FUJI EDSX11-140A

COMPACT CONTROLLER M [CC-M]
(PROGRAMMABLE STEP OUTPUT TYPE)
Digital Controller
DATA SHEET
PDC
The Compact Controller M (programmable step output type)
is a single-loop process controller.
It accepts 1 to 5 V DC and signals from thermocouples and
resistance bulb as input, and is provided with abundant control and computation functions to allow configuring a flexible system with a high cost performance.
FEATURES
1. Control and computation functions dependent on wafers
Control and computation functions are implemented by
combining function-software packages called "WAFERS."
Since the WAFERS are built in the controller, optimum
system can be programmed by using the front-panel keys
and the PC based configurator.
2. High visibility ensured with color graphic display
A color LCD is adopted for graphic display of multi-loop
bar graph and trend screens,etc.
3. Communication function (option)
RS-485 (Modbus® protocol or OPTO22 interface®) are
available.
4. Memory card (option)
Memory card can save any data, for example process input, WAFER output, etc.
SPECIFICATIONS
1. Control and Computation Functions
Control and computation functions are implemented by
combining function-software packages called "WAFERS."
Combination of WAFERS is called "WAFER connection."
CC-M comprises 100 kinds of WAFERS.
WAFER connection is made by operating the keys on the
front panel or using the PC based configurator.
(1) PID control
• Number of loops and PID:
1 loop (1 control output / 2PID)
• Proportional band (P):
1.0 to 3276.7%, set at 3000.0% for delivery
• Integration time (I):
0.1 to 3276.7 s, set at 3000.0 s for delivery
• Derivative time (D):
0.0 to 900.0 s, set at 0.0 s for delivery
(2) Programming function
• Programming method:
WAFER connection
• Program capacity:
48 WAFERS
• Kind of wafer : 100 kinds listed in Table 1
(3) Computation cycle:
200 ms
(4) Alarm function
• Method
: Alarm can be displayed and output
through WAFER connection.
• Kinds
: Each high/low of PV, SV and MV, PV
change rate alarm, MV change rate
alarm, high/low deviations.
EDSX11-140a
Date
Jan. 11, 2002
PDC
2. Input Signals
Performance under reference condition(23± 2˚C,
55± 10%RH, Power voltage and frequency variation ± 1%,
free from the effect of external noise) unless otherwise
specified.
2-1 Analog input signal
• Number of inputs:
8 inputs
• Inpute signal types:
DC voltage, thermocouple (option), resistance bulb (option)
Two thermocouple inputs or two resistance bulb inputs are selectable.
(1) DC voltage/DC current
• Input range: Selectable among 0 to 5 V
DC, 1 to 5 V DC and 0 to 10 V DC
Initial set before delivery : 1 to 5 V DC
• Input accuracy: ± 0.1% of input span± 1
digit
• Scaling (Engineering data conversion):
Settable within a range from -32767 to
32767
4, 3, 2, 1 or 0 digit below decimal point
is selectable.
Initial set before delivery : 0.00% to
100.00%
• Engineering unit: Settable in up to 8
characters
Usable characters: Alphabets numerals,
symbols such as +, – ,*,etc.
• Input accuracy guarantee range: –5%
to 105% of input range.
• Maximum continuous permissible
voltage: ± 35 V
• Input resistance: 1 MΩ or more
• Influence by ambient temperature:
± 0.1% FS/10°C or less.
• Influence by power supply fluctuation:
± 0.1% FS or less.
• Isolation: Non-isolated from internal circuit.
• In case of current input:
Shunt resistor need to be connected to
the analog input terminal.
(250 Ω shunt resistor is optional item)
(2) Thermocouple (option)
• Types and measurable ranges:
* See Table 2.
• Input accuracy: ± 0.2% FS ± 1 digit
[Note]B type: ± 5% between 0 to 400˚C
S and R type: ±1%between 0 to 500˚C
All type of TC: ± 5% under–100˚C
• Reference junction compensation error:
± 1.0°C (provided measurable range is
–50°C and higher)
[Note]Reference junction compensation resistor is connected at external
input terminal in case of thermocouple input is ordered.
• Input accuracy guarantee range:
–5% to 105% of input range.
• Input resistance: 1 MΩ or more
• Allowable signal source resistance:
100 Ω or less (Zener barrier connection
unallowable)
2
• Influence by signal source resistance:
About 0.25 µV/Ω
• Influence by ambient temperature:
± 0.2% FS/10°C ± 1°C or less.
• Influence by power supply fluctuation:
± 0.2% FS ± 1˚C or less
• Burnout detection: Provided
• Isolation: Isolated from internal circuit.
(3) Resistance bulb (option)
• Types and measurable ranges:
* See Table 2.
• Input accuracy: ± 0.2% FS ± 1 digit
• Input accuracy guarantee range:
-5% to 105% of input range
• Allowable wiring resistance: 10Ω or
less per wire, provided wiring resistance must be equal among 3 wires (Zener barrier connection unallowable)
• Influence by ambient temperature: ± 0.2% FS/10˚C or less.
• Influence by power supply fluctuation: ± 0.2% FS or less
• Burnout detection: Provided
• Isolation: Isolated from internal circuit.
[Note] FS: full span.
• Sampling period:
100 ms
2-2 Digital input signal
• Number of inputs:
10 inputs
• Electrical specifications:
No-voltage contact or transistor contact
ON/0 V, OFF/24 V, ON current/about 8
mA
Isolated from the internal circuit by
photocoupler. Not isolated between
each digital input and output.
• Contact rating: 30 V DC, 10 mA or more
• Signal judgment:
No-voltage contact
Contact resistance;
200 Ω or less at ON,
100 kΩ or more at OFF
Transistor contact
1V max at ON.,
leakage current 100µA max. at
OFF
3. Output Signals
Performance under reference condition(23± 2˚C,
55± 10%RH, Power voltage and frequency variation ± 1%,
free from the effect of external noise) unless otherwise
specified.
3-1 Analog output signal
(1) Auxiliary analog output
• Number of outputs:
4 outputs
• Types of signal : Selectable among 0 to 5 V DC, 1 to 5 V
DC and 0 to 10 V DC
Initial set before delivery: 1 to 5 V DC
• Output accuracy:
± 0.1% FS
• Load resistance:
15 kΩ or more
• Output guarantee range:
• 1 to 5 VDC : –12.5% to 112.5%
• 0 to 5 VDC : 0% to 112.5%
• 0 to 10VDC : 0% to 105%
• Influence by power supply fluctuation:
± 0.1% FS or less
• Isolation
: Non-isolated from internal circuit
3-2 Control output signal
• Number of outputs:
1 output
Increasing pulse; DO1
Decreasing pulse; DO2
• Electrical specifications:
Transistor open collector
1 V max. at ON, 10 µA max at OFF.
Isolated from the internal circuit by
photocoupler. Not isolated between
each digital input and output.
• Output rating : 30 V DC, 100 mA max. (resistive load)
[Note] Control outputs should be crossed sequentially
by an external sequence so that the increasing and
decreasing pulse signals are not turned to ON at the
same time.
3-3 Digital output signal
• Number of outputs:
8 outputs
• Electrical specifications:
Transistor open collector
1 V max. at ON, 10 µA max at OFF.
Isolated from the internal circuit by
photocoupler. Not isolated between
each digital input and output.
• Output rating : 30 V DC, 100 mA max. (resistive load)
3-4 Fault output signal (terminal symbol FLT)
• Number of outputs:
1 output
• Electrical specifications:
Transistor open collector
1 V max. at ON, 10 µA max at OFF.
Isolated from the internal circuit by
photocoupler. Not isolated between
each digital input and output.
• Output rating : 30 V DC, 100 mA max. (resistive load)
4. Display
• Display unit
: 16 Colors graphic liquid crystal display,
with CFL back light and contrast adjust
function.
• Contents of display:
• Menu
• Loop panel
Bar graph display, digital display, etc.
• Tuning screen
• Trend screen (max. 8 screens)
• Alarm and alarm historical screen
• Analog input/output and digital input/
output indication screen
• WAFER connection screen
• Parameter setting screen
5. Setting and Operation
(1) Set point setting method
• Setting key
: Up key/down key
• Setting speed : About 40 s/FS
• Setting resolution:
0.05% FS/each key press
(2) Control output operation method
• Operation key : Up key, down key
• Operation speed:
About 40 s/FS (usual),
(3) Operation mode
• Kinds of operation mode:
C, A, and M
[Note] C: Cascade mode (operation according to remote set point)
A: Auto mode (operation according to the local
set point)
M: Manual mode (control output to be manually
operated by operator)
• Changeover : Balance bumpless changeover from
Auto to Cascade
Balanceless bumpless in other
changeover
[Note] Balance bumpless changeover is a method
where each setting value needs to be balanced by
operator himself at the time of changeover.
Balanceless bumpless changeover is a method
where each setting value is automatically balanced
by the controller at the time of changeover.
(4) Security
• Method
: Setting of a password
• Password
: Settable in 4 numerals (within 0000 to
ffff)
Initial set before delivery: 0000
• Contents of security:
Inhibition of parameter setting
(5) Other setting items
• Tag name
: Settable in up to 8 characters
Usable characters; alphabes, numerals,
symboles such as +, – ,*,etc.
6. Power Supply
• Voltage rating : 100 V to 240 V AC/24 V DC
• Allowable range:
85 V to 264 V AC/20 V to 30 V DC
• Frequency
: 47 to 63 Hz
• Power consumption:
60 VA or less (100 V to 240 V AC)/
30 W or less (24 V DC)
• Power supply output voltage:
(terminal symbol VP and PC)
20V to 30V DC,max. 40mA
3
PDC
7. General performance and characteristics
• Insulation resistance:
500 V DC, 50 MΩ or more.
• Dielectric strength:
• 2,000 V AC for 1 minute between
power terminal and ground terminal in
case of 100 V to 240 V AC power supply
• 500 V AC for 1 minute between power
terminal and ground terminal in case of
24 V DC power supply.
• 500 V AC for 1 minute between signal
communication terminals and ground
terminal
• Rush current : 60 A or less. (100 V AC to 240 V AC
power supply)
• Clock
: Set and display year, month, day, hour,
minute, second
Accuracy : ± 100 ppm except of time lag
shorter than 1 s / power ON / OFF action.
• Memory backup:
• Protection by lithium battery.
(expected battery life is about 2 years
under room temperature)
• Parameter and program are stored in
non-volatile memory.
8. Operating and storage conditions
• Operating temperature:
0 to 50˚C
0 to 40°C in case of multiple mounting
(Temperature change rate: Max. 10˚C / h)
• Transport and storage temperature:
-20 to 70˚C
(Temperature change rate: Max. 20˚C / h)
• Operating humidity:
5 to 90% RH, condensation unallowable
• Transport and storage humidity:
5 to 95% RH, condensation unallowable
• Operating continuous vibration:
4.9 m/s2 or less
• Transport and storage shock:
Fall of 60cm max. in packed status
9. Power Failure and restart Function
• Permissible duration of momentary power failure:
20 ms at 90V AC (100 V to 240 V AC
only)
[Note] In case of 24 V DC, system power supply unit
(model: PXJ) is recommended to avoid power failure
problem.
• Behavior at power failure detection:
Control stops at detection of power failure.
• Power recovery mode:
Selectable initial start and continuous
start
4
10. Self-Diagnosis
• Control and computation circuit failure:
Monitoring with watchdog timer
• Input signal failure:
• Voltage/current input
Monitoring of range over
• Thermocouple and resistance bulb
Monitoring of disconection
• Behavior at failure:
: FLT is indicated, FLT lamp lights, FLT
output signal turns on, control stops and
control output is held.
11. Structure
• Enclosure
: Plastic (material: PC-ABS)
• Finish color
: Front frame and enclosure both gray
• Flame resistance:
UL94V-0
• Protection
: Front face; IP54 (display unit and operation key)
• External dimensions (W x H x D):
72 x 144 x 280 mm
• Mass
: 1.9 kg or less
• Mounting method:
Flush on indoor panel
Vertical mounting as standard
Tilted mounting allowed within backward angle 0° to 45°.
90° to 45°
For panel cutout dimension, refer to
Panel Cutout Dimensions
• External terminal:
Compression terminal type
12. Communications (option)
12-1 RS485 interface-1
• Communication behavior:
Slave
• Communication protocol:
Modbus® protocol
• Physical specification:
EIA RS-485
• Communication method:
Half-duplex, bit serial
Start-stop synchronizing
• Connection form:
Multi-drop
• Communication speed:
19.2 kbps
• Communication distance:
Max. 500 m in total
• Number of connectable units:
Max. 31 units
• Data length
: Fixed to 8 bits
• Parity
: Odd / Even / None
• Stop bit
: 1 or 2
• Isolation
: Isolated from internal circuit
• Terminator
: 100 Ω (optional item)
• Communication items:
Parameters and process value.
• RS232C / RS485 signal converter (optional item):
Code symbol: PDZT0001
12-2 RS485 interface-2
• Communication behavior:
Master
• Usage
: I/O extension
Analog input / output : Max.4
Digital input / output : Max.32
• Communication protocol:
OPTO22 interface®
• Physical specification:
EIA RS485
• Communication method:
Half-duplex, bit serial
Start-stop synchronizing
• Communication speed:
57.6 kbps
• Communication distance:
Max.50m in total
• Number of connectable units:
Max.31 units
[Note] Number of units is limited depend on the number of I/O points.
• Isolation
: Isolated from internal circuit
• Terminator
: 100 Ω (optional item)
• Communication item:
Parameters, process values,etc.
• Connectable slave unit:
SNAP I/O series® (OPTO22 corporation)
13. Memory Card Interface (option)
• Specification : Compact Flash® (Based on CFA)
• Compatible memory card:
5 V flash memory card
Capacity 4, 20 and 32 MB
• Application
: Process data logging (32 points or less)
• Saving period : 1s to 2h
• Data storage capacity:
Memory card
capacity
Data storge
4MB
about 180 thousand data
20MB
about 900 thousand data
32MB
about 1.35 million data
[Note] The data of max. 16 points (4 screens) can be
storaged at storage time as 1 s.
• Format method:
Dependent on this controller
• Data readout : Readout by PC using PCMCIA card slot
• Recommended memory card:
Made by Sandisk corporation
Sandisk compact Flash memory card is
standardized and on the market.
14. Standards under Conformity
(1) General safety:
IEC 1010-1 (1990)
EN 61010-1 (1993)
(2) EMC
: Emission EN 50081-2 (1994)
Immunity EN 50082-2 (1995)
15. Configuration Software (optional item)
15-1 Programming loader software
(code symbol : PDZP2001)
• WAFER connection can be entered, edited, uploaded and
downloaded.
• Operation parameter can be entered, edited, uploaded
and downloaded.
15-2 Recommended personal computer system
• Hardware
: DOS/V machine, Pentium 100MHz or
higher
Free hard disk capacity 40MB or more,
memory capacity 32MB or more
• Operating system:
Windows 95
15-3 Cable (code symbol : PDZL1001)
Using the configuration software, the configuration file is
downloaded via RS232C transmission cable.
5
PDC
Table 1
List of WAFERS
WAFER name
Primary PID
Kinds
Outline
9
Carries out computation on the
primary loop.
Secondary PID
4
Carries out computation on the
secondary loop.
2
Gain schedule
Outputs the PID parameter
corresponding to input 1 according
to the gain schedule table.
8
Bit concatevate
Outputs digital data as word data to
an external expansion I/O.
1
Bit slicing
Slices the digital data acquired as
word data from an external
expansion I/O into each bit.
1
Encoder
Encodes an input signal into
a binary code.
1
Sawtooth wave generator
Generates a sawtooth wave with
a slope entered for each
cycle time.
5
BCD
Converts BCD data into binary data
and binary data into BCD data.
6
Logical operation
Carries out AND,OR,NOT,XOR
and a combination of these logical
operations.
8
Carries out a combination of
Arithmetic operation
addition,subtraction,multiplication
and division.
Carries out temperature and
1
Temperature/pressure
pressure compensation through use
compensation
of differential pressure,compensated
pressure,proper temperature.
Linearize
7
Carries out segmented-line
approximation with 15-segmentedline function.
4
Time schedule control by step or
Program control
polygonal line approximation with
7 segments.
Flip-flop
1
RS flip-flop.
Pulse width integration
1
Adds the change of input at each
basic cycle to the previous
integration value.
Selector
Compares two input values,and
1
provides High output(Large one),
Low output(Small one),and result
of judgement on large/small.
Selects input or output via a switch
Changeover
1
function.Analog hold circuit also
provided.
Outputs on-delay,off-delay timer
Timer
1
signal via start of input signal
according to timer setting.
1
Carries out absolute value processing
Absolute value/sign
on input and outputs the result.Also
inversion
judges the sign(Positive,negative)of
input value and outputs the result.
6
WAFER name
Square root extraction
Lead,lag
Limiter
Ramp function
Analog averaging
Analog integration
Pulse generation
Dead band
Pulse No.counter
Pulse No.output
Decoder
Running average
Sample & hold
Dead time
ON-OFF
Alarm
Palse width modurator
Indicator
Kinds
Outline
Extracts square root of input value
1
and outputs the result.Low input
cutoff function equipped.
Carries out lead/lag operation on the
3
input and outputs the results.
Used as analog filter function and
for various compensations.
Limits the input within the range of
1
high/low limit settings,and outputs
the result.Also outputs high/low
limit alarm signal.
Outputs signal which changes...in
2
ramp from toward target value at
the set full scale time.There are two
of these wafers...in minute unit and
hour unit.
Carries out sequential integration on
1
input data,calculates the average
value at each averaging time,
and otuputs the result.
Integrates the value obtained by
1
multiplying the input data by
a proportional constant,and outputs
the result.
Outputs a pulse at the set time
1
interval.
Adds dead band compensation to
1
the input and outputs the result.
Detects rise of pulse and counts the
1
number of pulses.
Integrates the input signal and
1
converts it to number of pulses
for output.
Decodes 2-bit pure binary input and
1
outputs it to 4 terminals.
Calculates ranning average of input
2
data and outputs the result.
Holds the input value according to
1
sample signal(0/1)and continues
the output.
Usable for dead time compensation
6
control etc.Data sampling can be
done in 1 sec or 1 min units.
Outputs ON-OFF signal with
1
hysteresis.
Compares the input and set value
1
and outputs the judgment result.
1
Performs output processing in time
proportional PID control.
Indicate input data on the front
8
display (using 3 bar-graph display)
A variety of applications are possible through combination of WAFERS.
Table 2
SCOPE OF DELIVERY
List of Thermocouple and Resistance Bulb Measurable
range
Input signal
Thermocouple
Controller, panel mounting bracket, instruction manual
(depend on code symbols)
Input type code Input range code Measurable range˚C
J
00
0.0~400.0
J
01
01
0.0~800.0
K
02
0.0~400.0
K
03
0.0~800.0
Optional Items
Specificatio
Available
unit
PDZR2001
For compression terminal
1
Item
Terminator
Type
K
04
0.0~1200.0
for communication (100 Ω)
R
05
0.0~1600.0
Shunt resistor (250 Ω)
PDZS2001
For compression terminal
1
B
06
0.0~1800.0
Configuration software
PDZP2001
Programming loader
1
PDZL1001
Commonly usable cable
1
T
07
-200.0~200.0
(Under development)
T
08
-150.0~400.0
Communication cable for
configuration software
for configuration software
E
09
0.0~800.0
E
10
-200.0~800.0
S
11
0.0~1600.0
Communication cable (Note1)
N
12
0.0~1300.0
For compression terminal, PDZK4xx1
With compression
from PDA to PDA
terminal at both ends
(3m length)
1
U
13
-200.0~400.0
WRe5-26
14
0.0~2300.0
For compression terminal, PDZK5xx1
With M3.5 solderless
from PDA to PLC
terminal on PLC side
9-pin connector on PC side
1
RS232C / RS485
1
PL2
Resistance bulb Pt100
00
15
0.0~1300.0
00
0.0~150.0
For compression terminal, PDZK6xx1
01
0.0~300.0
from PDA to PC
02
0.0~500.0
Communication converter PDZT0001
03
0.0~600.0
04
-50.0~100.0
05
-100.0~200.0
06
-200.0~600.0
07
-200.0~850.0
1
signal converter
(Note 1) These cables are used for Modbus.
Length needs to be specified.
Block diagram of electrical isolation
Solid line shows
isolation from the
other units or circuits.
Power
supply
Power supply
unit
DI1 to DI10
DI / DO
unit
Ground
PV1
PV2
RS485
(Modbus)
DO1 to DO10
Ground
TC or RTD
input unit
AI / AO
unit
TC or RTD
input unit
Communication unit
AI1 to AI6
AO1 to AO4
RS485 (OPTO22)
7
PDC
CODE SYMBOLS
1 2 3 4 5 6 7 8 9 10111213 1415
PDC
1 3
1
Description
Controller function <4th digit code>
Programmable type
Number of control loops <5th digit code>
1 loop (1 control output)
Note 1
External terminal <6th digit code>
Compression terminal
2
Input signal <7th digit code>
1 to 5 V DC
Thermocouple
Resistance bulb Pt100
A
C
D
Note 2
Note 3
Note 3
Power supply voltage <9th digit code>
100V to 240V AC (Usable range 85V to 264V AC) 50 / 60Hz
24V DC (Usable range 20 to 30V DC)
A
B
Operation mode <10th digit code>
Cascade-Auto-Manual changeable type
C
Backup operation unit <11th digit code>
Without
Y
Communicatioin / Memory card interface <12th digit code>
(Slave)
(Master)
(memory card interface) Note4 Note5
Without
Without
Without
Without
Without
With
RS485
Without
Without
Note 6
RS485
RS485
Without
Note 6
RS485
Without
With
Note 6
RS485
RS485
With
Note 6
Y
M
C
D
U
R
Instruction manual <13th digit code>
Without
With (English)
Y
E
Programming method <14th digit code>
WAFER connection method
1
0
8
Factory configuration<15th digit code>
Without WAFER connection
With up to 48 WAFER connection
Note 7
Note 8
Note 1) Control and computation function could be done by WAFER connection or soft logic function.
Note 2) For current input, a shunt resistor is used for conversion into voltage.
Shunt resistor is optional item.
Note 3) Thermocouple and resistance bulb input are opitons.
Allowable up to 2 points.
Note 4) Communication cable and terminator are optional items.
Note 5) Recommended maker: Sandisk corporation.
Note 6) Slave interface is Modbus® protocol and master interface is OPTO22 interface®.
Note 7) In this case, WAFER connection programming should be made by user.
Connection tool (Programming loader) is optional item.
When set "2" on the 14th digit code, "0" should be set on the 15th digit code.
Note 8) WAFER connection specification sheets need to be prepared and submitted by user to Fuji.
Input signal and measurable range initial set before delibvery is as follows.
For specification of voltage input, scale is 0.00 to 100.00%
For specification of thermocouple, K, 0.0 to 400.0˚C.
For specification of resistance bulb is 0.0 to 150.0˚C.
8
FUNCTIONAL DIAGRAM
RS485 (Modbus®)
PC /
PLC
Communication
(option)
Control and computation
WAFER region
Memory
card
(option)
Loop 1
Analog input
1st
PID
Thermocople /
Resistance bulb
(option)
2nd
PID
Analog
output
Compression
terminal
Digital
input
Digital
output
Modbus®
(RS232C)
Control output
Communication
(option)
PC
Configuration software
RS485 (OPTO22
interface®)
OPTO22
SNAP I/O
9
PDC
67.5
OUTLINE DIAGRAM (Unit : mm)
Panel thickness 8 mm or less
Mounting bracket
Terminal cover
20
144
137.5
20
Panel
72
21.6
280
Note) The distance between other instruments and low end of PDA shall be more than 100mm.
PANEL CUTOUT DIMENSIONS
For mounting
multiple "n" units
250 or more
250 or more
For mounting
one unit
68
10
138
138 0
+1
+1
0
Number of
+0.7
0
(72.2n-4)
+1
0
units n
2
EXTERNAL CONNECTION DIAGRAM
Voltage
input
24 V external
power supply
(+)
RS-485
(Modbus®)
(-)
(COM)
24V
power
supply
for DIO
(+)
(-)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
AI1
SC
AI2
AI3
SC
AI4
AI5
SC
AI6
SC
VP
PC
DI9
DI10
DO9
DO10
MOD+
MODCOM
VPD
PCD
Note 1)
VPD
(+)
RS-485
(OPTO22®)
PCD
(+)
Process
variable
input 2
(-)
(COM)
(+)
Rcj
(-)
(-)
Voltage
input
Thermocouple
input
b
○
A
○
B
○
MI+2
22
MI-2
23
MI+3
24
MI-3
25
MI+4
26
MI-4
27
DO6
28
DO7
29
DO8
30
31 DIO-COM
DI6
32
DI7
33
34 DIO-COM
35
DI8
36
OPT+
37
OPT38
COM
I+2
39
Io2
40
Rcj-2
41
I-2
42
Note 1)
Voltage
output
Note 2
PCD
Resistance
bulb
input
Control
output
VPD
(+)
(+)
Process
variable
input 1
Rcj
(-)
(-)
Voltage
input
G
Thermocouple
input
b
○
A
○
B
○
MI+1
43
MI-1
44
AO1
45
SC
46
AO2
47
AO3
48
SC
49
AO4
50
FLT
51
DO1
52
DO2
53
DO3
54
DO4
55
56
DO5
DI1
57
58 DIO-COM
DI2
59
DI3
60
61 DIO-COM
DI4
62
DI5
63
I+1
64
Io1
65
Rcj-1
66
67
I-1
PCD
Resistance
bulb
input
N/- L/+
Instrument power supply 100 to 240VAC
Ground
-
+
Instrument power supply 24VDC
Note 1) COMPRESSION TERMINAL No.22,23,24,25,26,27,43,44 do not use (can't connect).
Note 2) Control outputs should be cross-connected to each other, externally.
+
M
-
L1
Do1
L2
Do2
11
PDC
[Note] Windows 95 is the registered trade mark of Microsoft corporation.
[Note] Modbus® is the registered trade mark of Gould Modicon.
[Note] Compact Flash® is the registered trade mark of Sandisk corporation.
[Note] OPTO22 interface and SNAP I/O is the registered trade mark of OPTO22(USA).
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan
http://www.fesys.co.jp/eng
Sales Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http: //www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan