ETC 20ALMDC-AXXX-8

Loop Powered Trip
Amplifiers
20ALM
The 20ALM is an input loop powered trip amplifier,
deriving its power from the input signal
■
High or low alarm option
■
Low voltage drop
■
Setpoints available on front panel as 0.4 to 2V signal (4 to
20mA)
■
LED indication of alarm
■
Unique low cost solution
PRICE
INFORMATION
AND ORDERING
Options and ordering codes
20ALM
115VAC
–
AXXX – 8
Options
115Vac rated contacts
115VAC
24Vac/dc rated contacts
DC
Description
The 20ALM is a 4-20mA loop powered trip amplifier. The
device derives its power from the input signal and therefore
requires no external power supply.
The output of the 20ALM is a single pole, normally open, solid state
relay which can be configured to close either above or below the
adjustable setpoint. The switched output can be connected to any
potential within 1kV of the transmitter supply, while transients of
2.5kV can be withstood.
The relay is designed to switch AC or DC.
Recommended operating conditions
Input current
4-20mA
Relay contact voltage
24Vac/dc or 110Vac
Relay current (max) 300mA @ 24Vdc – 130mA @ 110Vac
Output resistance 5Ω (on) 24V type – 24Ω on 110Vac type
Environmental conditions
Storage temperature
Operating ambient
Relative humidity
4-20mA
N.O. or N.C. solid
state relay output
3.4V
▲
▲
▲
58mm
1 2
▲
18mm
▲
3 4
▲
Connection details
1. Relay output -ve
2. Relay output +ve
1
4
Typ
Loop power
Max
2
Specifications
▲
63mm
3
▲
The device is housed in an ultra-compact DIN-Rail mounted
enclosure, only 18mm wide.
Dimensions
▲
The trip amplifier is typically used to activate a warning or control
system override when a sensor output goes above or below a pre-set
limit. Alternatively, the unit can be used for simple on/off control,
having a built in switching hysteresis.
-40-70˚C
0-55˚C
0-90% RH
3. Input channel +ve
4. Input channel -ve
Parameter
Supply voltage
Supply current
Full scale volt drop
Relay type 1 current
Relay type 2 current
Output resistance ‘ON’
Setpoint hysteresis
Trip point accuracy
Temperature coefficient
Trip point drift
Relay time response
Operating ambient
Relative humidity
Isolation voltage
Surge voltage
Notes
Min
4mA
3.4V
20mA
3.5V
315mA
130mA
5Ω/24Ω
50µA
Comments
At 20mA input
Rated at 24Vdc/ac
Rated at 110Vac
24V/110Vac relay type
Other values available
±0.25%
±100ppm/˚C
±100ppm/˚C
10ms
0˚C
0%
1kV
55˚C
90%
2.5kV for 50µS
Transient of 10kV/µS
Setpoint is adjusted by 20 turn potentiometers on the front panel.
Setpoint can be checked by measuring the 0.4 to 2V (4 to 20mA) voltage on the
front panel terminals.
High or low alarm is selectable using internal link.
Closed output contact is indicated by a red LED on the front panel.