MAGNETROL 961-58A1-034

Echotel ® Models 960/961
Ultrasonic Level Switches
for Hygienic Applications
D E S C R I P T I O N
Echotel® Model 960/961 Ultrasonic Level Switches use
pulsed signal technology for superior performance in
difficult process conditions, and to provide excellent
immunity from sources of electrical noise interference.
Extensive self-testing of the electronics and transducer
make this advanced switch suitable for a wide variety of
hygienic level switch applications.
Model 960 Switches use AS-Interface® (AS-i) bus digital
communications for high or low single point liquid level
measurement. The AS-i bus system provides a digital serial
interface with a single unshielded two-wire cable for
power and data transfer.
Model 961 is offered with either a 5-amp relay or a current shift electronics. The relay output electronics has a
DPDT relay for level detection, and a SPDT malfunction
relay. The current shift version indicates 8 mA during normal operation, 16 mA as a level alarm condition and a
user-selectable 3.6 or 22 mA malfunction indication.
The 960/961 switches are designed for the stringent
requirements of hygienic applications. These switches are
offered with a deep-drawn 304 stainless steel housing that
is favorable to CIP and SIP procedures. A 20 Ra surface
finish is featured with hygienic Model 960/961 transducers.
These transducers are available with 11⁄2" & 2"
Tri-Clamp® fittings, and DN65 Varivent® Type N flanges.
Model 960/961
(with Varivent® fitting)
Model 960/961
(with Tri-Clamp® fitting)
A P P L I C A T I O N S
• High or low level alarm
• CIP buffer tanks
• WFI systems
• Hygienic pump protection
• Beer vats
• Leak detection
F E A T U R E S
• Self-test technology provides unsurpassed
reliability and testing of electronics, transducer,
piezoelectric crystals, and electromagnetic noise
• 20 Ra surface finish with Tri-Clamp and Varivent fittings
• Adjustable time delay for turbulent aerated liquids
• Tip-sensitive transducer measures level within 1⁄4" of
the vessel bottom
• Pulsed signal technology provides superior performance in difficult process conditions
• Liquid chromatography skids
• Overfill protection
I N D U S T R I E S
• Bio-technology
• Chemical
• Brewing and spirits
• Food and beverage
• Pharmaceutical
P U L S E D
S I G N A L
T E C H N O L O G Y
Model 960/961 switches use pulsed signal
technology to detect the presence or
absence of liquid in an ultrasonic transducer gap. The transducer uses a pair of
piezoelectric crystals that vibrate at a
given frequency when subjected to an applied voltage.
The transmit crystal converts the applied voltage from the
electronics into an ultrasonic signal. When liquid is present
in the gap, the receive crystal senses the ultrasonic signal
and converts it back into an electrical signal. This signal is
sent to the electronics to indicate a wet gap condition.
When no liquid is present, the ultrasonic signal is attenuated and is not detected by the receive crystal.
Ultrasonic
transducer
Transmit
crystal
Challenging process conditions like aeration, suspended
solids, and high viscosities are overcome by using pulsed signal circuitry in 960/961 switches. Unlike many tuning forks,
pulsed signal ultrasonic switches do not need to be configured for different media densities, making these units the
most universally applied level switches on the markey today.
ADVANCED
SELF-TEST
Ultrasonic switches are often used as the
last means of detecting whether a
cer
Transdu ls
ta
process vessel will overflow and cause a
s
& cry
s
ic
spill of potentially hazardous liquids, or
Electron
e
empty out and possibly cavitate the
Nois
pumps. In these critical applications it is
desirable to have a method of periodically testing the
ultrasonic switch to ensure that it is functioning properly.
Receive
crystal
Ultrasonic signal transmission
across transducer gap
AND
DIAGNOSTICS
A microprocessor in the 960/961 electronics continuously
monitors all self-test data. Should a fault occur, the microprocessor can determine whether the malfunction is due
to the electronics, transducer, piezoelectric crystals, or the
presence of environmental noise. A pushbutton and Fault
LED is used to assist in troubleshooting the switch:
5 One flash of the Fault LED indicates a problem
with the transducer or piezoelectric crystals
Model 960/961 switches feature an advanced self-test
technology that not only tests the electronics, transducer,
and piezoelectric crystals, but also tests for the presence
of industrial sources of environmental noise. Should the
switch detect any problems a malfunction output is generated to alarm the user, and a red LED is lit to indicate
an alarm condition.
ADJUSTABLE
TIME
problem with one of the electronics boards
555 Three flashes of the Fault LED indicates
excessive levels of environmental noise
DELAY
Turbulence and splashing can cause
some fixed time response switches to
produce false level alarms. Model
960/961 switches overcome this difficulty
with an adjustable time delay feature.
2
55 Two flashes of the Fault LED indicates a
A potentiometer allows a 1⁄2 – 45-second delay to be set to
disregard waves or splashes, and reliably detect the true
liquid level.
A P P L I C A T I O N S
Model 960/961 Switches may be used for high or low
level alarm, empty pipe detection and pump protection in
Spray Ball
Fill Line
High Alarm
a wide variety of hygienic applications. Available with a
304 stainless steel electronics housing and a 20 Ra surface
finish transducer, typical applications include:
• CIP/SIP day tank point level
• Water for Injection (WFI) storage
• Liquid chromatography skids
Pump
Protection
• Brewery fill lines
• Condensate receiver tanks
Low Alarm
A G E N C Y
A P P R O V A L S
AGENCY
APPROVED MODELS
PROTECTION METHOD
FM & CSA
960-58AX-030
960-58AX-031
961-50AX-010
961-50AX-011
961-XDAX-030 or
961-XDAX-031
with transducers:
9X1-XXXX-XXX
Explosion Proof
960-58AX-074
960-58AX-075
961-XXAX-01X
961-XXAX-03X or
961-XXAX-07X
with transducers:
9X1-XXXX-XXX
Non-Incendive
961-50AX-01X
with transducers:
9X1-XXXX-XXX
Intrinsically Safe
960-58AX-0C0
960-58AX-0C1
961-XXAX-0C0
961-XXAX-0C1
with all metallic
transducers*
Flameproof
Ex II 1/2 G, EEx d IIC T6
961-50AX-0A0
961-50AX-0A1
with all metallic
transducers*
Intrinsically Safe
Ex II 1 G, EEx ia IIC T5
ATEX
AS-i
AREA CLASSIFICATION
Class I, Div. 1, Groups B, C, & D
Class II, Div. 1, Groups E, F, & G
Class III, Type 4X, IP 66, T6
Class I, Div. 2, Groups A, B, C, & D
Class II, Div. 2, Groups F & G
Class III, Type 4X, IP 66, T4
IP67 for 304 Stainless Steel Housing
Class I, Div. 1, Groups A, B, C, & D
Class II, Div. 1, Groups E, F, & G
Class III, Type 4X, IP 66, T4
These units have been tested to AS-Interface Specification
EN50295 and IEC 62026-2, and have met the demands of the
AS-Interface Test Requirements. AS-Interface certificate #76401
*Consult factory for model numbers
These units have been tested to EN 61326 and are
in compliance with the EMC Directive 89/336/EEC.
3
E L E C T R O N I C S
M O D E L
9 6 0
Supply Voltage
AS-i Version
AS-i Slave Type
AS-i Slave Profile
AS-i Data Bits
W I T H
S P E C I F I C A T I O N S
A S - I n t e r f a c e
Connectable Load
21 to 31 VDC
V 3.0
A/B (Maximum of 62 nodes)
S-0.A.E
D2 = 1 with a wet gap
D2 = 0 with a dry gap
D3 = 1 during malfunction
D3 = 0 in normal state
EN50295 and IEC 62026-2
Power Consumption
Less than 1 watt
Gap Condition:
Malfunction Status:
Ambient Temperature
Storage Temperature
M O D E L
9 6 1
Supply Voltage
Relay Outputs
Relay Ratings
Electronics:
Electronics:
W I T H
R E L A Y
DPDT:
SPDT:
Fail-safe
Power Consumption
Ambient Temperature
M O D E L
9 6 1
W I T H
T R A N S D U C E R
4
18 to 32 VDC, or 102 to 265 VAC, 50/60 Hz
One DPDT level relay and one SPDT malfunction relay
5 amps @ 120 VAC, 250 VAC, and 30 VDC, 0.4 amp @ 110 VDC
5 amps @ 120 VAC, 250 VAC, and 30 VDC, 0.15 amp @ 125 VDC
Selectable for high or low level
Less than 3 watts
-40° to +160° F (-40° to +70° C)
S H I F T
O U T P U T
11 to 35 VDC
8 mA normal operation, 16 mA level alarm (±1 mA)
3.6 mA or 22 mA selectable fault signal (±1 mA)
104 ohms with 11 VDC input, 1100 ohms with 35 VDC input
Selectable for high or low level
Less than 1 watt
-40° to +160° F (-40° to +70° C)
Loop Resistance
Fail-safe
Power Consumption
Ambient Temperature
Operating Frequency
Surface Finish
O U T P U T
C U R R E N T
Supply Voltage
Current Shift Output
Operating Temperature
Maximum Pressure
-13° to +160° F (-25° to +70° C)
-40° to +160° F (-40° to +70° C)
S P E C I F I C A T I O N S
1" and 2":
3" to 130":
-40° to +325° F (-40° to +163° C)
2000 psi (138 bar)
1500 psi (103 bar)
2 MHz
20 Ra (when ordered with 4th digit code S)
P E R F O R M A N C E
Repeatability
Response Time
Time Delay
Self-Test
Automatic:
Manual:
Shock Class
Vibration Class
Humidity
Electromagnetic Compatibility
P H Y S I C A L
S P E C I F I C A T I O N S
±0.078" (± 2 mm)
1
⁄2 second typical
Variable 0.5 – 45 seconds on rising and falling levels
Continuously verifies operation of electronics, transducer,
piezoelectric crystals, and electrical noise
Push button verifies operation of electronics, transducer,
and piezoelectric crystals
ANSI/ISA-S71.03 Class SA1
ANSI/ISA-S71.03 Class VC2
0-99%, non-condensing
Meets CE requirements EN 61326
S P E C I F I C A T I O N S
Housing Material
Cable Entry
Cast Aluminum:
304 Stainless Steel:
Cast aluminum A356-T6, or deep drawn 304 stainless steel
Dual 3⁄4" NPT, or M20
Dual 1⁄2" NPT, or M20
D I M E N S I O N A L
I N C H E S
S P E C I F I C A T I O N S
( m m )
5.24
(133)
4.00
(102)
4.43 (113)
5.24
(133)
5.75
(146)
5.75
(146)
1.80 (46) Typical
1.05 (26)
Typical
2.70 (69)
Typical
Actuation length
with NPT connection
Actuation length
with Tri-Clamp fitting
Actuation length
with Varivent fitting
0.25 (6)
∅ .875 (22)
∅ .875 (22)
0.25 (6)
Model 960/961
with NPT Connection
0.25 (6)
∅ .875 (22)
Model 960/961
with Tri-Clamp® fitting
Model 960/961
with DN65 Varivent® Flange
5
M O D E L
9 6 0 / 9 6 1
N U M B E R
E L E C T R O N I C S
Models available for quick shipment, usually within one week after factory
receipt of a complete purchase order, through the Expedite Ship Plan (ESP)
BASIC MODEL NUMBER
960
961
Actuator-Sensor-Interface (AS-i) electronics
Relay or current shift electronics
INPUT POWER
2
5
7
24 VDC line-powered (Model 961 only)
24 VDC loop-powered (Model 960 & 961)
102 to 265 VAC line-powered (Model 961 only)
OUTPUT SIGNAL
0
8
D
mA current shift for Model 961 (available with Input Power code 5)
Actuator-Sensor-Interface (AS-i) for Model 960 (available with Input Power code 5)
5 amp gold flash relays for Model 961 (available with Input Power codes 2 or 7)
COVER
0
1
Standard cover
Glass window cover
MOUNTING
0
Integral
AGENCY APPROVAL
1
3
7
A
C
FM/CSA Intrinsically safe, Non-Incendive
& Explosion Proof * (use with current shift
Output Signal code 0)
FM/CSA Explosion Proof & Non-Incendive
(use with Output Signal code 8 & D,
and Housing codes 0, 1)
FM/CSA Non-incendive (available with Output Signal
codes 0, 8 & D and Housing codes 4 & 5)
ATEX II 1G EEx ia IIC T5, Intrinsically safe (available
with Output Signal code 0 and Housing codes 0 &1)
ATEX II 1/2G EEx d IIC T6, Flameproof
(available with Output Signal codes 0, 8 & D,
and Housing codes 0 & 1))
* Explosion Proof approvals not available with housing codes 4 & 5
HOUSING & CONDUIT CONNECTION
0
1
4
5
9
6
6
A
0
Cast aluminum with 3⁄4" NPT dual conduit entries
Cast aluminum with M20 dual conduit entries
Deep drawn 304 stainless steel
w/ 1⁄2" NPT dual conduit entries
Deep drawn 304 stainless steel
w/M20 dual conduit entries
M O D E L
9 6 0 / 9 6 1
N U M B E R
S I N G L E
P O I N T
T R A N S D U C E R
Models available for quick shipment, usually within one week after factory
receipt of a complete purchase order, through the Expedite Ship Plan (ESP)
TRANSDUCER UNIT OF LENGTH
A
M
English (length in inches)
Metric (length in centimeters)
MATERIALS OF CONSTRUCTION
A
S
316/316L stainless steel
316/316L with 20 Ra hygienic finish (use only with Process Connection codes 3T, 4T, or VV)
PROCESS CONNECTIONS
11
3T
4T
VV
3
⁄4" NPT
11⁄2" Tri-Clamp® 16 AMP fitting
2" Tri-Clamp® 16 AMP fitting
DN65 – Varivent® Type N flange
ACTUATION LENGTH (unit of length specified in second digit)
1" to 130" in 1" increments
1" minimum for NPT process connections
2" minimum for 3T, 4T & VV process connections
Example: 4 inches = 004
Available English ESP lengths: 1", 2", 4", 6", 8", 12"
3 cm to 330 cm in 1 cm increments
3 cm minimum for NPT process connections
5 cm minimum for 3T, 4T & VV process connections
Example: 6 centimeters = 006
Available metric ESP lengths: 3, 5, 10, 30 cm
9
1
A
7
Q U A L I T Y
The quality assurance system in place at
Magnetrol® guarantees the highest level of
quality throughout the company. MAGNETROL
is committed to providing full customer
satisfaction both in quality products and
quality service.
The MAGNETROL quality assurance system is
registered to ISO 9001 affirming its commitment
to known international quality standards
providing the strongest assurance of product
and service quality available.
Several ECHOTEL Model 961 units are available
for quick shipment, usually within one week
after factory receipt of a complete purchase
order, through the Expedite Ship Plan (ESP).
ESP service may not apply to orders of ten
units or more. Contact your local representative for lead times on larger volume orders, as
well as other products and options.
E S P
Expedite
Ship
Plan
To take advantage of ESP, simply match the
color coded model number codes (standard
dimensions apply).
W A R R A N T Y
All MAGNETROL electronic level and flow
controls are warranted free of defects in materials or workmanship for one full year from
the date of original factory shipment.
If returned within the warranty period; and,
upon factory inspection of the control, the
cause of the claim is determined to be covered
under the warranty; then, MAGNETROL will
repair or replace the control at no cost to the
purchaser (or owner) other than transportation.
MAGNETROL shall not be liable for misapplication, labor claims, direct or consequential damage or expense arising from the
installation or use of equipment. There are
no other warranties expressed or implied,
except special written warranties covering
some MAGNETROL products.
For additional information, see Instruction Manuals 51-632 & 51-646.
5300 Belmont Road • Downers Grove, Illinois 60515-4499 • 630-969-4000 • Fax 630-969-9489 • www.magnetrol.com
145 Jardin Drive, Units 1 & 2 • Concord, Ontario Canada L4K 1X7 • 905-738-9600 • Fax 905-738-1306
Heikensstraat 6 • B 9240 Zele, Belgium • 052 45.11.11 • Fax 052 45.09.93
Regent Business Ctr., Jubilee Rd. • Burgess Hill, Sussex RH15 9TL U.K. • 01444-871313 • Fax 01444-871317
Copyright © 2011 Magnetrol International, Incorporated. All rights reserved. Printed in the USA.
Performance specifications are effective with date of issue and are subject to change without notice.
Magnetrol, Magnetrol logotype and Echotel are registered trademarks of Magnetrol International, Incorporated.
AS-Interface® is a registered trademark of the AS-International Association
Kynar® is a registered trademark of Elf Atochem North America, Inc.
Hastelloy® is a registered trademark of HAYNES INTERNATIONAL, INC. (DELAWARE CORPORATION)
Monel® is a registered trademark of the INCO family of companies
Tri-Clamp® is a registered trademark of Ladish Co.
Varivent® is a registered trademark of Tuchenhagen GmbH LTD
BULLETIN: 51-160.2
EFFECTIVE: August 2011
SUPERSEDES: October 2009