FUJI EDS11-164A

PX series
Digital temperature
Controller
Socket Type
MICRO-CONTROLLER X
MICRO-CONTROLLER X
(48mm×48mm)
DATA SHEET
PXR4
SOCKET
With front dimensions of 48×48mm, this socket type temperature controller enables On-Off control, PID control or
8-step ramp/soak function, using thermocouple, resistance
bulb or DC1 to 5V signal as input.
Though small-sized, it can be equipped with a variety of
functions.
FEATURES
1.PID with auto-tuning, PID self-tuning and fuzzy control are
installed as standard.
2.Front side waterproof specification in conformity with
NEMA4X (standard).
3.Two alarms are equipped, and 8-step ramp/soak function
can be installed as an option.
SPECIFICATIONS
1. General specifications
2. Control function of standard type
100 V (-15%) to 240 V (+10%) AC, 50/60 Hz
or 24 V (±10%) AC 50/60 Hz, 24 V (±10%) DC
When using 100 V AC: 8 VA or less
When using 220 V AC: 10 VA or less
When using 24 V AC/DC: 10VA
Insulation resistance 20 MΩ or more (500 V DC)
Dielectric strength Power supply-ground ... 1500 V AC for 1 min
Power supply-others ... 1500 V AC for 1 min
Ground-relay output ... 1500 V AC for 1 min
Ground-alarm output ... 1500 V AC for 1 min
Others ... 500 V AC for 1 min
Input impedance Thermocouple: 1 MΩ or more
Voltage: 450 kΩ or more
Current: 250Ω (external resistor)
Allowable signal Thermocouple: 100Ω or less
source resistance Voltage: 1 kΩ or less
Allowable wiring Resistance bulb: 10Ω or less per wire
resistance
Reference junction
±1°C (at 23°C)
compensation accuracy
Input value correction ±10% of measuring range
Set value correction ±50% of measuring range
Input filter
0 to 900.0 sec settable in 0.5 sec steps
(first order lag filter)
Noise reduction ratio Normal mode noise (50/60 Hz): 50 dB or more
Common mode noise (50/60 Hz): 140 dB or more
Control action
Power supply
voltage
Power
consumption
PID control (with auto tuning, self-tuning)
Fuzzy control (with auto tuning)
Self tuning
Proportional band (P) 0 to 999.9% of measuring range settable in
0.1% step
Integral time (I)
0 to 3200 sec settable in 1 sec step
Differential time (D) 0 to 999.9 sec settable in 0.1 sec step
On/off action if P = 0. Proportional action when I, D = 0.
Proportional cycle 1 to 150 sec settable in 1 sec step
Only for relay contact output or SSR/SSC drive
output
Hysteresis width 0 to 50% of measuring range
For On/off action only
Anti-reset windup 0 to 100% of measuring range
Automatically validated at auto tuning
Input sampling cycle 0.5 sec
Control cycle
0.5 sec
3. Input section
Input signal
Measuring range
Burnout
Thermocouple : J, K, R, B, S, T, E, N, PLII
Resistance bulb : Pt100
Voltage, current: 1 to 5 V DC, 4 to 20 mA DC
(Apply current input after connecting the
furnished 250Ω resistor to input terminal.)
See measuring range table (Table1)
For thermocouple or resistance bulb input
Control output upper/lower are selectable
4. Output section of standard type (control output 1)
Control output 1
Select one as follows
Relay contact: SPDT contact:
220V AC/30V DC, 3A (resistive load)
Mechanical life 10 million operations (no load)
Electrical life 100,000 operations (rated load)
Minimum switching current 100mA (24V DC)
SSR / SSC drive (Voltage pulse):
ON: 17 to 25 V DC
OFF: 0.5V DC or less
Max. current: 20mA or less
4 to 20mA DC: Allowable load resistance 600Ω
or less
EDS11-164a
Date
Apr. 1, 2011
PXR4
SOCKET
5. Operation and display section
11. Structure
Digital setting by 3 keys
With key lock function
Process value/set value Independent display
4 digits, 7-segment LED
Status display LED Control output, process alarm output
Setting accuracy
0.1% or less of measuring range
Indication accuracy Thermocouple: ±(0.5% of measuring range)
±1 digit ±1°C
(at 23°C)
For thermocouple R at 0 to 500°C ...
± (1% of measuring range) ±1 digit ±1°C
For thermocouple B at 0 to 400°C ...
± (5% of measuring range) ±1 digit ±1°C
Resistance bulb, voltage/current:
± (0.5% of measuring range) ±1 digit
Mounting method Panel flush mounting, DIN rail mounting.
(Mounting socket is required for mounting
DIN rail.)
External terminal 8 pins or 11 pins terminals
(Socket is required for wiring separately.)
Case material
Plastic
(non-combustible grade UL94V-0 equivalent)
Dimensions
48 × 48 × 84.7mm
Weight
Approx. 200 g
Protective
Front waterproof structure: NEMA4X
structure
(IEC standard IP66 equivalent)
(when mounted on panel with our genuine
packing. Waterproof feature unavailable
in close mounting of multiple units)
Rear case: IEC IP20
Outer casing
Black (front frame, case)
Parameter setting
method
Display
6. Alarm (option)
Alarm kind
Alarm ON-delay
Process alarm
output
Absolute alarm, deviation alarm, zone alarm
with upper and lower limits for each
Hold function available (See the figure below.)
Alarm latch, Excitation/non-excitation
selecting function provided
Delay setting 0 to 9999 sec settable in 1 sec
steps
Relay contact: SPST contact: 220 V AC/30 V DC,
1 A (resistive load)
Mechanical life 10 million operations (no load)
Electrical life 100,000 operations (rated load)
Minimum switching current 100 mA (5 V DC)
MAX 2 points output cycle 0.5 sec
What is alarm with hold?
The alarm is not turned ON immediately even when the process
value is in the alarm band. It turns ON when it goes out the alarm
band and enters again.
PV (process value)
Table 1 Measuring range table
Group
I
Period where lower
limit alarm is output
II
Power ON
Power ON
Power OFF
off
Lower limit alarm
on
off
off
Lower limit alarm
(with hold)
on
on
off
off
7. Other functions
Parameter mask
function
Ramp/soak
function (option)
Parameter display is disabled by software.
2 program pattern of 4 steps each, or 1
program pattern × 8 steps
Digital input allows to start/reset the action.
8. Power failure processing
Memory protection Held by non-volatile memory
9. Self-check
Method
Program error supervision by watchdog timer
10. Operation and storage conditions
Ambient operating -10°C to 50°C
temperature
(In low-temperature environment, start-up
time may vary in power activation.)
Ambient operating Less than 90% RH (no condensation)
humidity
Storage temperature -20°C to 60°C
2
input signal
measuring range(°C) measuring range(°F)
-238 to 1562
-150 to 850
Resistance bulb Pt100
32 to 1472
0 to 800
Thermocouple J
32 to 2192
0 to 1200
K
32 to 2912
0 to 1600
R
32 to 3272
0 to 1800
B
32 to 2912
0 to 1600
S
-238 to 752
-150 to 400
T
-238 to 1472
-150 to 800
E
32 to 2372
0 to 1300
N
32 to 2372
0 to 1300
PL2
-1999 to 9999
scaling range
1 to 5V
DC voltage
4 to 20mA
DC current
Note 1: For current input connect the supplied 250Ω resister at
the input terminal.
Note 2: Setting cannot be changed to a different group.
Note 3: When the measuring range exceeds 1000°C (1832°F),
decimal point cannot be used.
PXR Model Code Configuration
4 5 6 7 8
9 10 11 12 13
S 1 PXR 4
Digit
Specification
4 <Front dimensions>
48 × 48mm
5
6
7
8
9
10
11
12
13
<Input signal>
Thermocouple °C
Thermocouple °F
Resistance bulb Pt100 3-wire type I (°C)
Resistance bulb Pt100 3-wire type I (°F)
1 to 5V DC
4 to 20mA DC
Resistance bulb Pt100 3-wire type II (°C)
<Control output 1>
Relay contact output
Voltage pulse output (24V DC)
4 to 20mA DC output
<Terminal form>
Socket type
<Revision code>
<Optional specifications>
None
Alarm (1 pc.)
Ramp-soak
Alarm (1 pc.) + Ramp-soak
Alarm (2 pcs.)
Alarm (2 pcs.) + Ramp-soak
<Instruction manual> <Power supply voltage>
None
100 to 240V AC
English
100 to 240V AC
None
24V AC/24V DC
English
24V AC/24V DC
<Socket>
None
For rail mounting (8-pin screw terminal)
For panel mounting (8-pin screw terminal)
For rail mounting (11-pin screw terminal)
For panel mounting (11-pin screw terminal)
Note1)
Note2)
Note3)
Note4)
Note5)
Note6)
Note
4
Note5
Note5
Note6
T
R
N
S
A
B
W
A
C
E
S
1
0
1
4
5
F
G
N
V
C
B
Note1
Note2
Note3
Note4
0
1
2
4
5
0
0
0
0
0
0
0
0
0
0
Type: TP48X
Type: TP48SB
Type: TP411X
Type: TP411SBA
Input terminal (Pt100 input) assignment is same as PXW4/PXZ4/PXV4.
Input terminal (Pt100 input) assignment is different from PXW4/PXZ4/PXV4,
but in case of thermocouple input terminal assignment is same.
Input signal, measurement range, and set value at the time of deliver are as follows.
When thermocouple is specified: Thermocouple K, Measurement range; 0 to 400°C,
Set value; 0°C
When resistance bulb is specified: Pt, Measurement range; 0 to 150°C, Set value; 0°C
When voltage/current is specified: Scaling; 0 to 100%, Set value; 0%
For the cases other than the above, specify input signal and measurement range.
Input signal of the thermocouple and the resistance bulb can be switched by key operation
on the front panel.
Control action is set to reverse action when delivered. The reverse action and normal action can be
switched by key operation on the front panel.
3
PXR4
SOCKET
Scope of delivery
Scope of delivery Controller, panel mounting bracket,
watertight packing, instruction manual (as
ordered), socket (as ordered), 250Ω resistor
(for current input)
Option
Shunt resistor 250Ω ±0.1%
Model: ZZPPXR1-A190
Insulation block diagram
Power supply section
Relay contact control output 1
Alarm relay output 1, 2
Measurement input
Internal circuit
Voltage pulse, 4 to 20mA DC
control output 1
Note: Basic insulation (dielectric strength 1500 V AC)
between blocks delimited by line
.
Functional insulation (dielectric strength 500 V AC)
between blocks delimited by line
.
Non isolated between blocks which are not delimited from
each other.
4
OUTLINE DIAGRAM (Unit: mm)
Mounting frame
93.7
79.5
84.7
Panel
70.5
9
44.7
48
t
Water-proof packing
1
t
57
1
48
8
Panel cutout size (Unit: mm)
+0.5
45 0
Side stick mounting (n units)
+0.5
+0.5
45 0
73min.
45 0
+0.5
(48 x N-3) 0
63min.
Note: Waterproof is not available in stick mounting.
5
PXR4
SOCKET
CONNECTION DIAGRAM
(1) With alarm functions
11-pin socket
• When compatible with PXW4/PXZ4/PXV4 thermocouple input terminal
(When either one of the following is selected for the 5th digit of the code symbols: “T,” “R,” “W,” “A” and “B”)
Note that the terminal layout of the resistance bulb input type differs from that of PXW4/PXZ4/PXV4.
CONTROL OUTPUT
DC 4 to 20mA OUTPUT
5
4
+
SSR/SSC DRIVING OUTPUT
6
-
5
4
+
-
RY OUTPUT
COMMON
INPUTS
6
5
NOTE1
-
-
2
2
250Ω
+
A
3
B
2
ALARM OUTPUT
6
7
9
3
-
+
B
1
1
1
DC4 to 20mA DC1 to 5V R.T.D.
ALARM OUTPUT1
8
4
2
+
11
1
ALARM OUTPUT2
10
T.C.
POWER
AC100 to 240V
AC/DC 24V
50/60Hz
• When compatible with PXW4/PXZ4/PXV4 resistance bulb input terminal
(When either one of the following is selected for the 5th digit of the code symbols: “N” and “S”)
Note that the terminal layout of the thermocouple input type differs from that of PXW4/PXZ4/PXV4.
CONTROL OUTPUT
DC 4 to 20mA OUTPUT
5
INPUTS
+
4
+
-
SSR/SSC DRIVING OUTPUT
6
5
4
+
-
ALARM OUTPUT
6
RY OUTPUT
2
T.C.
7
B
A
R.T.D.
ALARM OUTPUT1
8
4
B
-
6
5
3
COMMON
9
3
2
1
11
ALARM OUTPUT2
10
POWER
AC100 to 240V
AC/DC 24V
50/60Hz
NOTE 1 : Use the 250Ω resistance (accessory).
6
(2) Without alarm functions
8-pin socket
• When compatible with PXW4/PXZ4/PXV4 thermocouple input terminal
(When either one of the following is selected for the 5th digit of the code symbols: “T,” “R,” “W,” “A” and “B”)
Note that the terminal layout of the resistance bulb input type differs from that of PXW4/PXZ4/PXV4.
CONTROL OUTPUT
RY OUTPUT
INPUTS
NOTE1
-
2
-
2
250Ω
+
+
1
1
DC4 to 20mA DC1 to 5V
A
3
B
2
B
1
R.T.D.
4
4
5
-
DC 4 to 20mA OUTPUT
+
4
5
-
6
2
+
+
5
3
-
SSR/SSC DRIVING
OUTPUT
7
1
8
T.C.
POWER
AC100 to 240V
AC/DC 24V
50/60Hz
• When compatible with PXW4/PXZ4/PXV4 resistance bulb input terminal
(When either one of the following is selected for the 5th digit of the code symbols: “N” and “S”)
Note that the terminal layout of the thermocouple input type differs from that of PXW4/PXZ4/PXV4.
CONTROL OUTPUT
RY OUTPUT
INPUTS
+
T.C.
3
2
4
B
3
B
2
A
R.T.D.
SSR/SSC DRIVING
OUTPUT
+
5
4
5
-
DC 4 to 20mA OUTPUT
+
4
5
-
6
7
1
8
POWER
AC100 to 240V
AC/DC 24V
50/60Hz
NOTE 1 : Use the 250Ω resistance (accessory).
7
PXR4
SOCKET
SOCKET OUTLINE DIAGRAM (Unit: mm)
Without alarm
φ27
TP48X TYPE (FOR RAIL MOUNTING)
TERMINAL SCREW
M3.5×8
TERMINAL SCREW
M3.5×8
4
5
6
2
1
8
7
6
5
4 3
7
8
1 2
70
45
3
5.5
35.4
TP48SB TYPE (FOR PANEL MOUNTING)
5
17
7.8
4
45
2-φ4.5
HOLE
7
50
20.3 MAX.
40±0.2
2-φ4.5
MOUNTING HOLE
With alarm
TP411X TYPE (FOR RAIL MOUNTING)
TP411SBA TYPE (FOR PANEL MOUNTING)
TERMINAL SCREW
M3.5×11
4.5
TERMINAL SCREW
M3.5×11
φ27
5
4
9
10
11
7.8
1
50
3
2
45
4
3
6
7
8
9
1 11
2
45
4.5
16.3
6.2
10
7
4
2-φ4.5
HOLE
25.6
5
35.4
6
70
8 7
31.2 MAX.
40±0.2
2-φ4.5
MOUNTING HOLE
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
International Sales Div
Sales Group
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fujielectric.com
Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425
http://www.fjielectric.com/products/instruments/
Information in this catalog is subject to change without notice.
Printed in Japan