ETC G408-1001

ULTRA
SLIMPAK®
G408-0001 &
G408-1001
DC Input Field
Configurable Isolator
Provides a Fully Isolated DC Output
in Proportion to a DC Input
Description
Benefits
Eliminates Ground Loops
Field Configurable Input
Ranges: 10mV to 100V,
1mA to 100mA
Field Configurable Output
Ranges: 0-5V, 0-10V,
0-1mA, 0-20mA, 4-20mA,
±5v, ±10V
Ultra Slim Housing for High
Density Installations
Flexible Power Supply
Accepts 9 to 30VDC
ASIC Technology
The Ultra SlimPak G408 is a DIN rail mount, DC input signal conditioner with 1800VDC isolation
between input, output and power. The field configurable input and output offers flexible, wide
ranging capability for DC current and voltage signals.
The input can be configured for any one of 12 voltage ranges from 10mV to 100V or 6 current ranges
from 1mA to 100mA (see Table 1). The output is linear to the input and can be set for either 0-5V,
0-10V, 0-1mA, 0-20mA or 4-20mA (for models G408-0001) and -5 to +5V or -10 to +10V (for model
G408-1001).
Wide ranging, precision zero and span pots allow 50% adjustability of offset and span turn-down
within each of the 18 switch selectable ranges. For example, the 0-2mA input range could be turned
down to 0-1mA and provide a full scale output signal (e.g. 4-20mA), or turned down and offset to
achieve a 1-2mA/4-20mA I/O combination.
The G408 also accepts bipolar inputs (e.g. 10V range set to bipolar = -10 to +10V) and offers selectable
normal or reverse operation (e.g. 4-20mA/20-4mA). The ASIC based I/O channel is optically isolated
to 1800VDC and is transformer isolated from the power supply.
Application
The G408 is useful in eliminating ground loops, converting signal levels, and providing signal drive.
The field configurable, wide ranging capability ensures maximum flexibility for most DC to DC
applications, minimizing spare part requirements.
Diagnostic LED
The G408 is equipped with a dual function LED signal monitor. The green, front mounted LED indicates
both DC power and input signal status. Active DC power is indicated by an illuminated LED. If the
input signal is more than 110% of the full scale range, the LED will flash at 8Hz. Below -10%, the flash
rate is 4Hz.
Figure 1: G408 Block Diagram
Configuration
Calibration
The G408 has 18 input range settings. Trim
potentiometers allow 50% input zero and
span adjustability within each of the 18 full
scale input ranges.
1. After configuring the DIP switches, connect the input to a calibrated DC source.
Connect the output to the actual device load
(or a load approximately equivalent to the
device load) and apply power.
Unless otherwise specified, the factory presets the Model G408-0001 and G408-1001
as follows:
G408-0001
Input Range:
Output Range:
4-20mA
4-20mA
Note: To maximize thermal stability, final
calibration should be performed in the operating installation, allowing approximately 1
to 2 hours for warm up and thermal equilibrium of the system.
2. Set the calibrator to the desired minimum
input and adjust the zero potentiometer for
the desired minimum output.
3. Set the calibrator to the desired maximum
input and adjust the span potentiometer for
the desired maximum output.
4. Repeat steps 2 and 3, as necessary, for best
accuracy.
G408-1001
Input Range:
4-20mA
Output Range: -10 to +10V
Table 1: G408 Input Range Settings
The DC power input accepts any source
between 9 and 30V; typically a 12V or
24VDC source is used (see Accessories).
Ranges
Voltage
Current
20mV
To minumize interference from electrical
and magnetic fields, the use of shielded,
twisted pair wires on the input and output
is recommended.
Refer to Tables 1 through 4 for the proper
switch settings. Use the switches on SW1 to
select the input type (voltage or current) and
also to select the desired input range and
function setting. Use SW2 to select the desired output type.
1
2
2mA
3
4
1
2
3
4
0 to 5V
0 to 10V
0 to 1mA
50mV
5mA
10mA
200mV
20mA
50mA
1V
100mA 2V
5V
10V
25V
50V
100V
Unipolar
Reverse
0 to 20mA
Selector SW1
6
7
8
Table 4: G408-1001 Output Settings
G408-1001
Ranges
Selector SW1
9
-5V to +5V
-10V to +10V
Key: = 1 = ON or Closed
7
8
Current
Voltage
4 to 20m
6
Table 2: G408 Function Settings
5
5
Key: = 1 = ON or Closed
Key: = 1 = ON or Closed
Function
Selector SW2
G408-0001
Ranges
100mV
500mV
WARNING! Do not change switch settings
with power applied. Severe damage will result!
Table 3: G408-0001 Output Settings
Selector SW1
Key: = 1 = ON or Closed
10
Figure 2: G408-0001 Factory Cal; 4-20mA,
Unipolar Input, Normal Operation, 4-20mA Output.
Figure 3: G408-1001 Factory Cal; 4-20mA,
Unipolar Input, Normal Operation -10 to 10V Output.
Note: All Ultra SlimPak modules are designed to operate in ambient
temperatures from 0 to 55°C when mounted on a horizontal DIN rail. If
five or more modules are mounted on a vertical rail, circulating air or
model HS01 Heat Sink is recommended. Refer to HS01 Technical
Bulletin (#721-0549-00) or contact the factory for assistance.
Figure 4: Wiring Diagram for G408-0001 and G408-1001
Figure 5: Mounting Multiple Modules
SPECIFICATIONS
Output (G408-1001)
Voltage
Output: -5V to +5V, -10 to +10V
Source Impedance: <10 Ohms
Drive: 10mA, max.
LED Indication (green)
Input Range
>110%(approx) input:8Hz flash
< -10%(approx) input: 4Hz flash
Accuracy (Including Linearity, Hysteresis)
<2mA/<20mV:± 0.35% of full scale, typical;
0.5%,max.
>2mA/>20mV:± 0.1% of full scale, typical; 0.2%, max.
Response Time (10-90%)
200mSec., typical
Stability (Temperature)
±0.025% of full scale/°C,typical; ±0.05%/°C, max.
Common Mode Rejection
DC to 60Hz: 100dB
Isolation (Input to Output)
1800VDC between input, output and power
EMC Compliance (CE Mark)
Emissions: EN50081-1
Immunity: EN50082-2
Safety: EN50178
Models & Accessories
Dimensions
Input
Voltage
Range Limits: 10mV to 100V
Impedance: >100K Ohms
Overvoltage:
400 Vrms, max.(Intermittent);
264 Vrms,max. (Continous)
Current
Range Limits: 1mA to 100mA
Impedance: 20 Ohms, typical
Overcurrent: 170mA RMS, max.
Overvoltage: 60VDC
Zero Turn-Up: 50% of full scale input
Span Turn-Down: 50% of full scale input
Common Mode (Input to Ground) 1800 VDC, max.
Output (G408-0001)
Voltage
Output: 0-5V, 0-10V
Source Impedance: <10 Ohms
Drive: 10mA, max.
Current
Output: 0-1mA,4-20mA,0-20mA
Source Impedance: >100K Ohms
Compliance:
0-1mA: 7.5V, max (7.5K Ohms)
4-20mA: 12V, max (600 Ohms)
0-20mA: 12V, max (600 Ohms)
Ordering Information
Mean Time Between Failures
60K Hours
Humidity (Non-Condensing)
Operating: 15 to 95% @ 45°C
Soak: 90% for 24 hours @ 65°C
Temperature Range
Operating: 0 to 55°C (32 to 131°F)
Storage: -25 to 70°C (-13 to 158°F)
Wire Terminals
Screw terminals for 12-22AWG
Power
Consumption: 1.5W typical, 2.5W max.
Range: 9 to 30VDC
Weight
0.5 lbs.
Agency Approvals
CSA certified per standard C22.2, No. 0-M91 and
142-M1987 (File No. LR42272).
UL recognized per standard UL508
(File No.E99775).
CE Conformance per EMC directive 89/336/EEC
and Low Voltage 73/23/EEC (Input < 75VDC,
only).
Specify:
1. Model: G408-0001 (standard outputs) or
G408-1001 (bipolar outputs)
2. Accessories: (see Accessories)
3. Optional Custom Factory Calibration; specify
C620 with desired input and output range.
Accessories
All SlimPak "G" series modules will mount on
standard TS32 (model MD02) or TS35 (model MD03)
DIN rail and include model HS01 heat sink. In addition,
the following accessories are available:
MD03 TS35x7.5 DIN rail
WV905 24VDCPower Supply (0.5 Amp)
H910 24VDC Power Supply (1 Amp)
H915 24VDC Power Supply (2.3 Amp)
MB03 End Bracket for MD03
C664 I/O Descriptive Tags
C006 0.1 Ohm, 5W, 1% shunt resistor
Factory Assistance
For additional information on calibration, operation and
installation contact our Technical Services Group:
Eurotherm Controls
703-669-1318
741-F Miller Drive
Leesburg, VA 20175-8993
703-443-0000
[email protected]
actionio.com
Action Instruments
[email protected]
721-0657-00-F 09/04 Copyright© Eurotherm, Inc 2004
Barber-Colman
Eurotherm Chessell
Eurotherm Controls