
with neutral pole
(d) = U:
UL/CSA version
= R:
ring tongue terminals,
UL/CSA version
= Blank: European version
(e) = Rated Current
Approvals:
UL508 Listed
Rated
Current
Type/
Cat. No.
0.3A
0.5A
0.75A
0.8A❶
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A❶
12.5A
13A
15A❶
16A
20A
25A
30A❶
32A
40A
50A
60A❶
63A
1ZU03
1ZU05
1ZU075
NA
1ZU1
1ZU1.6
1ZU2
1ZU2.5
1ZU3
1ZU3.5
1ZU4
1ZU5
1ZU6
1ZU8
1ZU10
1ZU12
1ZU125
1ZU13
1ZU15
1ZU16
1ZU20
1ZU25
1ZU30
1ZU32
1ZU40
1ZU50
NA
NA
Approvals
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
*
*
Type/
Cat. No.
2ZNU03
2ZNU05
2ZNU075
NA
2ZNU1
2ZNU1.6
2ZNU2
2ZNU2.5
2ZNU3
2ZNU3.5
2ZNU4
2ZNU5
2ZNU6
2ZNU8
2ZNU10
2ZNU12
2ZNU125
2ZNU13
2ZNU15
2ZNU16
2ZNU20
2ZNU25
2ZNU30
2ZNU32
2ZNU40
2ZNU50
NA
NA
Approvals
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
*
*
Voltage Rating❸
277VAC
277VAC
Interrupting Capacity
(UL/CSA - Ratings)
0.3-32A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-32A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
Group Short Circuit
(UL/CSA - Ratings)
0.3-10A (RC): 10kA; 12-32A (RC): 5kA
no branch circuit protection required
0.3-10A (RC): 10kA; 12-32A (RC): 5kA
no branch circuit protection required
Interrupting Capacity (VDE - Ratings)
0.3-32A (RC): 10kA
0.3-32A (RC): 10kA
Mechanical Endurance
10000 ON/OFF operations❷
10000 ON/OFF operations❷
Calibration Temperature
40°C (104°F)
40°C (104°F)
Standard Pack and Weight
10/0.3A - 32A = 1.4kg (3.1 lb.)
40A - 63A = 1.6kg (3.5 lb.)
5/0.3A - 32A = 1.3kg (2.9 lb.)
40A - 63A = 1.45kg (3.2 lb.)
Terminal Size Acceptability
Top: 18-3 AWG; Bottom: 18-2 AWG
Top: 18-3 AWG; Bottom: 18-2 AWG
Terminal Torque
20 lb.in.
20 lb.in.
Basic Dimensions (Elevation View)
❶ Not European standard rating.
❷ Please refer to page 21 for specific
applications.
❸ DC rating (Manufacturer’s self certification):
One pole 48VDC, two pole series 125VDC
* UL and CSA Pending
91.5 mm
(3.60 in.)
17.5 mm (0.69 in.)
91.5 mm
(3.60 in.)
35 mm (1.38 in.)
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
18
TWO POLE
THREE POLE
Basic Dimensions (side view)
35 mm
(1.38 in.)
3ZU03
3ZU05
3ZU075
NA
3ZU1
3ZU1.6
3ZU2
3ZU2.5
3ZU3
3ZU3.5
3ZU4
3ZU5
3ZU6
3ZU8
3ZU10
3ZU12
3ZU125
3ZU13
3ZU15
3ZU16
3ZU20
3ZU25
3ZU30
3ZU32
3ZU40
3ZU50
NA
NA
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
*
*
1.05-1.35xIN
60
40
UL
Minutes
UL
V-EA-Z Trip
0.3A Through 10A Rated Current
UL
UL
UL
UL
Tripping time t
2ZU03
2ZU05
2ZU075
NA
2ZU1
2ZU1.6
2ZU2
2ZU2.5
2ZU3
2ZU3.5
2ZU4
2ZU5
2ZU6
2ZU8
2ZU10
2ZU12
2ZU125
2ZU13
2ZU15
2ZU16
2ZU20
2ZU25
2ZU30
2ZU32
2ZU40
2ZU50
NA
NA
Approvals
UL
UL
UL
UL
UL
10
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
4
1
40
20
10
4
1
0.4
10-1
UL
4x10-2
UL
Seconds
0.3A
0.5A
0.75A
0.8A❶
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A❶
12.5A
13A
15A❶
16A
20A
25A
30A❶
32A
40A
50A
60A❶
63A
Type/
Cat. No.
Approvals
70mm (2.76 in.)
UL
UL
UL
10-2
4x10-3
10-3
UL
1
UL
20
40
60
40
UL
UL
UL
*
*
10
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
4
1
10
4
480Y/277VAC
480Y/277VAC
0.3-32A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-32A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-10A (RC): 10kA; 12-32A (RC): 5kA
no branch circuit protection required
0.3-10A (RC): 10kA; 12-32A (RC): 5kA
no branch circuit protection required
0.3-32A (RC): 10kA
0.3-32A (RC): 10kA
10000 ON/OFF operations❷
10000 ON/OFF operations❷
40°C (104°F)
40°C (104°F)
5/1.4kg (3.1 lb.)
4/1.68kg (3.7 lb.)
Top: 18-3 AWG; Bottom: 18-2 AWG
Top: 18-3 AWG; Bottom: 18-2 AWG
Magnetic Trip:
20 lb.in.
20 lb.in.
1. Hold for a minimum of 100ms at
2 times rated current.
2. Trip in under 100ms at 3 times
rated current.
91.5 mm
(3.60 in.)
35 mm (1.38 in.)
100
1.05-1.35xIN
UL
UL
3 4 5 6 8 10
V-EA-Z Trip
12.5A Through 32A Rated Current
UL
UL
2
Multiple of Rated Current
UL
Minutes
Rated
Type/
Current Cat. No.
3Z
Tripping time t
2Z
1
0.4
10-1
Seconds
4x10-2
10-2
4x10-3
10-3
1
2
3 4 5 6 8 10
20
40
100
Multiple of Rated Current
“Z” Trip Parameters
Rated Current, 0.3A to 32A.
91.5 mm
(3.60 in.)
NB: Trip curves shown comply with North
American standards. For trip curves
according to European standards please
consult Altech.
52.5 mm (2.07 in.)
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
19
Table HP 1: AMPERE RATINGS & HORSEPOWER RATING 1 PHASE
FLA & LRC CONVERTED TO
TABLE HORSEPOWER (SEE NOTE #2)
USE FLA & LRC RATINGS WHERE
NO HP RATING IS GIVEN
NOMINAL CIRCUIT VOLTAGE
V-EA
RATED
MOTOR
NAMEPLATE
MOTOR
NAMEPLATE
CURRENT
(SEE NOTE #1)
FLA
RATING
STARTING/
LRC RATING
0.30A
0.50A
0.75A
0.80A
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10.0A
12.0A
12.5A
13.0A
15.0A
16.0A
20.0A
25.0A
30.0A
32.0A
40.0A
0.30A
0.50A
0.75A
0.80A
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10.0A
12.0A
12.5A
13.0A
15.0A
16.0A
20.0A
25.0A
30.0A
32.0A
40.0A
1.80A
3.00A
4.35A
4.8A
6.0A
9.6A
12.0A
15.0A
18.0A
21.0A
24.0A
30.0A
36.0A
48.0A
60.0A
72.0A
75.0A
78.0A
90.0A
96.0A
120.0A
150.0A
180.0A
192.0A
240.0A
50.0A
60.0A
50.0A
60.0A
300.0A
360.0A
110-120
VAC
200
VAC
208
VAC
1/6hp
1/4hp
1/3hp
1/6hp
1/6hp
1/4hp
1/4hp
1/3hp
1/2hp
3/4hp
1/6hp
1/6hp
1/4hp
1/3hp
1/2hp
1/2hp
3/4hp
1hp
11/2hp
2hp
2hp
2hp
3hp
1hp
11/2hp
11/2hp
11/2hp
2hp
2hp
3hp
3hp
3hp
3hp
5hp
3hp
5hp
71/2hp
10hp
1/2hp
1/2hp
1/2hp
1/2hp
3/4hp
220-240
VAC
265
VAC
277
VAC
1/6hp
1/6hp
1/4hp
1/4hp
1/3hp
1/2hp
1/2hp
1/6hp
1/6hp
1/4hp
1/3hp
1/3hp
1/2hp
3/4hp
1/6hp
1/4hp
1/3hp
1/3hp
1/3hp
1/2hp
3/4hp
1hp
11/2hp
11/2hp
11/2hp
2hp
2hp
3hp
3hp
3hp
5hp
71/2hp
1hp
11/2hp
2hp
2hp
2hp
2hp
2hp
3hp
3hp
5hp
5hp
71/2hp
1hp
11/2hp
2hp
2hp
2hp
3hp
3hp
3hp
5hp
5hp
5hp
71/2hp
1hp
2hp
2hp
2hp
2hp
3hp
3hp
3hp
5hp
5hp
5hp
71/2hp
10hp
10hp
10hp
10hp
10hp
10hp
10hp
15hp
NOTE #1: For AC motor circuit nameplate full load current, AC general-use loads, AC resistance loads, AC incandescent lamp (tungsten) loads,
AC electric discharge lamp (ballast) loads.
NOTE #2: Conversions per UL508® Table 45.2 and NFPA-70: National Electrical Code® 1999 Tables 430-148 and 430-151A.
Table HP 2: AMPERE RATING & HORSEPOWER RATING 3 PHASE & 2 PHASE - 4 WIRE
FLA & LRC RATINGS CONVERTED TO TABLE HORSEPOWER (SEE NOTE #2)
USE FLA & LRC RATINGS WHERE NO HP IS LISTED
V-EA
RATED
CURRENT
(SEE NOTE #1)
0.30A
0.50A
0.75A
0.80A
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10.0A
12.0A
12.5A
13.0A
15.0A
16.0A
20.0A
25.0A
30.0A
32.0A
40.0A
50.0A
60.0A
MOTOR
NAMEPLATE
FLA
RATING
0.30A
0.50A
0.75A
0.80A
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10.0A
12.0A
12.5A
13.0A
15.0A
16.0A
20.0A
25.0A
30.0A
32.0A
40.0A
MOTOR
NAMEPLATE
STARTING/
LRC RATING
3.0A
5.0A
7.5A
8.0A
10.0A
16.0A
20.0A
25.0A
30.0A
35.0A
40.0A
42.0A
50.4A
67.2A
84.0A
100.8A
105.0A
109.2A
126.0A
134.4A
168.0A
210.0A
252.0A
268.8A
226.0A
50.0A
60.0A
282.5A
339.0A
110-120
VAC
Motor Design
B, C, D
E
200
VAC
Motor Design
B, C, D
E
208
VAC
Motor Design
B, C, D
E
220-240 VAC
(SEE NOTE #3)
Motor Design
B, C, D
E
1/2hp
1/2hp
1/2hp
3/4hp
3/4hp
440-480
VAC
Motor Design
B, C, D
E
1/2hp
3/4hp
1/2hp
3/4hp
1hp
11/2hp
2hp
2hp
3hp
3hp
5hp
5hp
71/2hp
71/2hp
71/2hp
10hp
10hp
10hp
15hp
20hp
20hp
20hp
25hp
30hp
1/2hp
1/2hp
1/2hp
3/4hp
1/2hp
1/2hp
1/2hp
3/4hp
1/2hp
1/2hp
3/4hp
3/4hp
1/2hp
1/2hp
3/4hp
3/4hp
1/2hp
1/2hp
1/2hp
3/4hp
3/4hp
1hp
1hp
2hp
2hp
3hp
3hp
3hp
3hp
3hp
5hp
5hp
5hp
5hp
71/2hp
1hp
1hp
2hp
2hp
3hp
3hp
3hp
3hp
3hp
5hp
71/2hp
71/2hp
10hp
10hp
1hp
1hp
2hp
2hp
3hp
3hp
3hp
3hp
3hp
5hp
71/2hp
71/2hp
10hp
71/2hp
1hp
11/2hp
2hp
3hp
3hp
3hp
3hp
3hp
5hp
5hp
71/2hp
10hp
10hp
10hp
1hp
11/2hp
2hp
3hp
3hp
3hp
3hp
3hp
5hp
5hp
71/2hp
10hp
10hp
10hp
1hp
11/2hp
2hp
2hp
3hp
3hp
5hp
5hp
71/2hp
71/2hp
71/2hp
10hp
10hp
10hp
15hp
20hp
20hp
30hp
10hp
10hp
15hp
20hp
10hp
10hp
15hp
20hp
10hp
15hp
30hp
40hp
1/2hp
1/2hp
3/4hp
1/2hp
1/2hp
3/4hp
1hp
11/2hp
11/2hp
11/2hp
2hp
2hp
3hp
3hp
5hp
5hp
5hp
1hp
11/2hp
11/2hp
11/2hp
2hp
2hp
3hp
3hp
5hp
5hp
5hp
1hp
1hp
2hp
2hp
3hp
3hp
3hp
3hp
3hp
5hp
5hp
5hp
5hp
10hp
71/2hp
10hp
71/2hp
10hp
15hp
15hp
NOTE #1: For AC motor circuit nameplate full load current, AC general-use loads, AC resistance loads, AC incandescent lamp (tungsten) loads,
AC electric discharge lamp (ballast) loads.
NOTE #2: Conversions per UL508® proposed Tables 45.2 and 45.4 and NFPA-70: National Electrical Code® 1999 Tables 430-149, 430-150 and 430-151B.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
20
V-EA INTERNAL RESISTANCE
Trip Characteristic
Rated
Current
(Amp)
B
(Ohms)
C
(Ohms)
D
(Ohms)
E
(Ohms)
G
(Ohms)
Z
(Ohms)
0.3
0.5
0.75/0.8
1.0
1.6
2.0
2.5
3.0
3.5
4.0
5.0
6.0
8.0
10
12/12.5
13
15/16
20
25
30/32
40
50
60/63
—
—
—
—
—
—
—
—
—
—
—
0.0528
—
0.0216
—
0.0113
0.0085
0.0067
0.0050
0.0032
0.0025
0.0019
0.0018
16.8620
6.8540
3.0540
1.7000
0.5870
0.4190
0.2950
0.2020
0.1390
0.1090
0.0654
0.0528
0.0278
0.0216
—
0.0084
0.0085
0.0067
0.0050
0.0032
0.0025
0.0019
0.0018
16.8620
6.0009
3.0540
1.7560
0.5870
0.4190
0.2950
0.2020
0.1390
0.1090
0.0654
0.0491
0.0240
0.0187
—
0.0085
0.0076
0.0064
0.0041
0.0027
0.0022
0.0018
0.0017
14.52000
5.92000
2.70000
1.48000
0.57400
0.40500
0.26900
0.18600
0.13900
0.10600
0.05900
0.04600
0.03040
0.02020
0.00724
0.00724
0.00731
0.00582
0.00411
0.00272
0.00212
0.00184
0.00172
16.8620
6.8540
3.0540
1.7560
0.5870
0.4190
0.2950
0.2020
0.1390
0.1090
0.0654
0.0491
0.0333
0.0211
0.0084
0.0084
0.0076
0.0064
0.0046
0.0030
0.0022
0.0019
0.00179
31.5060
10.2460
5.3920
2.6910
0.9440
0.8900
0.4290
0.3460
0.1790
0.1620
0.1050
0.0823
0.0371
0.0278
0.0151
0.0151
0.0114
0.0075
0.0050
0.0032
—
—
—
Resistances listed are “hot” values, as
opposed to cold start values. Operating
voltage drop across the V-EA and power
loss per pole can be approximated with
basic formulas:
VDROP
= IOPERATING x RTABLE
PLOSS P/P = I2OPERATING x RTABLE
Voltage drops should be reviewed when
V-EAs with high internal resistance are
used (e.g., load voltage minimums).
Power loss should be reviewed when
V-EAs with high rated currents are used
(e.g., enclosure heating).
The listed V-EA internal resistance values
should not be used in calculations of
available short-circuit current downstream
of the V-EA. The dynamic impedance of
the V-EA under short-circuit conditions
can vary significantly from internal
resistance values in normal operation.
LINE CURRENT FREQUENCY EFFECTS ON TRIP CURVES
Frequency Effects on Magnetic Trip Curves
Trip
Curve
Z
B
C
G
D
E
Trip Zone
Trip Zone
At
At
16 2/3 - 60Hz
100 Hz
(x RC)
(x RC)
2-3
3-5
5 - 10
8 - 10
10 - 16
14 - 18
2.2 - 3.3
3.3 - 5.5
5.5 - 11.0
8.8 - 11.0
11.0 - 17.6
15.4 - 19.8
Trip Zone
At
200 Hz
(x RC)
Trip Zone
At
400 Hz
(x RC)
Trip Zone
At
DC
(x RC)
2.4 - 3.6
3.6 - 6.0
6.0 - 12
9.6 - 12.0
12.0 - 19.2
16.8 - 21.6
2.8 - 4.2
4.2 - 7.0
7.0 - 14.0
11.2 - 14.0
14.0 - 22.4
19.6 - 25.2
3.0 - 4.5
4.5 - 7.5
7.5 - 15.0
12.0 - 15.0
15.0 - 24.0
21.0 - 27.0
The thermal trip is not affected by the frequency of the line
current. The magnetic trip is within the trip zone of the
characteristic curve for frequencies from 16 2/3 to 60Hz. At
lower and higher frequencies, the magnetic trip will be delayed
longer than indicated by the characteristic curve, roughly as
follows:
At 100Hz:
At 200Hz:
At 400Hz:
At DC:
Mag. Trip Current = 1.1 x curve current
Mag. Trip Current = 1.2 x curve current
Mag. Trip Current = 1.4 x curve current
Mag. Trip Current = 1.5 x curve current
For example, at 16 2/3 - 60 Hz the magnetic trip zone for the “G”
characteristic is 8 to 10 times the rated current of the specific
V-EA (i.e., hold for at least 100ms at 8 x RC, trip in less than
100ms at 10 x RC). With a 400Hz current, a magnetic trip at 10
x RC would be greatly delayed (thermal would likely trip first), as
the magnetic trip zone is now 11.2 to 14 x RC. If a quicker
magnetic trip is required with 400Hz, the “B” or “C” characteristic
should be considered.
MECHANICAL ENDURANCE RATINGS (ON/OFF OPERATIONS)
Application
AC
AC
AC
AC
AC
General Use
Motor Starting Across the Line
Incandescent Lamps (Tungsten)
Electrical Discharge Lamps (Ballast)
Resistance
Manufacturers self certification
2 x (1.15 x RC)
2 x RC
RC
No Load
Total
—
1000
—
—
—
6000
—
—
6000
6000
—
5000
6000
—
—
4000
4000
4000
4000
4000
10000
10000
10000
10000
10000
20000 ON/OFF operations with no load
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
21
SHORT CIRCUIT RATINGS FOR V-EA MANUAL MOTOR CONTROLLER
Backup
Protection
Trip
Curve
Amp Range
UL-Listed
RK5-Fuse
up to 10kA
UL-Listed
MCCB
up to 10kA
No BCP
Required
up to:
all
0.3 - 10A
4xRC*
min 15A, max 70A
4xRC*
min 15A, max 70A
10kA
all
12 - 30/32A
4xRC*
max 125A
4xRC*
max 125A
5kA
all
40 - 50A
4xRC*
max 200A
4xRC*
max 200A
5kA
all
60 / 63A
4xRC*
max 250A
4xRC*
max 250A
5kA
*up to nearest rated current
TEMPERATURE CORRECTION CURVE
Ambient Temperature and Adjacent Mounting/Loading Adjustment
Calibration Temperature
160
150
140
130
Adjacent Mounting Temperature
Adjustment 3% of RC for every
additional pole above 3.
Maximum 20% off RC for a total
of 10 poles or more.*
%
110
20
Rated Current (%)
120
Ambient Temperature Adjustment
5% of RC for every 10°C (18°F).
100
up
to 3
pol
es
90
adj
ace
nt m
oun
ted
80
ma
or ximum
mo
re, 20%
adj
ace off R
nt m C fo
oun r a t
ted otal
*
off
70
60
* Cooling spacer (Part #15.960)
between each group of 3 poles
will eliminate these adjustments.
50
10
pol
es
40
-40
-40
-30
-22
-20
-4
-10
14
0
32
10
50
20
68
30
86
40
104
50
122
60
140
70
158
80
176
90 (°C)
194 (°F)
Ambient Temperature
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
22
CUT-AWAY VIEWS OF V-EA MINIATURE CIRCUIT BREAKER
Shown in “on” position
Manual Disconnect/Reset
Thermal (Inverse-Time) Trip
Magnetic (Instantaneous) Trip
Arc Guides
Arc Chamber
De-ionization Chamber (Arc Chute)
Shown in “off” position
Magnetic Trip
Electromagnetic Coil
Thermal Trip
Bimetallic Element
Top Terminal
M5 Cross-Slot Screw
Bottom Terminal
M5 Cross-Slot Screw
Bottom Terminal Cage
Moveable Contact,
Pivoted Lever
Top Terminal Cage
Fixed Contact
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
23
INSTALLATION RECOMMENDATIONS
INTRODUCTION
EASY REMOVAL
The V-EA* easily snaps onto a readily available, international
standard 35mm DIN Rail. Mounting can be in any position from
full horizontal to full vertical without affecting performance.
All housings are the same size regardless of rated current,
simplifying layout and modifications.
Line power feed can be to either top or bottom terminals. This
provides flexibility to power distribution enclosure entry (top,
bottom, sides) and internal raceway runs (e.g., power in one
horizontal raceway can feed both the row above and the row
below).
Minimal free space is required to remove or replace the V-EAs,
and with standard housing and terminal sizes, ratings can be
changed or multi-poles can replace multi-single pole or viceversa. To obtain the highest density mounting arrangement
without serious problems from heat build-up, see “Temperature
Correction Curve” (page 22).
Removal, One Pole
1. Insert tip of 4mm or less straight blade screwdriver into the
slot of the metal retaining clip.
2. Brace the shank of the screwdriver against the terminal
side of the V-EA* and gently lever the clip away from the
DIN rail.
3. When the clip moves out, continue rotating screwdriver
and V-EA* up and off of the bottom of the DIN rail lip.
4. Grasp V-EA* and lift upwards to disengage from the top
lip of the rail, then remove.
Altech and our distributors are pleased to quote custom rail
assemblies. Multi-function assemblies can include cut-to-order
DIN Rail, mounted V-EA and MA circuit breakers, FI Earth
Leakage breakers, lightning/surge protectors, interface modules
(cable fan-out, relays, I/O, power supply, etc.), terminal blocks
with marking tags, and other control components to meet your
specifications. Order assemblies with only one part number or
even your drawing number.
DIN Rail Information
Mounting rails are internationally standardized and are available
in several sizes with or without perforations. Zinc-plated yellow
chromated steel is standard. Copper and aluminum DIN Rails
are also available. Please contact Altech for your DIN Rail
needs.
Stock
1.0mm (.039 in.)
Thick
15mm
(.59 in.)
7.5mm
(.28 in.)
TS35x7.5
Stock
1.5mm (.059 in.)
Thick
TS35x15
25mm
7
mm
CL
18mm
6.2mm
17.5mm
C
L
35mm
5.3mm
17.5mm
• Field wiring terminal size acceptability:
Top: 18-3 AWG
Bottom: 18-2 AWG
• Use 75°C insulation copper conductors only, loaded to
60°C ampacity.
35mm
(1.38 in.)
35mm
(1.38 in.)
WIRING
CL
• Wire conductor stripping length:
Top Terminals: 11.5mm (approximately 7/16”)
Bottom Terminals: 12.5mm (approximately 1/2”)
• For terminal screws, we recommend a #2 Phillips or
Posidriv screwdriver. Terminals are also readily
accessible to battery operated screwdrivers. Please
contact Altech for tool and ordering information.
• Terminal tightening torque is rule-of-thumb 20 lb.in.
5.3mm
TS35 DIN Rail Perforations Dimensions + 0.1mm (.003 in.)
SNAP-ON MOUNTING
1. Place the upper lip of the V-EA* under the upper lip of the rail.
2. Press down on bottom terminal area until the V-EA* springloaded clip snaps under lower lip of the rail.
* V-EA miniature circuit breaker handling is representative for MA
circuit breakers and FI Earth Leakage circuit breakers.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
24
V-EA DIMENSIONS
General
Mounting in
Enclosure
44mm (1.73 in.)
115mm (4.53 in.)
37.5mm (1.48 in.)
25.5mm (1.0 in.)
18mm
(.71 in.)
45mm (1.77 in.) NOTE 3
45.5mm (1.79 in.)
7mm
(.28 in.)
TS35 x 7.5
DIN Rail
46mm
(1.81 in.)
Actual
Cut-Out
Standoff
35mm (1.38 in.)
91.5mm (3.60 in.)
6mm (.24 in.)
Transparent
Outer Cover
of Enclosure
20mm
(.79 in.)
8mm (.31 in.)
14mm (0.55 in.)
15mm (.59 in.)
30.5mm
(1.20 in.)
3mm (.12 in.)
NOTE 2
Interior
(Cut-Out)
Cover
63mm (2.48 in.)
44mm (1.73 in.)
68mm (2.68 in.)
70mm (2.76 in.) NOTE 1
For note information see section below.
Not Shown: Width of Face (Thickness)
One Pole 17.5mm (.69 in.)
Two Pole 35mm (1.38 in.)
Three Pole 52.5mm (2.07 in.)
ALTECH/SPELSBERG EK/AK NONMETALLIC ENCLOSURES FOR MCBS
NOTE 1: For totally enclosing the V-EA, the
minimum interior depth of the enclosure is
70mm plus DIN Rail depth (7.5 or 15mm) plus
any rail mounting stand-off depth.
NOTE 2: Fork lugs with a thickness up to
3mm can be inserted in the lower terminals
under the head of the captive M5 (i.e. 5mm
diameter to outside of threads) terminal screw.
NOTE 3A: The V-EA’s raised face is sized to
fit through standard European enclosure cutouts, which allow sight and operation of the
trip/reset handle but keep all wiring covered.
As shown in Fig. 1, Altech/Spelsberg AK/EK
nonmetallic enclosures are ready-made for
this attractive and efficient packaging approach.
NOTE 3B: The V-EA was successfully shortcircuit tested in TYPE 1 metal enclosures with
the V-EA face extending through a 46mm cutout in the cover. Typical applications include:
• V-EA on 35mm wide by 15mm deep DIN
Rail, mounted to back wall of a 3 inch deep
enclosure with no back panel.
• V-EA on 35mm wide by 7.5mm deep DIN
Rail, mounted to the back panel of a 3 inch
deep enclosure with panel.
Fig 1. Altech/Spelsberg EK/AK nonmetallic enclosure with Altech/ABL Sursum V-EA
and MA Circuit Breakers installed.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
25
MA Three Phase
Adjustable Trip
Miniature Circuit Breakers/
Manual Motor Controllers
The MA was designed to handle the high
inrush loads of 3 phase transformers, power
supplies, motors, etc. The MA protects wiring
and equipment from damage caused by the
three major classes of over-current, yet
greatly reduces the number of nuisance trips
in high starting and inrush current circuits.
An IEC device with excellent ratings under a
UL listing at 480Y/277V (including group
ratings) and at 500V under international
standards, the Altech/ Sursum MA provides
short and long term cost effective circuit
protection for USA and/or export
applications. The short term advantages
include: (1) adjustable thermal trip allows
finalization of initial designs before
procurement of the load equipment is
complete; (2) snap-on mounting for readily
available, internationally standardized DIN
Rail saves panel layout design time as well
as installation and change labor; (3) large
cage-clamp terminals with screws suitable to
power screwdrivers, simplifies and speeds
wiring; (4) convenient switched disconnect
during factory testing and/or initial start-up
saves time and aggravation. The key long
term advantage is customer satisfaction and
proven over-current protection of wiring and
equipment (and the lack of rework/repair
costs).
Type and
Rated
Current
UL508 listed
CAN/CSA-C22.2 No.14 certified
Type Designation
MA
__
(a)
__
(b)
__
(c)
RT
__
(d)
(a) = MA - Manual Motor Controller
(b) = Rated Current
(c) = U - US Housing
(d) = Blank - Standard Terminal
RT - Ring-tongue Terminal
Voltage Rating
480Y/277VAC
AIC (Interrupt Capacity)
0.16A-2.5A: 42kA; 4.0A-16A: 14kA; 20A-40A: 10kA
Standard Short Circuit Withstand Rating 0.16A-2.5A: 42kA; 4.0A-16A: 14kA
(UL/CSA Ratings)
Group Short Circuit Ratings
(UL/CSA Ratings)
see above
Typical Life
6000 on/off operations with 2xRC
Calibration Temperature
25°C, +0°, -5° (77°F, +0° -9°)
Standard Pack and Weight
1/450g (1.0 lb.)
Terminal Size Acceptability
Top/Bottom: 18-3 AWG
Cat. No.
FLA Dial
Adjustment
Markings
MA0.16U
15.901U
0.1/ 0.12/0.14/0.16
MA0.25U
15.902U
0.16/0.19/0.22/0.25
MA0.40U
15.903U
0.25/0.30/0.35/0.40
MA0.63U
15.904U
0.40/0.48/0.56/0.63
MA1.0U
15.905U
0.63/0.75/0.87/1.0
MA1.6U
15.906U
1.0/1.2/1.4/1.6
MA2.5U
15.907U
1.6//1.9/2.2/2.5
MA4.0U
15.908U
2.5/3.0/3.5/4.0
MA6.3U
15.909U
4.0/4.8/5.6/6.3
MA10U
15.910U
6.3/7.5/8.7/10
MA16U
15.911U
10/12/14/16
MA20U
15.912U
16/17/18.5/20
MA25U
15.913U
20/21.5/23/25
MA32U
15.914U
25/27/30/32
MA40U
15.915U
32/34/37/40
GROUP SHORT
CIRCUIT RATING
AT 480VACa
(and BCP size)
42kARMS
symmetrical
(max. 1200A
MCCB
or RK5)
14kARMS
symmetrical
(max. 350A
MCCB
or RK5)
10kARMS
symmetrical
(max. 350A
MCCB
or RK5)
3Ø HORSEPOWER RATINGS AT NOMINAL LINE VOLTAGE
(See Note for HEA Definition)
110-120V
HP (HEA)
200V
HP (HEA)
208V
HP (HEA)
220-240V
HP (HEA)
460-480V
HP (HEA)
Through MA2.5U, ampere rated for motor circuits having a fullload-amperage (FLA) not exceeding the MA’s general purpose
rated current (RC, equals maximum dial setting) and a locked
rotor current not exceeding 6 times the MA’s RC.
1/2 (4.0)
3/4 (3.2)
3/4
(3.1)
1
(3.6)
2
3/4 (5.6)
11/2 (6.0)
11/2
(5.7)
11/2
(5.2)
3
(4.8)
1
(7.2)
2
2
(7.5)
3
(9.6)
5
(7.6)
2
(13.6)
3 (11.0)
3
(10.6)
5
(15.2)
10
(14.0)
3
(19.2)
5 (17.5)
5
(16.7)
5
(15.2)
10
(14.0)
3
(19.2)
5 (17.5)
71/2
(24.2)
71/2
(22.0)
15
(21.0)
5
(30.4)
71/2 (25.0)
71/2
(24.2)
10
(28.0)
20
(27.0)
5
(30.4)
10 (32.0)
10
(31.0)
10
(28.0)
25
(34.0)
(7.8)
(3.42)
Note: HEA - Horsepower Equivalent Amperes, the nominal amperage assigned to standard motor horsepower ratings in design guide tables such as
NFPA-70 Tables 430-148, 430-149, 430-150; UL1077 Table 16.2; CSA - C22.2 No. 235-M89 Tables 44 and 45; CSA-C22.2 No. 14-M91 Table 19, etc.
Multiply HEA values (in parenthesis) by 1.1 if power factor is 90%, and by 1.2 if power factor is 80%.
a The standard-circuit short-circuit rating is 14kA for all types. Group ratings can be used in a standard circuit (e.g., MA1.0U at 42kA), but a higher
standard rating cannot be used in a group circuit (e.g., MA40U at 14kA only in standard circuit.)
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
26
DIMENSIONS
TRIP CHARACTERISTICS MA/U
120
44mm (1.73 in.)
60
40
37.5mm (1.48 in.)
20
25.5mm (1.0 in.)
10
Tripping time t
Minutes
7mm
(.28 in.)
6
4
2
1
40
20
10
45mm (1.77 in.)
35mm (1.38 in.)
6
4
2
1
Seconds
45mm (1.77 in.)
89.5mm (3.52 in.)
6mm (.24 in.)
MA0.16U-MA16U
MA 3 Phase Controller
Thermal Overload (B, C, D)
“Must Trip” Current = 115% of Dial Setting
“Must Not Trip” > 1 hr = 105% of Dial Setting
0.6
0.4
Magnetic Trip
Nominal 1100% of Rated Current
0.2
0.1
7mm (.28 in.)
1 1.15 1.5
2 2.3 3
4 5 6 6.9 8 10 12
16 19
Multiple of Dial Setting (Thermal)
Multiple of Rated Current (Magnetic Trip)
Rated Current = Max. Dial Setting
17.5mm (1.28 in.)
120
30.5mm
(1.20 in.)
3mm
(.12 in.)
60
40
44mm (1.73 in.)
20
68mm (2.68 in.)
MA20U-MA40U
MA 3 Phase Controller
Thermal Overload (B, C, D)
“Must Trip” Current = 115% of Dial Setting
“Must Not Trip” > 1 hr = 105% of Dial Setting
1
3
L2
L1
5
L3
Tripping time t
Minutes
10
6
4
2
1
40
20
10
6
4
MA.16
VDE 0660 AC-3
500V
50-60Mz
12A
10A
14A
16A
40°C
20°C
2
1
T1
T2
2
Seconds
ABL SURSUM
T3
4
0.6
0.4
0.2
6
0.1
52.5mm (2.07 in.)
Magnetic Trip
Nominal 1100% of Rated Current
11.15 1.5
2 2.3
3
4
5 6 6.9 8 1012 15
12.5
Multiple of Dial Setting (Thermal)
Multiple of Rated Current (Magnetic Trip)
Rated Current = Max. Dial Setting
MA/USA Manual Motor Controller
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
27
MS Three Phase
Adjustable Trip Economy
Manual Motor Controllers
Due to its high breaking capacity with high current limitation the MS
Manual Motor Controllers provide an optimum of protection for
electrical motors as well as for other consumer units up to 25 amps.
They are equipped with phase failure sensitivity, isolating and main
switch functions; 13 ranges are covering nominal rated currents from
0.1 up to 25 amps.
The MS’s are temperature compensated; the trip current of the
magnetic part is 12 x ln. The Manual Motor Controllers are built in
accordance with IEC 947.
with overload and short circuit protection,
phase failure sensitivity according to
IEC 947-4-1, DIN VDE 0660 Part 102
Type/
Rated
Cat. No. Current
C
US
Type Designation
MS
—
(a)
016
—
(b)
(a) = MS - Manual Motor Controller
(b) = Rated Current
MS016
MS025
MS04
MS063
MS1
MS1.6
MS2.5
MS4
MS6.3
MS10
MS16
MS20
MS25
0.16
0.25
0.4
0.63
1.0
1.6
2.5
4.0
6.3
10.0
16.0
20.0
25.0
Overload
Instantaneous
3Ø Horsepower Rating
release
setting
adjustment/FLA
(A)
(A)
115V 200V 230V 480V 600V
0.1 - 0.16
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.63 - 1
1 - 16
1.6 - 2.5
2.5 - 4
4 - 6.3
6.3 - 10
10 - 16
16 - 20
20 - 25
Maximum Voltage
600V AC (MS20 and MS25, 480V AC)
Interrupting Capacity (UL/CSA Rating)
5kA
Group Short Circuit
(UL/CSA - Ratings)
5kA
Interrupting Capacity
(VDE - Ratings)
0.16-6.3A: Self protected
10-25A: 6kA
Mechanical Endurance
10000 on/off operations
Standard Pack and Weight
1/250g (0.55lb)
Terminal Size Acceptability
14-10AWG
Terminal Torque
1.8Nm (16lb. in.)
1.92
3
4.8
7.6
12
19.2
30
48
75.6
120
192
240
300
Ampere rated for motor circuits having
–
–
–
–
–
a full-load-amperage (FLA) not
–
–
–
–
–
exceeding the MS’s general purpose
–
–
–
–
–
rated current and a locked rotor
–
–
–
–
–
current not exceeding 6
–
–
–
1/2hp
1/2hp
times the MS’s rated
–
–
–
3/4hp
1hp
current.
–
1/2hp
1/2hp
1hp 11/2hp
1/2hp
3/4hp
1hp
2hp
3hp
3/4hp 11/2hp 11/2hp
3hp
5hp
1hp
2hp
3hp
5hp 71/2hp
2hp
3hp
5hp
10hp 10hp
3hp
5hp 71/2hp 15hp
–
3hp
5hp 71/2hp 15hp
–
Dimensions
30mm
(1.18 in.)
42mm
(1.65 in.)
35.5mm
(1.40 in.)
45mm
(1.77 in.)
80mm (3.15 in.)
76.5mm (3.01 in.)
45mm
(1.77 in.)
63mm
(2.48 in.)
71.5mm (2.81 in.)
75.5mm (2.97 in.)
85.5mm (3.37 in.)
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
28
Accessories
MS Three Phase Adjustable Trip Economy Manual Motor Controllers
Auxiliary contact blocks for side mounting (3.5A/230VAC; 2A/400V AC)
Width
mm
Contacts
Type/
Cat. No.
Weight
Std.
Pk.
9
2NO
HMS20
40
10
9
1NO + 1NC
HMS11
40
10
9
1NO
HMS10
35
10
9
2NC
HMS02
40
10
9
1NC
HMS01
35
10
Insulated Enclosure IP 55
Emergency-Stop
with integrated PE(N) terminal top and
bottom each 2 metric knock-outs
twist or key to release,
red on yellow background
Type/
Cat. No.
Weight
g/pc.
Std.
Pk.
MS.G55
240
1
Release
Type/
Weight
Type
Cat. No. g/pc.
Twist
Key
MS.PV
MS.PS2
Std.
Pk.
60
65
5
5
Indicator Light
Flush Mounting Enclosure IP55
with neon bulb, nominal rated voltage:
220 - 240V or 380 - 440V
with integrated PE(N) terminal
Type/
Cat. No.
Weight
g/pc.
Std.
Pk.
MS.F55
170
1
Color
Type/
Weight Std.
Cat. No.
g/pc. Pk.
220-240V 380-440V
trans
green
red
yellow
MS.SLW2
MS.SLG2
MS.SLR2
MS.SLJ2
MS.SLW3
MS.SLG3
MS.SLR3
MS.SLJ3
10
10
10
10
5
5
5
5
Busbar
Busbar
63A
no
spacing
for
2 MS
G45-14-2
with auxiliary
switch
(1/2 pole)
G54-14-2
spacing
Type/Cat. No.
for
for
3 MS
4 MS
G45-14-3
G54-14-3
for
5 MS
Power Feed Block
Type/
Cat. No.
Rating
(A)
Std.
Pk.
GE2-14
63A
1
G45-14-4 G45-14-5
G54-14-4 G54-14-5
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
29
FI Earth Leakage
Circuit Breakers
FI compact Earth Leakage Circuit
Breakers detect and interrupt earth
(ground) faults. They are VDE
approved for the European system
of protecting people, animals,
equipment and property from
dangerous line-to-ground and shock
hazard currents.
US applications include ground-fault
protection of equipment (GFPE)
using the 10mA and 30mA fault
current ratings, especially when high
distributed capacitance or other
leakages cause excessive nuisance
trips at lower fault currents.
Applications for the 300mA rating are
equipment protection and fire
prevention, limiting the energy of a
fault to less than the minimum
ignition energy for many materials.
FI 2
Type Designation
__
__ • __
FI (a)
(b)
(c)
(a) = 2-2 pole; 4-4 pole
(b) = 1-16A; 2-25A; 3-40A; 4-63A
(c) = 01 - 10mA
= 03 - 30mA
= 30 - 300mA
FI 4a
Maximum
Rated
Line
Current
Fault
Trip
Current
Type
Cat. No.
16A
10mA
FI 21.01
15.921
25A
25A
30mA
300mA
FI 22.03
FI 22.30
40A
40A
30mA
300mA
FI 23.03
FI 23.30
Fault
Trip
Current
Type
Cat. No.
15.922
15.924
30mA
300mA
FI 42.03
FI 42.30
15.926
15.929
15.923
15.925
30mA
300mA
FI 43.03
FI 43.30
15.927
15.930
63A
63A
30mA
300mA
FI 44.03
FI 44.30
15.928
15.931
Earth Leakage Circuit Breaker
with Auxiliary Contactsb
Earth Leakage Circuit Breaker
with Auxiliary Contactsb
25A
40A
63A
30mA
30mA
30mA
30mA
30mA
FI 22.03Y 15.932
FI 23.03Y 15.934
FI 42.03Y
FI 43.03Y
FI 44.03Y
15.933
15.935
15.936
Voltage Rating (maximum)
240VAC, 50/60Hz
(VDE: 125/220VAC, 50Hz)
Short Circuit Capacity
Up to rated current (RC) 40A = 1.5kA, RC 63A = 2kA. 10kA in combination with series fuse of
European Operation Class gL/gG: RC 16A = 63A fuse, RC 20/40A = 80A fuse, RC 63A = 100A fuse.
Fault Trip Current Calibration
FI trips are calibrated at less than fault trip current for ensured safety (Typical trip range between
66.6-83.3% fault trip current, e.g., typical trip at 20-25mA for fault RC of 30mA)
Typical Life
Fully functional after 4,000 operations to DIN/VDE 0664 (CEE27) and 16000 additional fault current trips.
Standard Pack and Weight
1/290g (0.64 lb.);
1/390g (0.86 lb.) with auxiliary contact
1/450g (1.0 lb.)
1/550g (1.21 lb.) with auxiliary contact
Terminal Size Acceptability
16-6 AWG
14-3 AWG
415VAC, 50/60Hz (400Hz available on request)
(VDE: 220/380VAC, 50Hz)
Equivalent Circuit
1
2
a For 2-Phase applications, terminal 5 and 6 (next
to Neutral terminals) must be connected to one
phase for the test circuit to be operable.
N
N
1 3 5 N
Test
2 4 6 N Test
Note: If the power system has a marked conductor, it must connect through the FI and not be grounded at any
point downstream.
b Provided with mounted Auxiliary Switch, one N.O.,
one N.C. isolated feedthrough contact (Form X
double make and Y double break), which adds
9mm (.35 in.) to the width dimension.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
30
64mm (2.52 in.)
58mm (2.28 in.)
5
N
72.5mm (2.85 in.)
72.5mm (2.85 in.)
36mm (1.42 in.)
2
N
2
4
6
N
36mm (1.42 in.)
3
90.5mm (3.56 in.)
1
46°
R1
N
22.9mm
(0.90 in.)
R1
1
13.5mm
(0.53 in.)
45.4mm (1.79in.)
88°
10.9mm
(0.43 in.)
13.5mm
(0.53 in.)
R1
5.8mm
(0.23 in.)
8mm
13.5mm
(0.31 in.) (0.53 in.)
3.2mm
(0.13 in.)
9mm
(0.35 in.)
18mm
(0.71 in.)
9mm
(0.35 in.)
18mm
(0.71 in.)
18mm
(0.71 in.)
FI 2
FI 4
6.5mm
(0.26 in.)
31mm (1.22 in.)
18mm
(0.71 in.)
72mm (2.83 in.)
36mm (1.42 in.)
15.7mm
(0.62 in.)
44mm (1.73 in.)
68mm (2.68 in.)
FI 2 and FI 4
Temperature Range
Environmental Information marked with “Snowflake” approval for -25°C to 40°C (-13°F to 104°F) ambient
temperature. (Temperature effect on RC: for every 10°C temperature rise above 40°C decrease RC by 7%.)
Fluctuating Climate Conditions
To maximum 45°C, 95% relative humidity.
Electrical Shock Protection
Uninsulated electrically live parts within 30mm of the operating handle are “finger safe” (terminal screw
heads) and uninsulated live parts within 100mm of the operating handle are “back-of-hand safe” (terminals).
Impact/Shock Protection
15g with impact force half-cycle sinusoidal and 11ms duration, 18 impacts total with 6 on each principal axis
(3 impacts each face). FI is DIN Rail mounted during the test, and electrically loaded with 25% of Fault RC.
Successful testing required no trip during the test, no damage and no loosened parts.
Vibration/Seismic Resistance
5g, at frequency of 55Hz to 2,000Hz, applied for 35 ± 5 minutes along each of the three principal axes, plus
5 minutes of application at every established critical resonant frequency. FI is DIN Rail mounted during the
test, and loaded with 25% Fault RC. To pass, the FI did not trip at 25% Fault RC, but did trip between each
of the principal axis tests when the fault current was raised to 125% Fault RC, and there was no damage
and no loosened parts. Suitable for machinery and mobile vehicle applications.
Housing Class
Ingress Protection (IP) Class 40; internal working components and live parts (excluding terminals) are
protected against ingress of solid objects greater than 1mm diameter (class 4-), but have no protection from
ingress of water (class-0).
Non-Sinusoidal Fault
The FI is tested and approval stamped for tripping sensitivity to non-sinusoidal fault currents, which become
zero or almost zero within one cycle of the line frequency. Waveforms and allowed trip-current ranges are as
follows:
1.
AC Sinusoidal Fault - 0.5-1.0 times Fault RC
2a.
Pulsating DC Fault;
Positive and Negative Half-Waves - 0.35-1.4 times Fault RC
Phased Half-Wave, 90° - 0.25-1.4 times Fault RC
Phased Half-Wave, 135° - 0.11-1.4 times Fault RC
2b.
3.
Insulation Category
Pulsating DC on 6mA
DC (continuous) Base - Max. 1.4 times Fault RC + 6mA
At VDE rated voltage, suitable for Class C environments with relatively high dust and moisture levels and
little HVAC control, e.g., industrial, commercial, agricultural; on machine tools, hoists, warehouse equipment,
etc.; in boiler rooms, unheated storage, covered shipping/receiving, open workshops, etc.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
31
V-EA and MA
Circuit Breaker
Accessories
Accessories can be factory or field
mounted on V-EA miniature circuit
breakers and MA motor protection
switches for enhanced control and
monitoring
capabilities.
Field
mounting kits include all necessary
parts and instructions. Accessories
can be gang mounted on a single
breaker (the Auxiliary Switch in the
outside position). The mounting
arrangement links the internal latchpins for the tripping mechanisms,
ensuring
simultaneous
trips.
Handles are linked to simplify
manual resetting.
FA
UA
Shunt Trip
Undervoltage Trip
Type/
Cat. No.
Trip/Coil
Voltage
AC/DC
FA12U
FA24U
FA48U
FA110Ua
FA110Ua
FA110Ua
12V
24V
48-72V
110V
220V
380VAC
Max. Coil
Current
Approvals
1.3A
0.6A
0.2A
0.25A
0.5A
0.8A
UL
UL
UL
UL
UL
UL
Std.Pk.: 1
Unit Weight: 120 grams (0.27 lb.)
Width: 17.5mm (.689in.)
Coil actuated, the FA Shunt Trip allows
electrical remote tripping of a breaker. It
is trip-free and the housing and terminal
specifications are the same as for V-EA
miniature circuit breakers.The Shunt Trip
contains its own contacts which break
the tripping power circuit when tripped. It
is available with trip-coils in most
standard control voltages. The device is
UL and CSA listed for general use.
Type/
Cat. No.
UA120
UA208
UA240
UA277
UA415
UA480
Line Voltage
60Hz*
120VAC
208VAC
240VAC
277VAC
415VAC
480VAC
Std.Pk.: 1
Unit Weight: 70 grams (0.16 lb.)
Width: 17.5mm (.689in.)
Re-power your system under controlled
conditions following a power loss or
serious undervoltage. Altech/Sursum UA
Undervoltage Trips are coupled to the
tripping latch pins of the V-EA or MA to
which they are attached, reliably producing trips at the drop-out voltage and
preventing resetting when less than 85%
line voltage is present. The Undervoltage
Trip is provided with at least 6-inch
pigtails of stranded fixture wire for hookup to the V-EA or MA line terminals.
• Reset-Hold Voltage = 0.85 x Ve
• Drop-Out Voltage = 0.35 to 0.7 x Ve
aOne device with wide voltage range.
* Please consult Altech for your 50Hz
application needs.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
32
H
Lock-out
Auxiliary Switch
Type/
Cat. No.
H11U
Approvals
UL
HFI11
❶
Cat. No. EASS
Prevent inadvertent
resetting of the V-EA or MA
during maintenance.
Fits 1/4” pad lock.
Ring Tongue
Terminals
Available for VE-A and
MA series. Please
specify when ordering
and refer to type
designation.
For Use With:
V-EA, MA
FI
Std. Pk.: 1
Unit Weight: 45 grams (0.12 lb.)
Width: 9mm (.354in.)
Contact Ratings
H11U
HFI11
10A / 220V AC
6A / 230V AC
3A / 110V DC or pulsed
–
1A / 220V DC or pulsed 1A / 220V DC or pulsed
4mm2 (12 AWG)
Wire Size (max.)
4mm2 (12 AWG)
Two isolated, feedthrough Form X and
Y contacts are provided: one with the
same form as the breaker (HS designation, closed auxiliary contacts when
breaker is on and breaker contacts are
closed); and one with the opposite form
as the breaker (HO designation, closed
auxiliary contacts when breaker is
tripped and breaker contacts are open).
Upper level terminals are metalstamped "HS" and lower level terminals
are stamped "HO", providing clear identification for drawings and physical
wiring (line/load on either terminal).
Altech/Sursum H Auxiliary Switch is
suitable for logic interrogation and for
use as a two-circuit Form C contact. It
can also function as an auxiliary switch
for control circuits. The H11U is UL and
CSA listed for general use.
Busbar Systems
Cooling Spacer
Please see pgs. 32-35
for your busbar needs.
Cat. No. 15.960
See also Correction
Curve, pg. 22.
❶ V-EA and MA can also be locked in the on and off position by simply using a
common lead or meter seal, which gets fed through the hole in the handle
and a corresponding hole in the case housing.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
33
Altech Busbar Systems
The Altech Busbar system is an innovative
way to jumper up to 57 poles of Altech
Miniature Circuit Breakers (MCB)/ Manual
Motor Controllers (MMC).
Without Busbar
The advantages of this jumper system are:
• Installation time savings
• Panel space savings
• Less or no maintenance
• High electrical ratings
• Customers can cut the busbar
without losing the UL approval
With Busbar
Tw o Po wer Feed Methods
START/ END Feed Method
CENTER/ MIDDLE Feed Method
Rated current per phase
Rated current per power feed block
L1
80A
L2
80A
L3
80A
L1
2
18mm : 160A
25mm : 100A
100A
100A
25mm : 200A
2
18mm :
2
L1
L2
2
L2
160A
L3
160A
200A
200A
L3
80/100A
80/100A
80/100A
80/100A
80/100A
80/100A
L1
80/100A
80/100A
L2
80/100A
L3
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
34
Accessories
Power Feed Devices
Power Feed Lug
Application examples:
Power Feed Block*
UL508 listed
UL File 205412
Easy connection of the power supply wires to
the busbar/MCB. Power Feed Devices
ensures permanent connection.
UL508 listed
UL File 205412
Type Designation
T
—
(d)
DIN Rail Clip
16 mm
(0.63 in.)
43.5 mm
(1.71 in.)
Power Feed lug/block
50mm2 or 95mm2 cross-section area
USA and Canadian design basics
T-Terminal connection
B-Busbar connection
31.6 mm
(1.24 in.)
11 mm
(0.43 in.)
35.6 mm
(1.40 in.)
31.6 mm
(1.24 in.)
35.6 mm
B (1.40 in.)
A
63 mm
(2.48 in.)
6.8 mm (0.27 in.)
Type/Cat. No.
Electrical Ratings
Terminal Site Acceptability
Recommended/Required Torque
Material of Lug
Insulation Material
For use with
3 mm (0.12 in.)
P50UT
115A/480VAC
10-1/0 AWG
5.6Nm (50lb. in.)
MS58 Brass
Zytel FR 72G25-V Plastic
18 and 25mm2 1-3 phase Busbar
63 mm
(2.48 in.)
59 mm (2.32 in.)
(a) =
(b) =
(c) =
(d) =
U
—
(c)
28.5 mm
(1.12 in.)
21 mm
(0.83 in.)
P 50
— —
(c) (b)
88.5 mm
(3.48 in.)
A
B
P95UB
200A/480VAC
1-4/0 AWG
19.5Nm (175lb. in.)
MS58 Brass
Zytel FR 72G25-V Plastic
18 and 25mm2 3 phase Busbar
Assembly Instructions
P50UT
P95UB
The power feed lugs (Cat. # P50UT) fit together with the lugs of
the busbar in the terminals of the MCB/MA.
Miscellaneous Accessories
Type/Cat. No:
For use with:
End Caps
18/25CAP3P
18/25mm2 2&3 phase Busbar
Insulation Caps
BRS5
18/25mm2 1-3 phase Busbar
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
35
BUSBAR ORDERING
INFORMATION
1 PHASE
UL508 listed
UL File 205412
For choosing the proper busbar, please
consider the following specifications:
1. Number of phases
56 x 17.8 = 996.8 mm (39.24 in.)
17.8 mm (0.70 in.)
3.5 mm (0.14 in.)
2. Number of devices / MMCs
2 mm (0.79 in.)
3. Number of poles/number of pins
❶
15 mm (0.59 in.)
15 mm (0.59 in.)
4. Sum of out going device currents
1007 mm (39.65 in.)
Type/Cat. No. Designation:
3
P
— —
(a) (b)
25
—
(c)
U
—
(d)
3
—
(e)
H
—
(f)
/
—
(g)
(a) = Number of transverse copper strips
inserted. (Can be 1, 2 or 3 for
1, 2 or 3 phases)
(b) = Pin version
(c) = 18mm2 or 25mm2 cross-section area
(d) = USA and Canadian design basics
(e) = 1 or 3 track insulation
(f) = Blank - No Spacing
H-Auxiliary Switch (1/2 pole)
spacing
(g) = Total number of pins
18mm2
Type/Cat. No.
No. of
Pins ❷
No. of MMC
to Jumper
Length/
mm
1P18U1/2
1P18U1/4
1P18U1/8
1P18U1/12
1P18U1/24
1P18U1/36
1P18U1/48
1P18U1/57
2
4
8
12
24
36
48
57
2x1 pole
4x1 pole
8x1 pole
12x1 pole
24x1 pole
36x1 pole
48x1 pole
57x1 pole
32
68
144
208
420
638
852
1009
1 PHASE
UL508 listed
UL File 205412
Technical Specifications:
36 x 27 = 972 mm (38.27 in.)
• Material of Busbar: E-Cu58 F25 Copper
• Insulation Track Material:
27 mm (1.06 in.)
2 mm (0.79 in.)
4mm (0.16 in.)
Bergamid B700 Plastic (130°)
• Electrical Ratings:
15 mm (0.59 in.)
15 mm (0.59 in.)
18mm2: 80A/480VAC
25mm2: 100A/480VAC
• Manufactured according to VDE 0660
Part 100 and 502, VDE 0606, VDE 0659
982 mm (38.66 in.)
With Auxiliary Switch (1/2 pole) Spacing ❸
NOTES:
❶ Do not exceed the busbars rated current.
❷ For additional pin configurations,
please consult Altech.
18mm2
Type/Cat. No.
No. of
Pins ❷
No. of MMC
to Jumper
Length/
mm
1P18U1H/2
1P18U1H/4
1P18U1H/8
1P18U1H/12
1P18U1H/18
1P18U1H/24
1P18U1H/30
1P18U1H/37
2
4
8
12
18
24
30
37
2x1 pole
4x1 pole
8x1 pole
12x1 pole
18x1 pole
24x1 pole
30x1 pole
37x1 pole
48
102
206
314
472
640
804
982
❸ For one pole spacing busbars, please consult Altech.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
36
2 PHASE
3 PHASE
L2
L1
Copper strips
Insulation Track
End Cap
L2
56 x 17.75 = 994 mm (39.13 in.)
17.75 mm
(0.70 in.)
7 mm
(0.28 in.)
37 mm
(1.46 in.)
7 mm
(0.28 in.)
2 mm (.079 in.)
L3
21 mm
(0.83 in.)
End Cap
L2
L1
Copper strips
Insulation Track
End Cap
L3
L1
L2
2 mm (.079 in.)
37 mm
(1.46 in.)
55 x 17.75 = 976 mm (38.43 in.)
17.75 mm
(0.70 in.)
UL508 listed
UL File 205412
13 mm (.51 in.)
13 mm (.51 in.)
UL508 listed
UL File 205412
End Cap
21 mm
(0.83 in.)
L1
1009 mm (39.72 in.)
991 mm (39.02 in.)
18mm2
Type/Cat. No.
25mm2
Type/Cat. No.
No. of
Pins ❷
No. of MMC
to Jumper
Length/
mm
18mm2
Type/Cat. No.
25mm2
Type/Cat. No.
No. of
Pins ❷
No. of MMC
to Jumper
Length/
mm
2P18U3/4
2P18U3/8
2P18U3/12
2P18U3/18
2P18U3/24
2P18U3/36
2P18U3/48
2P18U3/56
2P25U3/4
2P25U3/8
2P25U3/12
2P25U3/18
2P25U3/24
2P25U3/36
2P25U3/48
2P25U3/56
4
8
12
18
24
36
48
56
2x2 pole
4x2 pole
6x2 pole
9x2 pole
12x2 pole
18x2 pole
24x2 pole
28x2 pole
65
137
208
315
421
635
849
991
3P18U3/6
3P18U3/9
3P18U3/12
3P18U3/18
3P18U3/24
3P18U3/36
3P18U3/48
3P18U3/57
3P25U3/6
3P25U3/9
3P25U3/12
3P25U3/18
3P25U3/24
3P25U3/36
3P25U3/48
3P25U3/57
6
9
12
18
24
36
48
57
2x3 pole
3x3 pole
4x3 pole
6x3 pole
8x3 pole
12x3 pole
16x3 pole
19x3 pole
101
154
208
315
421
635
849
1009
2 PHASE
3 PHASE
UL508 listed
UL File 205412
13 mm (.51 in.)
15 x 62.3 = 934.5 mm
13 mm (.51 in.)
62.3 mm (2.45 in.)
2 mm (.079 in.)
7 mm (0.28)
17.8 mm
(0.70 in.)
2 mm (.079 in.)
37 mm
(1.46 in.)
37 mm
(1.46 in.)
7 mm (0.28 in.)
22 x 44.5 = 979 mm (38.54 in.)
44.5 mm (1.75 in.)
17.8 mm (0.70 in.)
UL508 listed
UL File 205412
21 mm
(0.83 in.)
21 mm
(0.83 in.)
1009 mm (39.72 in.)
982 mm (38.66 in.)
With Auxiliary Switch (1/2 pole) Spacing
❸
With Auxiliary Switch (1/2 pole) Spacing ❸
18mm2
Type/Cat. No.
25mm2
Type/Cat. No.
No. of
Pins ❷
No. of MMC
to Jumper
Length/
mm
18mm2
Type/Cat. No.
25mm2
Type/Cat. No.
No. of
Pins ❷
No. of MMC
to Jumper
Length/
mm
2P18U3H/4
2P18U3H/8
2P18U3H/12
2P18U3H/18
2P18U3H/24
2P18U3H/36
2P18U3H/46
2P25U3H/4
2P25U3H/8
2P25U3H/12
2P25U3H/18
2P25U3H/24
2P25U3H/36
2P25U3H/46
4
8
12
18
24
36
46
2x2 pole
4x2 pole
6x2 pole
9x2 pole
12x2 pole
18x2 pole
23x2 pole
74
164
253
386
520
787
1009
3P18U3H/6
3P18U3H/9
3P18U3H/12
3P18U3H/18
3P18U3H/24
3P18U3H/36
3P18U3H/48
3P25U3H/6
3P25U3H/9
3P25U3H/12
3P25U3H/18
3P25U3H/24
3P25U3H/36
3P25U3H/48
6
9
12
18
24
36
48
2x3 pole
3x3 pole
4x3 pole
6x3 pole
8x3 pole
12x3 pole
16x3 pole
110
172
235
359
484
733
982
❸ For one pole spacing busbars, please consult Altech.
❸ For one pole spacing busbars, please consult Altech.