ETC VX1500P

JAGUAR VX
Torque Vector System
Sensorless Vector Variable Frequency Inverters
- 0.4kW to 280kW
■ High performance, Torque Vector Control
■ Up to 250% torque at 1Hz
■ Low torque ripple at low speed
■ Fast torque response - 200mS, 0 - 100% load
■ Load speed regulation < 1% open loop
■ User friendly self tuning to motor
■ Ultra compact IP20 enclose (≤ 22kW)
■ Dual LED/LCD plain English display
■ User programmable I/O
■ Low motor noise profile
■ Auto energy saving function
■ Renowned IMO 5 year warranty
5
Specifications
JAGUAR VX ORDER CODES
VX40
VX75
VX150
VX220
VX400
VX550
VX750
VX1100
VX1500
VX1850
VX2200
JAGUAR VXP ORDER CODES
-
-
-
-
-
-
MOTOR RATING (kW)
0.4
0.75
1.5
2.2
4
5.5
7.5
11
15
18.5
22
RATED O/P CURRENT (A)
1.5
2.5
3.7
5.5
9
13
18
24
30
39
45
100% RATED I/P CURRENT RMS
1.7
2.9
5.5
7.7
12.6
18.2
24.4
36.3
48.5
59
72
45
50
65
85
110
140
200
315
340
450
510
VX750P VX1100P VX1500P VX1850P VX2200P
(AT 400V)*
HEAT LOSS (W)
(AT 2 KHz CARRIER FREQUENCY)
INPUT VOLTAGE/FREQUENCY
3 PHASE
380 TO 415V (+10%,-15%)
50/60 Hz (+5%,-5%)
WEIGHT (Kg)
2.4
3.2
3.2
3.2
3.2
6.5
5.3/6.5
10.6/6.5
INPUT POWER FACTOR**
0.96
0.95
0.94
0.93
0.94
0.95
0.95
0.95
OUTPUT VOLTAGE FREQUENCY
3 PHASE
JAGUAR VX ORDER CODES
VX30K
VX37K
JAGUAR VXP ORDER CODES
VX30KP VX37KP
VX45K
0 - V INPUT
VX55K
VX75K
VX45KP VX55KP VX75KP
VX90K
10.6/11.5 10.6/11.5
0.94
0.95
10.6/12
0.96
0.2 - 400 Hz (‘P’ MODELS 0.2 - 120 Hz)
VX110K VX132K VX160K VX200K VX220K
VX90KP VX110KP VX132KP VX160KP VX200KP VX220KP VX280KP
MOTOR RATING (kW)
30
37
45
55
75
90
110
132
160
200
220
280
RATED O/P CURRENT (A)
60
75
91
112
150
176
210
253
304
377
415
520
100% RATED I/P CURRENT RMS
58
71
85
104
141
168
203
243
293
363
400
508
1200
1400
1600
1900
2300
2700
3000
3400
4000
4600
5000
6000
(AT 400V)*
HEAT LOSS (W)
(AT 2 KHz CARRIER FREQUENCY)
INPUT VOLTAGE/FREQUENCY
WEIGHT (Kg)
INPUT POWER FACTOR**
OUTPUT VOLTAGE FREQUENCY
NOTES *
**
3 PHASE
380 TO 415V (+10%,-15%)
50/60 Hz (+5%,-5%)
36
36/37
37/44
45/54
54/61
61/88
88
88/120
120/125
125/177
177
177
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
3 PHASE
0 - V INPUT
0.2 - 400 Hz (‘P’ MODELS 0.2 - 120 Hz)
FIGURES FOR INPUT ARE QUOTED WHEN USING A DC REACTOR FROM VX30K AND VX30KP UP, NO REACTOR < 30KW
AT 100% FULL LOAD CURRENT AND USING DC REACTOR
PRICE
INFORMATION
AND ORDERING
Jaguar VX
Basic circuit configuration and terminals
WARNING! INVERTER MUST
BE EARTHED
Braking resistor (option)
for all inverters.
DC Bus reactor
(Optional ≤22kW)
P(+)
Terminal Markings
Markingsfor
forDC
DC
* Terminal
reactor and
and Braking
Braking
bus reactor
Resistor for
or Braking
Resistor
Braking Unit
The marking
marking of
of these
these
The
terminals varies
varies between
between
terminals
different
sizes
of
JaguarVX
VX
different sizes of Jaguar
inverter. Please refer to
inverter.
Please
refer
to
pages 19, 20 and 21 for
manual
specific details.
specific for
detail.
DB
GND
(PE)
GND
(PE)
Link P1 to (*)
if DC reactor
not required
Input
contactor
On-board braking IGBT and resistor applicable
only to VX40 to VX750 and VX750P to VX1100P.
Disconnect the internal resistor (R) before
connecting an external resistor.
N(-)
*
*
*
2
0V Braking unit (option).
Applicable to VX1100, VX1500P, VX30K
1
24V and inverters larger than these.
BU
P(+)
P1
RTS = Volt-free NC contact
for thermal protection.
RTS
R
L1
3-phase
power
supply
50Hz or
60Hz
U
V
W
L2
Note (1)
L3
Analog voltage
frequency ref.
input
(Pot. 1kΩ, 1W)
4-20mA
analog input
Programmable
analog
output
(13)
(12)
(11)
+10V DC
(C1)
+ve
250Ω
(FMA)
(FMP)
(CM)
Digital
output
Power
charge
LED
‘CRG’
SMPS
Z
0V A/D +24V DC
GND
(PE)
Current
detection
Gate
drive
Voltage
detection
Connect via
RF filter (if fitted)
Note (2)
DC voltage
detection
M
Earth busbar
at MCC
Keypad Panel
Keys
0 to 10V DC
Pulse output
0V
(V1) Note (3)
(FWD) 4.7kΩ
CPU
LED, LCD
displays
Frequency
command
switch
PWM
generator
Accel /
Decel
regulator
Autovoltage
regulator
Function
generator
Torque
vector
calculator
PRICE
INFORMATION
AND ORDERING
(REV) 4.7kΩ
BU
RTS
(THR) 4.7kΩ
1 2
(HLD) 4.7kΩ
(X1) 4.7kΩ
Input
signal
CPU
A/D
Protective
logic
(AX1) Run
relay
(AX2) output Note (3)
(X2) 4.7kΩ
Control
inputs
(30C) Trip
(30B) relay
(30A) output
(X3) 4.7kΩ
(X4) 4.7kΩ
(Y1E)
(X5) 4.7kΩ
(Y2E)
(BX) 4.7kΩ
Output
signal
(Y3E)
(RST) 4.7kΩ
(P24) or (CMS)
Note (6)
(Y4E)
0V
(Y5E)
+24V DC
(CMC)
0V
NOTES (1)
(2)
(3)
(4)
(5)
(6)
Programmable
outputs
(P24) or (CMS) Note (6)
(CM) Note (4)
For inverters rated ≤22kW the inrush contactor is replaced by an SCR. 0V Common Terminals (11) and
Voltage detection circuit applicable for inverters ≥30kW only.
(CM) are optically isolated.
Standard for inverters ≥30kW, optional for smaller models.
Relay status shown as at inverter
Two terminals (CM) standard for inverters ≤22kW, one for ≥30kW.
‘power ON’ or ‘healthy’.
If motor thermistors are required, please consult IMO.
Internal +24V DC supply terminal designated P24 (≤22kW) or CMS (≥30kW).
Jaguar VX
Control circuit connections
Purpose
Analog
frequency
setting
Terminal
Meter
outputs
Programmable
outputs
Relay
outputs
Description
11
Speed reference 0V common
For use with terminals 12, 13 and C1 (and V1, ≥30kW only)
12
Potentiometer input
Maximum speed demand is at +10V with a 0V to +10V DC
input. Input impedance 20kΩ (≤22kW), 22kΩ (≥30kW).
13
Potentiometer supply
Regulated +10V DC power supply for 1kΩ min. speed control
potentiometer. Input 10mA max.
C1
Current loop input
Maximum speed demand is at 20mA with a 4-20mA DC
input, impedance 250Ω. Inverter output frequency is
proportional to current input signal, zero speed = 4mA.
V1*
Auxiliary freq. reference
Bipolar 0V to ±10V input.
CM†
0V common
0V common terminals for general use.
FWD
Forward and STOP command
REV
Reverse and STOP command
If FWD and
FWD-P24 closed: Motor runs forward
open: Motor decelerates to rest REV are both
closed or both
open, inverter
REV-P24 closed: Motor runs in reverse
open: Motor decelerates to rest output STOPS.
HLD
FWD/REV command hold
HLD-P24 closed: Latches momentary FWD or REV inputs
open: FWD/REV non-latching
Coast-to-stop command
BX-P24
THR
External Trip/Alarm input
THR-P24 closed: Normal
open: Trip (OH2) inverter output instantaneously
RST
Trip/Alarm RESET
BX
Programmable
inputs
Terminal Name
closed: Inhibit inverter output instantaneously
open: Normal
If RST-P24 closed for ≥100ms, inverter internal fault trips are
reset, and also alarm 30A/B/C (see below).
X1
Programmable input 1
X2
Programmable input 2
X3
Programmable input 3
Preset speeds or mains-to-inverter changeover
X4
Programmable input 4
Preset acc/dec command. LOC/REM changeover.
DC injection brake command.
X5
Programmable input 5
Preset acc/dec times. 2nd motor V/F ratio. Data protection
enable/disable.
P24
P24
+24V DC power supply
Preset speeds or motorised potentiometer
24V current source for programmable I/O terminals and for
FWD, REV, HLD, BX, THR, RST and X1 to X5.
Output frequency, current, torque or load factor can be
selected. 0V to +10V DC at 2mA max. (Min. impedance 5kΩ)
Pulse output proportional to inverter output frequency. Pulse
frequency 6 to 100 x O/P Hz at +10V DC (adjustable).
FMA
Analog meter
FMP
Pulse frequency meter
CMC
Open-collector common
Y1E
Programmable output 1
Y2E
Programmable output 2
Y3E
Programmable output 3
Y4E
Programmable output 4
Y5E
Programmable output 5
Y2E FAR
Y3E FDT
30A
30B
30C
Normally open
Normally closed
Common
Relay changes state when an internal protection function is
active and when the inverter trips.
Contact: 250V AC, capacity 0.5A, cosφ 0.3
Run relay
Relay closes when inverter is running
Contact: 250V AC, capacity 0.5A, cosφ 0.3
AX1*
AX2*
Output:
27V DC,
Up to 16 different outputs can be programmed
50mA per
from the operating Functions representative of O/P channel,
total 50mA
dynamic operating conditions.
maximum.
Factory defaults:
Caution
Y1E Inverter running
0V
* Standard for ≥30kW only, optional for ≤22kW.
Y4E Overload early warning
Y5E Undervoltage
Read Technical
Manual before
use.
† Two CM terminals for ≤22kW, one for ≥30kW.
PRICE
INFORMATION
AND ORDERING
Jaguar VX
Parameter list/function code table
Group
No.
Name
LCD Display
Setting range
Basic
Functions
00
Frequency command
00 FREQ COMND 0 = KEYPAD, ∧ or ∨ keys
1 = TERMINAL, 0 to +10V
2 = TERMINAL, 4 to 20mA
—
—
0
01
Operating mode
01 OPR METHOD
0 = KEYPAD, RUN/STOP keys
1 = TERMINAL, (FWD) & (REV)
—
—
0
02
Max. O/P frequency
02 MAX Hz
VX, 50-400Hz VX…P, 50-120Hz
Hz
1
50
03
Base freq., motor 1
03 BASE Hz -1
VX, 50-400Hz VX…P, 50-120Hz
Hz
1
50
04
Max. O/P V, motor 1
04 RATED V -1
0 = Output dependent on supply V*
320 to 480 = output V
V
1
400
05
Accel. time, motor 1
05 ACC TIME 1
0.01 to 3600
s
0.01
6.00
06
Decel. time, motor 1
06 DEC TIME 1
0.00 = ramp inhibit, or 0.01 to 3600
s
0.01
6.00
07
Torque boost, motor 1
07 TRQ BOOST 1
0.0 = auto; 0.1 to 20.0 fixed boost
—
0.1
0.0
[0.1]
08
Electronic thermal
O/L, type
08 ELECTRN OL
0 = Inactive
1 = Active for standard motor
2 = Active for inverter-rated motor
—
—
1
09
Electronic O/L, level
09 OL LEVEL
20% to 105% of inverter rating
A
0.01
†
10
Restart after
momentary power
supply failure
10 RESTART
0 = Inactive 1
1 = Inactive 2
2 = Active, smooth recovery
3 = Active, restart at set Hz
4 = Active, restart at start Hz
—
—
3
11
O/P freq. HI limit
11 H LIMITER
VX, 0-400Hz VX…P, 0-120Hz
Hz
1
70
12
O/P freq. LO limit
12 L LIMITER
VX, 0-400Hz VX…P, 0-120Hz
Hz
1
0
13
Min. O/P freq. (bias)
13 FREQ BIAS
VX, 0-400Hz VX…P, 0-120Hz
Hz
1
0
14
Freq. I/P ref. gain
14 FREQ GAIN
0.0 to 200.0%
%
0.1
100.0
15
Driving torque limit
15 DRV TORQUE
20 to 180, 999% (999 = no limit)
%
1
150
[120]
16
Braking torque limit
16 BRK TORQUE
0, 20 to 180, 999% (999 = no limit)
%
1
100
[100]
17
DC inj. brk. Start frequ. 17 DC BRK Hz
0.0 to 60.0Hz
Hz
0.1
0.0
18
DC inj. brk. Brkg. level 18 DC BRK LVL
0.0 to 100%
%
0.1
0.0
19
DC inj. brk. Brkg. time 19 DC BRK t
0.0 (brake inactive), or 0.1 to 30.0s
s
0.1
0.0
20
to
26
Pre-set multistep
frequencies 1 to 7
20 MULTI Hz -1
to
26 MULTI Hz -7
VX
0.00, 0.20 to 400.0Hz
VX…P 0.00, 0.20 to 120.0Hz
(0.00 = preset disabled)
Hz
0.01
0.00
27
Intl. electronic thermal
O/L for intl. brkg. R
27 DBR OL
0 = Inactive
1 = Active for intl. R, invrs. ≤7.5kW
2 = Inactive
—
—
1 [0]
28
Slip compensation
28 SLIP COMP
-9.9Hz to +5.0Hz
Hz
0.1
0.0
29
Torque vector control
29 TRQ VECTOR
0 = Inactive 1 = Active
—
0
30
Number of motor poles 30 MTR POLES
2
4
2 to 14 (even nos. only)
Unit Resol.
—
Def.
Functions marked by heavy outlines can be set whilst the inverter is running. DEF = factory-set defaults. Resol = resolution.
Default values are for all inverters. Where VX…P defaults differ, they are shown in square brackets […].
* LCD display shows 0V
† Approx. rated current for inverter-rated motors
PRICE
INFORMATION
AND ORDERING
Jaguar VX
Parameter list/function code table (continued)
Group
No.
31
31
Function Block 32 to 41 31 • 32—41 •
0 = Functions 32 to 41 hidden
1 = Functions 32 to 41 displayed
—
—
0
Prog. I/P
terminals
32
Select the functions of
terminals X1 to X5
32 X1-X5 FUNC
0000 to 2222
—
—
0000
Acc./Dec. 33
times
34
35
36
37
38
Accel time 2
Decel time 2
Accel time 3
Decel time 3
Accel time 4
Decel time 4
3X ACC TIME X
0.00 = Ramp inhibited, coasting
0.01 to 3600s
s
0.01
10.00
10.00
15.00
15.00
3.00
3.00
2nd
motor
39
Base freq., motor 2
39 BASE Hz -2
VX, 50-400Hz VX…P, 50-120Hz
Hz
1
50
40
Max. O/P V, motor 2
40 RATED V -2
0 = Output dependent on supply V*
320 to 480 = output V
V
1
400
41
Torque boost, motor 2
41 TRQ BOOST 2
0.1 to 20.0 fixed boost
—
0.1
2.0
42
Function Block 43 to 51 42 • 43—51 •
0 = Functions 43 to 51 hidden
1 = Functions 43 to 51 displayed
—
—
0
43
FMP terminal, pulse
rate multiplier
43 FMP PULSES
x6 to x100
—
1
x24
44
Voltage O/P adjustmt.
44 FMP V-ADJ
50% to 120%
%
1
100%
45
FMA terminal, voltage
adjustment
45 FMA V-ADJ
65% to 200%
%
1
100%
46
FMA terminal function 46 FMA FUNC
0 = O/P freq.
2 = O/P torque
—
—
0
47
Select the functions of
terminals Y1E to Y5E
47 Y1-Y5 FUNC
00000 to FFFFF
—
—
01234
48
FAR function (‘At
Speed’ window)
48 FAR HYSTR
0.0 to 10.0Hz
Hz
0.1
2.5
49
FDT function (level)
49 FDT LEVEL
VX, 0-400Hz VX…P, 0-120Hz
Hz
1
50
50
FDT function (hyster.)
50 FDT HYSTR
0.0 to 30.0Hz
Hz
0.1
1.0
51
O/L alarm (level)
51 OL WARNING
Approx. 20 to 105% inverter rated
current
A
0.01
†
52
Function Block 53 to 59 52 • 53—59 •
0 = Functions 53 to 59 hidden
1 = Functions 53 to 59 displayed
—
—
0
Frequency 53
control
54
Skip frequency 1
53 JUMP Hz 1
VX, 0-400Hz VX…P, 0-120Hz
Hz
1
0
Skip frequency 2
54 JUMP Hz 2
VX, 0-400Hz VX…P, 0-120Hz
Hz
1
0
55
Skip frequency 3
55 JUMP Hz 3
VX, 0-400Hz VX…P, 0-120Hz
Hz
1
0
56
Skip hysteresis
56 JUMP HYSTR
0 to 30Hz
Hz
1
3
57
Starting frequency
57 START Hz
0.2Hz to 60.0Hz
Hz
0.1
0.5
58
Holding time
58 HOLDING t
0.0 to 10.0s
s
0.1
0.0
59
Frequency I/P
reference filter
59 FILTER
0.01 to 5.00s
s
0.01
0.05
42
Digital
O/P
Analog
O/P
O/P term.
functions
52
Name
LCD Display
Setting range
1 = O/P current
3 = %FLT
Unit Resol.
Def.
Functions marked by heavy outlines can be set whilst the inverter is running. DEF = factory-set defaults. Resol = resolution.
Default values are for all inverters. Where VX…P defaults differ, they are shown in square brackets […].
* LCD display shows 0V
† Approx. rated current for inverter-rated motors
PRICE
INFORMATION
AND ORDERING
Jaguar VX
Parameter list/function code table (continued)
Group
No.
60
60
Function Block 61 to 79 60 • 61—79 •
0 = Functions 61 to 79 hidden
1 = Functions 61 to 79 displayed
—
—
0
61
LEDs, function for
normal display
61 LED MNTR 1
0 to 8
—
—
0
62
LEDs display at STOP
62 LED MNTR 2
0 = Set point (flashing)
1 = Actual output value only
—
—
0
63
Coefficient for machine 63 SPEED COEF
speed and line speed
0.01 to 200.00 x Hz output
—
0.01
0.01
64
LCD display function
64 LCD MNTR
0 to 3: Drive status, standard screen
or bar graphs
—
—
0
Pattern operation,
mode select
65 PATTERN
0 to 3: Inactive or cyclic
—
—
0
66 Pattern stages 1 to 7
to
72
6X STAGE X
Operation time 0.00 to 6000s
FWD/REV codes F1 to F4
ACC/DEC codes R1 to R4
s
0.01
0.00
F1
73
ACC/DEC mode
73 ACC PTN
0 to 2: linear, S-curve, non-linear
—
—
0
74
Series brake motor
driving
74 SERIES BRK
75
Energy saving
75 ENERGY SAV
0 = Inactive 1 = Active
—
—
0 [1]
76
REV phase sequ. lock
76 REV LOCK
0 = Inactive 1 = Active
—
—
0
77
Data initialising (data
reset)
77 DATA INIT
0 = Inactive 1 = Active
—
—
0
78
Language of displays
78 LANGUAGE
0 to 3
—
—
1
79
LCD display
brightness
79 BRIGHTNESS
0 (bright) to 10 (dark)
—
—
5
80
80
Function Block 81 to 94 80 • 81—94 •
0 = Functions 81 to 94 hidden
1 = Functions 81 to 94 displayed
—
—
0
Special
Functions
2
81
PWM carrier frequency 81 MTR SOUND
(motor sound)
0 (low) to 10 (high) carrier
frequency
—
—
10
82
Auto-restart, start delay 82 RESTART 1
0.0 to 5.0s
s
0.1
0.1
83
Auto-restart, freq. fall
rate
83 FALL RATE
0.00 to 100.00
Hz/s
1
10
84
Auto-reset, number of
restarts
84 AUTO RESET
0 to 7
—
—
0
85
Auto-reset, interval
85 RESET INT
2 to 20s
s
—
5
86
Motor 1, frame size
86 MOTOR CAP
0 = 1 higher 1 = nominal
2 = 1 lower 3 = 2 lower
—
—
1
87
Motor 1, rated current
87 MOTOR 1-Ir
0.00 to 2000A
A
0.1
†
88
Motor 1, no-load current
88 MOTOR 1-Io
0.00 to 2000A
A
0.1
†
89
Motor 2, rated current
89 MOTOR 2-Ir
0.00 to 2000A
A
0.1
†
90
Motor 1, tuning
90 TUNING
0 = Inactive 1 = Active
—
—
0
91
Motor 1, %R1 value
91 %R1 SET
0.00 to 50.00%
%
0.01
†
92
Motor 1, %X value
92 %X SET
0.00 to 50.00%
%
0.01
†
93
93 DD FUNC 1
94
Manufacturer’s use
only
95
Data security
95 DATA PRTC
—
—
0
LED &
LCD
displays
65
Pattern
operations
Special
Functions
1
Motor
characteristics
Special
Functions
3
Name
LCD Display
Setting range
Unit Resol.
Not available
0 = GERMAN, 1 = ENGLISH
2 = SPANISH, 3 = ITALIAN
Def.
—
94 DD FUNC 2
0 = Unlocked
1 = Data secure
Jaguar VX
Dimensions (mm) 0.4 to 280kW
Jaguar VX40
Jaguar VX550, VX750, and VX750P, VX1100P
130
110
96
7
97
12
10
KEYPAD OPERATION
KEYPAD OPERATION
Hz
Hz
r/min
r/min
%
PRG
FUNC
DATA
A
%
A
m/min
m/min
V
V
PRG
RUN
RESET
195
220
196
37
6
260
STOP
RESET
RUN
FUNC
DATA
260
STOP
238
246
10
6
87
7
Jaguar VX75 to VX400
162
10
Jaguar VX1100 to VX2200 and VX1500P to VX2200P
145
150
136
52
7
195
250
226
6
96
12
10
KEYPAD OPERATION
Hz
r/min
A
%
m/min
V
KEYPAD OPERATION
Hz
r/min
%
A
m/min
V
PRG
RESET
RUN
FUNC
DATA
260
STOP
PRG
246
RESET
RUN
FUNC
DATA
400
STOP
378
6
102
7
10
*N.B. JAGUAR VX inverters are designed
for use within shielded steel enclosures
162
10
78
68
KEYPAD OPERATION
Hz
r/min
%
A
m/min
V
PRICE
INFORMATION
AND ORDERING
REMOTE MOUNTING
KEYPAD WITH OPTIONAL
2M CONNECTOR CABLE
125
STOP
115
PRG
RESET
RUN
FUNC
DATA
STOP
Keypad panel
mounting dimensions.
Common to all modules.
Jaguar VX30K to VX220K, VX30KP to VX280KP
W
W1
D
D1
2 holes
dmm diam.
CHARGE
KEYPAD OPERATION
Hz
r/min
%
A
m/min
V
PRG
RESET
H
RUN
FUNC
DATA
H1
STOP
H2
d
Side vents on
inverters from
VX30K to VX75K
and VX30KP to
VX90KP only
VX
30K-D
30KP-D
37KP-D
37K-D
45KP-D
45K-D
55KP-D
55K-D
75KP-D
75K D
90KP-D
90K-D
110KP-D
110K-D
132KP-D
132K-D
160KP-D
160K-D
200KP-D
200K-D
220KP-D
220K D 280KP-D
W
W1
H
H1
H2
D
D1
d
340
240
550
530
500
290
185
10
340
240
550
530
500
290
185
10
375
275
550
530
500
290
185
10
375
275
675
655
625
275
170
10
530
430
675
645
610
290
185
15
530
430
740
710
675
300
180
15
530
430
740
710
675
330
205
15
530
430
740
710
675
330
205
15
530
430 1000 970
935
435
295
15
530
430 1000 970
935
435
295
15
680
580 1000 980 N/A 435
320 N/A
680
580 1000 980 N/A 435
320 N/A
Jaguar VX
Optional accessories
Accessor y
Function
Filters
A specially designed range of easily fitted low profile ‘footprint’ filters up to
22kW and stand alone filters up to 280kW are available to provide maximum
RF reduction. See page 363 for details.
Function Copy Unit
Saves and loads stored set-ups for up to 12 complete function sets. ‘Copy
Edit’, ‘verify’ and ‘write-protected’ modes available. Operates from an 85V to
265V AC supply. Target or donor drives do not need to be powered up to
transfer data.
Encoder Feedback Module
Enables Jaguar VX inverters to be operated in closed-loop control mode.
Speed control range 180 to 3600 rpm. Speed variation ±0.2% at 3600 rpm.
Encoder output, 20 to 2000 pulses per revolution.
Relay Output Module
Converts programmable outputs Y1E . . . Y5E to relay outputs.
Contact rating 0.3A at 250V AC, cosØ = 0.3.
PID Control Mode Unit
Digitally adjustable P, I and D terms through the medium of a
supplementary function menu.
Reference input 0V to 10V DC
Feedback input 0V to 10V DC or 4-20mA DC.
Synchronisation Module
Provides a multi-synch tasking capability via rotary encoders for
Master/Slave and ‘Follower’ applications.
Serial Communication Module
RS422 or RS485, multi-drop up to 31 Jaguar VX inverters of all sizes. Optoisolated.
FieldBus Modules
Dedicated FieldBus units which allow the connection of multiple
Jaguar VX inverters to a site standard FieldBus link.
FieldBus systems available:
Modbus Plus
Interbus S
Profibus DP
DeviceNet
Regenerative Brake Units
Provides additional braking for high inertia loads for inverters 11kW to
280kW. (Units below 11kW have regenerative braking capability built in as
standard).
Pod Extension Cable
Allows the Jaguar VX keypad to be removed and mounted separately.
PRICE
INFORMATION
AND ORDERING