Altech 1G10UM Datasheet

Typical UL508 Application
Altech's V-EA UL508
Manual Motor Controllers
are approved for
Group Installations
Disclaimer: This an application example. Installation should be done by a qualified
electrician under the guidance of UL/NEC® specifications..
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
AltechUL508
PowerCircuitofaUL508APanel
21
AltechUL508
V-EASeries
508 listed
E137938
C22.2 No.14 certified
LR104391
UL508 Listed
Manual Motor Controllers
“Suitable as Motor Disconnect”
•
•
•
•
•
DIN Rail Mounted
17.5mm width per pole
Thermal Magnetic
480Y/277V AC, 50/60Hz
10kA Short Circuit
Withstand Capacity
• Applications Include:
•
•
•
•
•
AC Motor Starting, Across the Line
AC General Use
AC Resistance
AC Discharge Lamps (Ballast)
AC Incandescent Lamps (Tungsten)
VoltageRating
ShortCircuitWithstandRating
(UL/CSA-Ratings)
GroupShortCircuitWithstandRating
(UL/CSA-Ratings)
InterruptingCapacity(VDE-Ratings)
CalibrationTemperature
OperatingTemperature
StorageTemperature
TerminalSizeAcceptability
TerminalTorque
TerminalProtectionDegree
HorsePowerRatings
MechanicalEnduranceRatings
480Y/277VAC
0.3-25A: 1 pole - 42VDC; 2 Pole - 80VDC
30-60A: 1 pole - 24VDC; 2 Pole - 60VDC
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-10A (RC): 10kA; 12-60A (RC): 5kA
no branch circuit protection required
0.3-63A (RC): 10kA
40°C (104°F)
-25°C to 55°C (-13°F to 131°F)
-40°C to 70°C (-40°F to 158°F)
Top: 18-3 AWG; Bottom: 18-2 AWG (Line/Load reversible)
20 lb.in.
IP20
see page 32
see page 33
s h o r t c ir c u it Wit h s t a n d r at in g s f o r v -e a ma n u a l mo t o r c o n t r o l l e r
Trip
Curve
AmpRange
Backup
Protection
UL-Listed
RK5-Fuse
upto10kA
UL-Listed
MCCB
upto10kA
NoBCP
Required
upto:
all
0.3 - 10A
4xRC*
min 15A, max 70A
4xRC*
min 15A, max 70A
10kA
all
12 - 30/32A
4xRC*
max 125A
4xRC*
max 125A
5kA
all
40 - 50A
4xRC*
max 200A
4xRC*
max 200A
5kA
all
60 / 63A
4xRC*
max 250A
4xRC*
max 250A
5kA
*up to nearest rated current
22
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
Minutes
60
40
Time
versus
CurrentTripCurve
10
4
1
For the exact trip curve,
please refer to pages 30-31.
10
Time t
4
1
Dimensionsinmm
0.4
Z
B
CG D E
sideview
10-1
35 mm
(1.38 in.)
Seconds
4x10-2
10-2
4x10-3
10-3
2
3 4
74.7 mm
(2.94 in.)
6 8 10 16 20
Multiple of Rated Current
1 Po l e
2 Po l e
3 Po l e
93.3 mm
(3.67 in.)
93.3 mm
(3.67 in.)
17.5 mm
(0.69 in.)
93.3 mm
(3.67 in.)
35 mm
(1.38 in.)
52.5 mm
(2.07 in.)
ApplicationOverview
Trip-Characteristics*
Thermal Trip
Magnetic Trip
Must not Must Trip Must not Must Trip
Trip>100ms
<1hr
Trip>100ms at 100ms
Semiconductors
Lighting
Wiring
Protection
Control
Circuits
Motors
Business
Power
Equipment Transformers Supplies
Appliances
Heaters
General
Low
Inrush
High
Inrush
Components/
General
devices with Reactive
Solenoid low surgeElectronics
Load
current and
short
circuit
High
withstand
Efficiency
capabilities
B-Characteristics
1.13xRC
1.45xRC
3xRC
5xRC
C-Characteristics
1.13xRC
1.45xRC
5xRC
10xRC
D-Characteristics
1.13xRC
1.45xRC
10xRC
16xRC
E-Characteristics
1.05xRC
1.35xRC
14xRC
18xRC
G-Characteristics
1.05xRC
1.35xRC
8xRC
10xRC
Z-Characteristics
1.05xRC
1.35xRC
2xRC
3xRC
*The value of each characteristic is shown vertically beneath its corresponding heading.
Warning!
This information should only be used as a selection guide. The use of a Miniature Circuit Breaker/Manual Motor Controller
in an application with a certain Trip-Characteristic always requires prototype testing! It is the responsibility of the circuit
design engineer to select the appropriate Miniature Circuit Breaker/Manual Motor Controller for his specific application.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
AltechUL508
Characteristic Trip Boundaries
Applications
23
Application Examples:
Business equipment, wiring protection,
lighting, appliances, control circuits, some
motors and some electronic applications.
Relatively long thermal trip delay but low
magnetic trip point.
UL508 Listed
OnePole
StandardPack:12
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
TwoPole
StandardPack:6
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Rated Type/
Current Cat.No. Approvals
1.0A
1B1UM
1.6A
1B1.6UM
2.0A
1B2UM
2.5A
1B2.5UM
3.0A
1B3UM
3.5A
1B3.5UM
4.0A
1B4UM
5.0A
1B5UM
6.0A
1B6UM
8.0A
NA
10A
1B10UM
12A
NA
13A
1B13UM
15A
1B15UM
16A
1B16UM
20A
1B20UM
25A 1B25UM
30A
1B30UM
32A
1B32UM
40A
1B40UM
50A
1B50UM
60A
1B60UM
63A
1B63UM
Rated Type/
Current Cat.No. Approvals
1.0A
2B1UM
1.6A
2B1.6UM
2.0A
2B2UM
2.5A
2B2.5UM
3.0A
2B3UM
3.5A
2B3.5UM
4.0A
2B4UM
5.0A
2B5UM
6.0A
2B6UM
8.0A
NA
10A
2B10UM
12A
NA
13A
2B13UM
15A
2B15UM
16A
2B16UM
20A
2B20UM
25A 2B25UM
30A
2B30UM
32A
2B32UM
40A
2B40UM
50A
2B50UM
60A
2B60UM
63A
2B63UM
ThreePole
StandardPack:4
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Type/
Rating Cat.No. Approvals
0.3-63A/
N63UM
480Y/277V
StandardPack:5
Add-on
NeutralPole
Weight:
0.775kg (1.71lb.)
StandardDual
ConnectionTerminal
• Box clamp terminals
Top: 18-3 AWG;
Bottom: 18-2 AWG
(Line/Load reversible)
Ring
tongue
• Ring tongue terminals
Box
clamp
Dimensions*:
11.3 mm
(0.44 in.)
18.3 mm
(0.72 in.)
24
Rated Type/
Current Cat.No. Approvals
1.0A
3B1UM
1.6A
3B1.6UM
2.0A
3B2UM
2.5A
3B2.5UM
3.0A
3B3UM
3.5A
3B3.5UM
4.0A
3B4UM
5.0A
3B5UM
6.0A
3B6UM
8.0A
NA
10A
3B10UM
12A
NA
13A
3B13UM
15A
3B15UM
16A
3B16UM
20A
3B20UM
25A 3B25UM
30A
3B30UM
32A
3B32UM
40A
3B40UM
50A
3B50UM
60A
3B60UM
63A
3B63UM
max. 8-12 mm
(0.31-0.47 in.)
E137938
5.3 mm
(0.21 in.)
AltechUL508
B-Trip
Characteristic
M5 screw
* May differ by manufacturer.
Top terminal ring tongue
maximum thickness 1.6 mm.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
C-Trip
Characteristic
Application Examples:
Low inrush motors, lighting, wiring
protection, appliances, business
equipment, and control circuit
applications. Relatively long thermal trip
delay and medium magnetic trip point.
UL508 Listed
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
TwoPole
StandardPack:6
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Rated Type/
Current Cat.No. Approvals
0.3A
2C03UM
0.5A
2C05UM
0.75A
2C075UM
0.8A
NA
1.0A
2C1UM
1.6A
2C1.6UM
2.0A
2C2UM
2.5A
2C2.5UM
3.0A
2C3UM
3.5A
2C3.5UM
4.0A
2C4UM
5.0A
2C5UM
6.0A
2C6UM
8.0A
2C8UM
10A
2C10UM
12A
NA
13A
2C13UM
15A
2C15UM
16A
2C16UM
20A
2C20UM
25A 2C25UM
30A
2C30UM
32A
2C32UM
40A
2C40UM
50A
2C50UM
60A
2C60UM
63A
2C63UM
StandardPack:4
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Type/
Rating Cat.No. Approvals
0.3-63A/
N63UM
480Y/277V
StandardPack:5
Add-on
NeutralPole
Weight:
0.775kg (1.71lb.)
StandardDual
ConnectionTerminal
• Box clamp terminals
Top: 18-3 AWG;
Bottom: 18-2 AWG
(Line/Load reversible)
Ring
tongue
• Ring tongue terminals
Box
clamp
Dimensions*:
11.3 mm
(0.44 in.)
18.3 mm
(0.72 in.)
M5 screw
* May differ by manufacturer.
Top terminal ring tongue
maximum thickness 1.6 mm.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
AltechUL508
StandardPack:12
ThreePole
Rated Type/
Current Cat.No. Approvals
0.3A
3C03UM
0.5A
3C05UM
0.75A
3C075UM
0.8A
NA
1.0A
3C1UM
1.6A
3C1.6UM
2.0A
3C2UM
2.5A
3C2.5UM
3.0A
3C3UM
3.5A
3C3.5UM
4.0A
3C4UM
5.0A
3C5UM
6.0A
3C6UM
8.0A
3C8UM
10A
3C10UM
12A
NA
13A
3C13UM
15A
3C15UM
16A
3C16UM
20A
3C20UM
25A 3C25UM
30A
3C30UM
32A
3C32UM
40A
3C40UM
50A
3C50UM
60A
3C60UM
63A
3C63UM
max. 8-12 mm
(0.31-0.47 in.)
OnePole
Rated Type/
Current Cat.No. Approvals
0.3A
1C03UM
0.5A
1C05UM
0.75A
1C075UM
0.8A
NA
1.0A
1C1UM
1.6A
1C1.6UM
2.0A
1C2UM
2.5A
1C2.5UM
3.0A
1C3UM
3.5A
1C3.5UM
4.0A
1C4UM
5.0A
1C5UM
6.0A
1C6UM
8.0A
1C8UM
10A
1C10UM
12A
NA
13A
1C13UM
15A
1C15UM
16A
1C16UM
20A
1C20UM
25A 1C25UM
30A
1C30UM
32A
1C32UM
40A
1C40UM
50A
1C50UM
60A
1C60UM
63A
1C63UM
5.3 mm
(0.21 in.)
E137938
25
High inrush motors, transformers, power
supplies, heaters and reactive loads.
Relatively long thermal trip delay and very
high magnetic trip point.
UL508 Listed
OnePole
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
TwoPole
StandardPack:6
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Rated Type/
Current Cat.No. Approvals
0.3A
1D03UM
0.5A
1D05UM
0.75A
1D075UM
0.8A
NA
1.0A
1D1UM
1.6A
1D1.6UM
2.0A
1D2UM
2.5A
1D2.5UM
3.0A
1D3UM
3.5A
1D3.5UM
4.0A
1D4UM
5.0A
1D5UM
6.0A
1D6UM
8.0A
1D8UM
10A
1D10UM
12A
NA
13A
1D13UM
15A
1D15UM
16A
1D16UM
20A
1D20UM
25A 1D25UM
30A
1D30UM
32A
1D32UM
40A
1D40UM
50A
1D50UM
60A
1D60UM
63A
1D63UM
Rated Type/
Current Cat.No. Approvals
0.3A
2D03UM
0.5A
2D05UM
0.75A
2D075UM
0.8A
NA
1.0A
2D1UM
1.6A
2D1.6UM
2.0A
2D2UM
2.5A
2D2.5UM
3.0A
2D3UM
3.5A
2D3.5UM
4.0A
2D4UM
5.0A
2D5UM
6.0A
2D6UM
8.0A
2D8UM
10A
2D10UM
12A
NA
13A
2D13UM
15A
2D15UM
16A
2D16UM
20A
2D20UM
25A 2D25UM
30A
2D30UM
32A
2D32UM
40A
2D40UM
50A
2D50UM
60A
2D60UM
63A
2D63UM
ThreePole
StandardPack:4
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Rated Type/
Current Cat.No. Approvals
0.3A
3D03UM
0.5A
3D05UM
0.75A
3D075UM
0.8A
NA
1.0A
3D1UM
1.6A
3D1.6UM
2.0A
3D2UM
2.5A
3D2.5UM
3.0A
3D3UM
3.5A
3D3.5UM
4.0A
3D4UM
5.0A
3D5UM
6.0A
3D6UM
8.0A
3D8UM
10A
3D10UM
12A
NA
13A
3D13UM
15A
3D15UM
16A
3D16UM
20A
3D20UM
25A 3D25UM
30A
3D30UM
32A
3D32UM
40A
3D40UM
50A
3D50UM
60A
3D60UM
63A
3D63UM
Type/
Rating Cat.No. Approvals
0.3-63A/
N63UM
480Y/277V
StandardPack:5
Add-on
NeutralPole
Weight:
0.775kg (1.71lb.)
StandardDual
ConnectionTerminal
• Box clamp terminals
Top: 18-3 AWG;
Bottom: 18-2 AWG
(Line/Load reversible)
Ring
tongue
• Ring tongue terminals
Box
clamp
Dimensions*:
11.3 mm
(0.44 in.)
max. 8-12 mm
(0.31-0.47 in.)
E137938
StandardPack:12
26
Application Examples:
5.3 mm
(0.21 in.)
AltechUL508
D-Trip
Characteristic
18.3 mm
(0.72 in.)
M5 screw
* May differ by manufacturer.
Top terminal ring tongue
maximum thickness 1.6 mm.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
E-Trip
Characteristic
Application Examples:
High efficiency motors, which have
exceedingly high inrush currents.
Relatively short thermal trip delays and
very high magnetic trip points.
UL508 Listed
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
TwoPole
StandardPack:6
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Rated Type/
Current Cat.No. Approvals
0.3A
2E03UM
0.5A
2E05UM
0.75A
2E075UM
0.8A
NA
1.0A
2E1UM
1.6A
2E1.6UM
2.0A
2E2UM
2.5A
2E2.5UM
3.0A
2E3UM
3.5A
2E3.5UM
4.0A
2E4UM
5.0A
2E5UM
6.0A
2E6UM
8.0A
2E8UM
10A
2E10UM
12A
2E12UM
13A
2E13UM
15A
2E15UM
16A
2E16UM
20A
2E20UM
25A 2E25UM
30A
2E30UM
32A
2E32UM
40A
2E40UM
50A
2E50UM
60A
2E60UM
63A
2E63UM
StandardPack:4
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Type/
Rating Cat.No. Approvals
0.3-63A/
N63UM
480Y/277V
StandardPack:5
Add-on
NeutralPole
Weight:
0.775kg (1.71lb.)
StandardDual
ConnectionTerminal
• Box clamp terminals
Top: 18-3 AWG;
Bottom: 18-2 AWG
(Line/Load reversible)
Ring
tongue
• Ring tongue terminals
Box
clamp
Dimensions*:
11.3 mm
(0.44 in.)
18.3 mm
(0.72 in.)
M5 screw
* May differ by manufacturer.
Top terminal ring tongue
maximum thickness 1.6 mm.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
AltechUL508
StandardPack:12
ThreePole
Rated Type/
Current Cat.No. Approvals
0.3A
3E03UM
0.5A
3E05UM
0.75A
3E075UM
0.8A
NA
1.0A
3E1UM
1.6A
3E1.6UM
2.0A
3E2UM
2.5A
3E2.5UM
3.0A
3E3UM
3.5A
3E3.5UM
4.0A
3E4UM
5.0A
3E5UM
6.0A
3E6UM
8.0A
3E8UM
10A
3E10UM
12A
3E12UM
13A
3E13UM
15A
3E15UM
16A
3E16UM
20A
3E20UM
25A 3E25UM
30A
3E30UM
32A
3E32UM
40A
3E40UM
50A
3E50UM
60A
3E60UM
63A
3E63UM
max. 8-12 mm
(0.31-0.47 in.)
OnePole
Rated Type/
Current Cat.No. Approvals
0.3A
1E03UM
0.5A
1E05UM
0.75A
1E075UM
0.8A
NA
1.0A
1E1UM
1.6A
1E1.6UM
2.0A
1E2UM
2.5A
1E2.5UM
3.0A
1E3UM
3.5A
1E3.5UM
4.0A
1E4UM
5.0A
1E5UM
6.0A
1E6UM
8.0A
1E8UM
10A
1E10UM
12A
1E12UM
13A
1E13UM
15A
1E15UM
16A
1E16UM
20A
1E20UM
25A 1E25UM
30A
1E30UM
32A
1E32UM
40A
1E40UM
50A
1E50UM
60A
1E60UM
63A
1E63UM
5.3 mm
(0.21 in.)
E137938
27
General industrial, including motors, some
transformers, solenoids, control circuits,
lighting and wiring. Meets the US trip
norms with relatively short thermal trip
delay and high magnetic trip point.
UL508 Listed
StandardPack:12
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
TwoPole
StandardPack:6
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Rated Type/
Current Cat.No. Approvals
0.3A
1G03UM
0.5A
1G05UM
0.75A
NA
0.8A
1G08UM
1.0A
1G1UM
1.6A
1G1.6UM
2.0A
1G2UM
2.5A
1G2.5UM
3.0A
1G3UM
3.5A
1G3.5UM
4.0A
1G4UM
5.0A
1G5UM
6.0A
1G6UM
8.0A
1G8UM
10A
1G10UM
12A
1G12UM
13A
1G13UM
15A
1G15UM
16A
1G16UM
20A
1G20UM
25A 1G25UM
30A
1G30UM
32A
1G32UM
40A
1G40UM
50A
1G50UM
60A
1G60UM
63A
1G63UM
Rated Type/
Current Cat.No. Approvals
0.3A
2G03UM
0.5A
2G05UM
0.75A
NA
0.8A
2G08UM
1.0A
2G1UM
1.6A
2G1.6UM
2.0A
2G2UM
2.5A
2G2.5UM
3.0A
2G3UM
3.5A
2G3.5UM
4.0A
2G4UM
5.0A
2G5UM
6.0A
2G6UM
8.0A
2G8UM
10A
2G10UM
12A
2G12UM
13A
2G13UM
15A
2G15UM
16A
2G16UM
20A
2G20UM
25A 2G25UM
30A
2G30UM
32A
2G32UM
40A
2G40UM
50A
2G50UM
60A
2G60UM
63A
2G63UM
ThreePole
StandardPack:4
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Rated Type/
Current Cat.No. Approvals
0.3A
3G03UM
0.5A
3G05UM
0.75A
NA
0.8A
3G08UM
1.0A
3G1UM
1.6A
3G1.6UM
2.0A
3G2UM
2.5A
3G2.5UM
3.0A
3G3UM
3.5A
3G3.5UM
4.0A
3G4UM
5.0A
3G5UM
6.0A
3G6UM
8.0A
3G8UM
10A
3G10UM
12A
3G12UM
13A
3G13UM
15A
3G15UM
16A
3G16UM
20A
3G20UM
25A 3G25UM
30A
3G30UM
32A
3G32UM
40A
3G40UM
50A
3G50UM
60A
3G60UM
63A
3G63UM
Type/
Rating Cat.No. Approvals
0.3-63A/
N63UM
480Y/277V
StandardPack:5
Add-on
NeutralPole
Weight:
0.775kg (1.71lb.)
StandardDual
ConnectionTerminal
• Box clamp terminals
Top: 18-3 AWG;
Bottom: 18-2 AWG
(Line/Load reversible)
Ring
tongue
• Ring tongue terminals
Box
clamp
Dimensions*:
11.3 mm
(0.44 in.)
max. 8-12 mm
(0.31-0.47 in.)
E137938
OnePole
28
Application Examples:
5.3 mm
(0.21 in.)
AltechUL508
G-Trip
Characteristic
18.3 mm
(0.72 in.)
M5 screw
* May differ by manufacturer.
Top terminal ring tongue
maximum thickness 1.6 mm.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
StandardPack:12
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
TwoPole
StandardPack:6
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Rated Type/
Current Cat.No. Approvals
0.3A
1Z03UM
0.5A
1Z05UM
0.75A
1Z075UM
0.8A
NA
1.0A
1Z1UM
1.6A
1Z1.6UM
2.0A
1Z2UM
2.5A
1Z2.5UM
3.0A
1Z3UM
3.5A
1Z3.5UM
4.0A
1Z4UM
5.0A
1Z5UM
6.0A
1Z6UM
8.0A
1Z8UM
10A
1Z10UM
12A
1Z12UM
13A
1Z13UM
15A
1Z15UM
16A
1Z16UM
20A
1Z20UM
25A 1Z25UM
30A
1Z30UM
32A
1Z32UM
40A
1Z40UM
50A
1Z50UM
Rated Type/
Current Cat.No. Approvals
0.3A
2Z03UM
0.5A
2Z05UM
0.75A
2Z075UM
0.8A
NA
1.0A
2Z1UM
1.6A
2Z1.6UM
2.0A
2Z2UM
2.5A
2Z2.5UM
3.0A
2Z3UM
3.5A
2Z3.5UM
4.0A
2Z4UM
5.0A
2Z5UM
6.0A
2Z6UM
8.0A
2Z8UM
10A
2Z10UM
12A
2Z12UM
13A
2Z13UM
15A
2Z15UM
16A
2Z16UM
20A
2Z20UM
25A 2Z25UM
30A
2Z30UM
32A
2Z32UM
40A
2Z40UM
50A
2Z50UM
ThreePole
StandardPack:4
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Rated Type/
Current Cat.No. Approvals
0.3A
3Z03UM
0.5A
3Z05UM
0.75A
3Z075UM
0.8A
NA
1.0A
3Z1UM
1.6A
3Z1.6UM
2.0A
3Z2UM
2.5A
3Z2.5UM
3.0A
3Z3UM
3.5A
3Z3.5UM
4.0A
3Z4UM
5.0A
3Z5UM
6.0A
3Z6UM
8.0A
3Z8UM
10A
3Z10UM
12A
3Z12UM
13A
3Z13UM
15A
3Z15UM
16A
3Z16UM
20A
3Z20UM
25A 3Z25UM
30A
3Z30UM
32A
3Z32UM
40A
3Z40UM
50A
3Z50UM
Type/
Rating Cat.No. Approvals
0.3-63A/
N63UM
480Y/277V
StandardPack:5
Add-on
NeutralPole
Weight:
0.775kg (1.71lb.)
StandardDual
ConnectionTerminal
• Box clamp terminals
Top: 18-3 AWG;
Bottom: 18-2 AWG
(Line/Load reversible)
Ring
tongue
• Ring tongue terminals
Box
clamp
Dimensions*:
11.3 mm
(0.44 in.)
18.3 mm
(0.72 in.)
M5 screw
* May differ by manufacturer.
Top terminal ring tongue
maximum thickness 1.6 mm.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
AltechUL508
OnePole
Semiconductors, components which failshort (vs. fail-open), and
components/devices with low surgecurrent and short circuit withstand
capabilities. Relatively short thermal delay
and very low magnetic trip point.
max. 8-12 mm
(0.31-0.47 in.)
UL508 Listed
E137938
Application Examples:
5.3 mm
(0.21 in.)
Z-Trip
Characteristic
29
B Trip Curve
C Trip Curve
D Trip Curve
V-EA-B Trip
1.0A Through 10A Rated Current
V-EA-C Trip
0.3A Through 10A Rated Current
V-EA-D Trip
0.3A Through 10A Rated Current
1.13-1.45xIN
10
10
Tripping time t
1
1
4
1
10-1
4x10-2
4x10-2
10-2
4x10-3
10-2
3 4 5 6 8 10
20
40
100
1
Multiple of Rated Current
V-EA-B Trip
13A Through 63A Rated Current
20
40
10-2
4x10-3
10-3
100
Minutes
10
10
10
Seconds
10-2
4x10-3
4
1
0.4
2
3 4 5 6 8 10
20
40
100
Multiple of Rated Current
1
0.4
10-1
10-1
4x10-2
10-2
4x10-3
10-3
1
1
2
100
4
4x10-2
Seconds
1
Tripping time t
10
0.4
40
3 4 5 6 8 10
20
40
Multiple of Rated Current
“B”MagneticTripParameters
Rated current 1.0A to 63A.
“C”MagneticTripParameters
Rated current 0.3A to 63A.
1. Hold for a minimum of 100ms at
surge of 3 times rated current.
2. Trip in under 100ms at 5 times rated
current.
1. Hold for a minimum of 100ms at
surge of 5 times rated current.
2. Trip in under 100ms at 10 times
rated current.
100
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
4
10
4
3 4 5 6 8 10 16 20
1.13-1.45xIN
60
40
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
4
2
V-EA-D Trip
13A Through 63A Rated Current
1
10-3
1
Multiple of Rated Current
1
10-1
Seconds
1
0.4
1
Tripping time t
Minutes
Tripping time t
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
4x10-2
30
3 4 5 6 8 10
1.13-1.45xIN
60
40
60
40
4
2
V-EA-C Trip
13A Through 63A Rated Current
1.13-1.45xIN
10
4
Multiple of Rated Current
Minutes
2
10
10-1
4x10-3
10-3
1
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
4
4x10-2
Seconds
10-1
10
1
0.4
0.4
10-3
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
4
Minutes
10
1
4
60
40
Tripping time t
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
4
Minutes
10
1.13-1.45xIN
60
40
Seconds
Tripping time t
Minutes
1.13-1.45xIN
60
40
Seconds
AltechUL508
V-EATripCurves
10-2
4x10-3
10-3
1
2
3 4 5 6 8 10 16 20
40
Multiple of Rated Current
“D”MagneticTripParameters
Rated current 0.3A to 63A.
1. Hold for a minimum of 100ms at
surge of 10 times rated current.
2. Trip in under 100ms at 16 times
rated current.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
100
V-EATripCurves
E Trip Curve
G Trip Curve
V-EA-E Trip
0.3A Through 10A Rated Current
10
Thermal Overload
“Must Trip” = 125% Rated Current
“Must Not Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
“Must Not Trip” = Rated Current
4
1
1
0.4
10-1
10
Tripping time t
Tripping time t
4
60
40
Minutes
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
4
Minutes
4
1
0.4
10
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
4
1
40
20
10
4
1
0.4
10-1
4x10-2
10-1
Seconds
4x10-2
10-2
4x10-3
1
2
3 4 5 6 8 10 1418 20
40
4x10-2
10-2
Seconds
Minutes
10
10
Tripping time t
1.05-1.35xIN
1.05-1.35xIN
60
40
1
Seconds
V-EA-Z Trip
0.3A Through 10A Rated Current
V-EA-G Trip
0.3A Through 10A Rated Current
1.05-1.35xIN
60
40
10-3
Z Trip Curve
4x10-3
10-2
4x10-3
10-3
100
1
Multiple of Rated Current
E0.3A-E10A
2
3 4 5 6 8 10
20
40
100
10-3
Multiple of Rated Current
1
2
3 4 5 6 8 10
20
40
100
Multiple of Rated Current
V-EA-E Trip
12A Through 60A Rated Current
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
4
Thermal Overload
“Must Trip” = 125% Rated Current
“Must Not Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
“Must Not Trip” = Rated Current
4
1
4
1
0.4
10-1
4
1
0.4
10
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
4
1
10
Tripping time t
Tripping time t
10
10
4
1
0.4
10-1
10-1
Seconds
4x10-2
10-2
4x10-3
1
2
3
4 5 6
8 10 14 18 20
40
100
Multiple of Rated Current
4x10-2
10-2
4x10-3
10-2
4x10-3
10-3
1
2
3 4 5 6 8 10
20
40
Multiple of Rated Current
100
10-3
1
2
3 4 5 6 8 10
20
40
Multiple of Rated Current
“E”MagneticTripParameters
Rated Current, 0.3A to 50A,
60/63A (dotted line).
MagneticTrip:
1. Hold for a minimum of 100ms at
surge of 14 times (60A, 10
times) rated current.
2. Trip in under 100ms at 18 times
(60A, 14 times) rated current.
“G”MagneticTripParameters
Rated Current, 0.3A to 63A.
“Z”TripParameters
Rated Current, 0.3A to 50A.
MagneticTrip:
1. Hold for a minimum of 100ms at
surge of 8 times rated current.
2. Trip in under 100ms at 10 times
rated current.
MagneticTrip:
1. Hold for a minimum of 100ms at
2 times rated current.
2. Trip in under 100ms at 3 times
rated current.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
100
AltechUL508
4x10-2
Seconds
Tripping time t
10
60
40
Minutes
10
1
Seconds
1.05-1.35xIN
1.05-1.35xIN
60
40
Minutes
Minutes
1.05-1.35xIN
60
40
10-3
V-EA-Z Trip
12A Through 50A Rated Current
V-EA-G Trip
12A Through 63A Rated Current
31
AltechUL508
TableHP1:AMPERERATINGS&HORSEPOWERRATING1PHASE
FLA & LRC CONVERTED TO
TABLE HORSEPOWER (SEE NOTE #2)
USE FLA & LRC RATINGS WHERE
NO HP RATING IS GIVEN
NOMINAL CIRCUIT VOLTAGE
V-EA
RATED
MOTOR
NAMEPLATE
MOTOR
NAMEPLATE
CURRENT
(SEE NOTE #1)
FLA
RATING
STARTING/
LRC RATING
0.30A
0.50A
0.75A
0.80A
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10.0A
12.0A
12.5A
13.0A
15.0A
16.0A
20.0A
25.0A
30.0A
32.0A
40.0A
0.30A
0.50A
0.75A
0.80A
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10.0A
12.0A
12.5A
13.0A
15.0A
16.0A
20.0A
25.0A
30.0A
32.0A
40.0A
1.80A
3.00A
4.35A
4.8A
6.0A
9.6A
12.0A
15.0A
18.0A
21.0A
24.0A
30.0A
36.0A
48.0A
60.0A
72.0A
75.0A
78.0A
90.0A
96.0A
120.0A
150.0A
180.0A
192.0A
240.0A
50.0A
60.0A
50.0A
60.0A
300.0A
360.0A
110-120
VAC
200
VAC
208
VAC
1/6hp
1/4hp
1/3hp
1/6hp
1/6hp
1/4hp
1/4hp
1/3hp
1/2hp
3/4hp
1/6hp
1/6hp
1/4hp
1/3hp
1/2hp
1/2hp
3/4hp
1hp
11/2hp
2hp
2hp
2hp
3hp
1hp
11/2hp
11/2hp
11/2hp
2hp
2hp
3hp
3hp
3hp
3hp
5hp
3hp
5hp
71/2hp
10hp
1/2hp
1/2hp
1/2hp
1/2hp
3/4hp
220-240
VAC
265
VAC
277
VAC
1/6hp
1/6hp
1/4hp
1/4hp
1/3hp
1/2hp
1/2hp
1/6hp
1/6hp
1/4hp
1/3hp
1/3hp
1/2hp
3/4hp
1/6hp
1/4hp
1/3hp
1/3hp
1/3hp
1/2hp
3/4hp
1hp
11/2hp
11/2hp
11/2hp
2hp
2hp
3hp
3hp
3hp
5hp
71/2hp
1hp
11/2hp
2hp
2hp
2hp
2hp
2hp
3hp
3hp
5hp
5hp
71/2hp
1hp
11/2hp
2hp
2hp
2hp
3hp
3hp
3hp
5hp
5hp
5hp
71/2hp
1hp
2hp
2hp
2hp
2hp
3hp
3hp
3hp
5hp
5hp
5hp
71/2hp
10hp
10hp
10hp
10hp
10hp
10hp
10hp
15hp
NOTE #1: For AC motor circuit nameplate full load current, AC general-use loads, AC resistance loads, AC incandescent lamp (tungsten) loads,
AC electric discharge lamp (ballast) loads.
NOTE #2: Conversions per UL508® Table 45.2 and NFPA-70: National Electrical Code® 2008 Tables 430-248 and 430-251(A).
Table h P 2: a mPe r e r at in g & h o r s e Po We r r at in g 3 Ph a s e & 2 Ph a s e - 4 Wir e
FLA & LRC RATINGS CONVERTED TO TABLE HORSEPOWER (SEE NOTE #2)
USE FLA & LRC RATINGS WHERE NO HP IS LISTED
V-EA
RATED
CURRENT
(SEE NOTE #1)
0.30A
0.50A
0.75A
0.80A
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10.0A
12.0A
12.5A
13.0A
15.0A
16.0A
20.0A
25.0A
30.0A
32.0A
40.0A
50.0A
60.0A
MOTOR
NAMEPLATE
FLA
RATING
0.30A
0.50A
0.75A
0.80A
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10.0A
12.0A
12.5A
13.0A
15.0A
16.0A
20.0A
25.0A
30.0A
32.0A
40.0A
MOTOR
NAMEPLATE
STARTING/
LRC RATING
3.0A
5.0A
7.5A
8.0A
10.0A
16.0A
20.0A
25.0A
30.0A
35.0A
40.0A
42.0A
50.4A
67.2A
84.0A
100.8A
105.0A
109.2A
126.0A
134.4A
168.0A
210.0A
252.0A
268.8A
226.0A
50.0A
60.0A
282.5A
339.0A
110-120
VAC
Motor Design
B, C, D
E
200
VAC
Motor Design
B, C, D
E
208
VAC
Motor Design
B, C, D
E
220-240 VAC
(SEE NOTE #3)
Motor Design
B, C, D
E
1/2hp
1/2hp
1/2hp
3/4hp
3/4hp
440-480
VAC
Motor Design
B, C, D
E
1/2hp
3/4hp
1/2hp
3/4hp
1hp
11/2hp
2hp
2hp
3hp
3hp
5hp
5hp
71/2hp
71/2hp
71/2hp
10hp
10hp
10hp
15hp
20hp
20hp
20hp
25hp
30hp
1/2hp
1/2hp
1/2hp
3/4hp
1/2hp
1/2hp
1/2hp
3/4hp
1/2hp
1/2hp
3/4hp
3/4hp
1/2hp
1/2hp
3/4hp
3/4hp
1/2hp
1/2hp
1/2hp
3/4hp
3/4hp
1hp
1hp
2hp
2hp
3hp
3hp
3hp
3hp
3hp
5hp
5hp
5hp
5hp
71/2hp
1hp
1hp
2hp
2hp
3hp
3hp
3hp
3hp
3hp
5hp
71/2hp
71/2hp
10hp
10hp
1hp
1hp
2hp
2hp
3hp
3hp
3hp
3hp
3hp
5hp
71/2hp
71/2hp
10hp
71/2hp
1hp
11/2hp
2hp
3hp
3hp
3hp
3hp
3hp
5hp
5hp
71/2hp
10hp
10hp
10hp
1hp
11/2hp
2hp
3hp
3hp
3hp
3hp
3hp
5hp
5hp
71/2hp
10hp
10hp
10hp
1hp
11/2hp
2hp
2hp
3hp
3hp
5hp
5hp
71/2hp
71/2hp
71/2hp
10hp
10hp
10hp
15hp
20hp
20hp
30hp
10hp
10hp
15hp
20hp
10hp
10hp
15hp
20hp
10hp
15hp
30hp
40hp
1/2hp
1/2hp
3/4hp
1/2hp
1/2hp
3/4hp
1hp
11/2hp
11/2hp
11/2hp
2hp
2hp
3hp
3hp
5hp
5hp
5hp
1hp
11/2hp
11/2hp
11/2hp
2hp
2hp
3hp
3hp
5hp
5hp
5hp
1hp
1hp
2hp
2hp
3hp
3hp
3hp
3hp
3hp
5hp
5hp
5hp
5hp
10hp
71/2hp
10hp
71/2hp
10hp
15hp
15hp
NOTE #1: For AC motor circuit nameplate full load current, AC general-use loads, AC resistance loads, AC incandescent lamp (tungsten) loads,
AC electric discharge lamp (ballast) loads.
NOTE #2: Conversions per UL508® proposed Tables 45.2 and 45.4 and NFPA-70: National Electrical Code® 2008 Tables 430-249, 430-250 and 430-251B).
32
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
V-EAINTERNALRESISTANCE
TripCharacteristic
Rated Current B C D E G
(Amp) (Ohms) (Ohms) (Ohms) (Ohms) (Ohms)
Z
(Ohms)
0.3
0.5
0.75/0.8
1.0
1.6
2.0
2.5
3.0
3.5
4.0
5.0
6.0
8.0
10
12/12.5
13
15/16
20
25
30/32
40
50
60/63
31.5060
10.2460
5.3920
2.6910
0.9440
0.8900
0.4290
0.3460
0.1790
0.1620
0.1050
0.0823
0.0371
0.0278
0.0151
0.0151
0.0114
0.0075
0.0050
0.0032
0.0022
0.00195
—
—
—
—
—
—
—
—
—
—
—
—
0.0528
—
0.0216
—
0.0113
0.0085
0.0067
0.0050
0.0032
0.0025
0.0019
0.0018
16.8620
6.8540
3.0540
1.7000
0.5870
0.4190
0.2950
0.2020
0.1390
0.1090
0.0654
0.0528
0.0278
0.0216
—
0.0084
0.0085
0.0067
0.0050
0.0032
0.0025
0.0019
0.0018
16.8620
6.0009
3.0540
1.7560
0.5870
0.4190
0.2950
0.2020
0.1390
0.1090
0.0654
0.0491
0.0240
0.0187
—
0.0085
0.0076
0.0064
0.0041
0.0027
0.0022
0.0018
0.0017
14.52000
5.92000
2.70000
1.48000
0.57400
0.40500
0.26900
0.18600
0.13900
0.10600
0.05900
0.04600
0.03040
0.02020
0.00724
0.00724
0.00731
0.00582
0.00411
0.00272
0.00212
0.00184
0.00172
16.8620
6.8540
3.0540
1.7560
0.5870
0.4190
0.2950
0.2020
0.1390
0.1090
0.0654
0.0491
0.0333
0.0211
0.0084
0.0084
0.0076
0.0064
0.0046
0.0030
0.0022
0.0019
0.00179
Resistances listed are “hot” values, as
opposed to cold start values. Operating
voltage drop across the V-EA and power
loss per pole can be approximated with
basic formulas:
VDROP =IOPERATING xRTABLE
PLOSS P/P =I2OPERATING xRTABLE
Voltage drops should be reviewed when
V-EAs with high internal resistance are
used (e.g., load voltage minimums).
Power loss should be reviewed when
V-EAs with high rated currents are used
(e.g., enclosure heating).
The listed V-EA internal resistance
values should not be used in
calculations of available short-circuit
current downstream of the V-EA. The
dynamic impedance of the V-EA under
short-circuit conditions can vary
significantly from internal resistance
values in normal operation.
l in e c u r r e n t f r e Qu e n c Y e f f e c t s o n t r iP c u r v e s
Trip
TripZoneTripZone TripZone TripZone TripZone
CurveAt At At At At
162/3-60Hz 100Hz 200Hz400Hz DC
(xRC)(xRC) (xRC) (xRC) (xRC)
Z
B
C
G
D
E
2-3
3-5
5 - 10
8 - 10
10 - 16
14 - 18
2.2 - 3.3
3.3 - 5.5
5.5 - 11.0
8.8 - 11.0
11.0 - 17.6
15.4 - 19.8
2.4 - 3.6
3.6 - 6.0
6.0 - 12
9.6 - 12.0
12.0 - 19.2
16.8 - 21.6
2.8 - 4.2
4.2 - 7.0
7.0 - 14.0
11.2 - 14.0
14.0 - 22.4
19.6 - 25.2
3.0 - 4.5
4.5 - 7.5
7.5 - 15.0
12.0 - 15.0
15.0 - 24.0
21.0 - 27.0
The thermal trip is not affected by the frequency of the line
current. The magnetic trip is within the trip zone of the
characteristic curve for frequencies from 16 2/3 to 60Hz. At
lower and higher frequencies, the magnetic trip will be
delayed longer than indicated by the characteristic curve,
roughly as follows:
At100Hz:
At200Hz:
At400Hz:
AtDC:
Mag. Trip Current = 1.1 x curve current
Mag. Trip Current = 1.2 x curve current
Mag. Trip Current = 1.4 x curve current
Mag. Trip Current = 1.5 x curve current
For example, at 16 2/3 - 60 Hz the magnetic trip zone for
the “G” characteristic is 8 to 10 times the rated current of
the specific V-EA (i.e., hold for at least 100ms at 8 x RC,
trip in less than 100ms at 10 x RC). With a 400Hz current,
a magnetic trip at 10 x RC would be greatly delayed
(thermal would likely trip first), as the magnetic trip zone is
now 11.2 to 14 x RC. If a quicker magnetic trip is required
with 400Hz, the “B” or “C” characteristic should be
considered.
me c h a n ic a l e n d u r a n c e r at in g s (o n /o f f o Pe r at io n s )
Application
AC
AC
AC
AC
AC
General Use
Motor Starting Across the Line
Incandescent Lamps (Tungsten)
Electrical Discharge Lamps (Ballast)
Resistance
Manufacturersselfcertification
2x(1.15xRC)
2xRC
RC
NoLoad
Total
—
1000
—
—
—
6000
—
—
6000
6000
—
5000
6000
—
—
4000
4000
4000
4000
4000
10000
10000
10000
10000
10000
20000 ON/OFF operations with no load
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
AltechUL508
FrequencyEffectsonMagneticTripCurves
33