ETC BM3

1,2 & 3 PHASE BURST FIRING
TRIGGER MODULE
BM1/2/3
X10219
INTRODUCTION
This burst fire control module incorporates the unique MONO-LINK - Gate to Gate firing feature which uses
single path hard firing for each phase thyristor pair, eliminating cathode firing connections. The zero crossing
triggered output has a variable on/off ratio which is proportional to the manual control signal or dc input demand
signal. Phase timing problems are eliminated, as the opto-isolated output driver stage is self timing from the
associated power device connections. The burst firing circuit prevents fast changes in load current thus inhibiting
Radio Frequency Interference.
APPLICATIONS
Virtually all resistive heater loads including air curtains, space heaters, ovens, furnaces, hot plates, extruders,
moulders, boilers, soldering pots and irons, heating tapes, drying and other heating & ventilating applications,
when used in conjunction with auxiliary power devices.
FEATURES
• Fires triacs or thyristors up to 440V,
• Hz supplies.
• MONO-LINK  - Gate to Gate firing.
• No phase timing or matching required.
• Zero volts switching (RFI free).
• Status LED giving output ratio indication.
• High Isolation opto-coupled output.
INSTALLATION AND DIMENSIONS
EXAMPLE - BM3
POWER CONNECTIONS
SPECIFICATIONS
Signal Span minimum
Signal Span maximum
Signal Zero offset
dV/dt rating
Max. Gate/Line voltage
Trigger isolation voltage
Trigger output rating
Storage temperature
0 to 2V dc
0 to 25V dc
0 to 30% of span
100V/ µs
440V ac
2500V rms
0.8A
-20°C to +85°C
AC input supply
Auxiliary output
Line Frequency
Max. Ambient temperature
Cycle time base nominal
Mono-Link fuse
Manual potentiometer
Power connections
18 to 24V ac/dc @ 65mA
5V dc @ 5mA protected
50/60 Hz
65°C operational
1 second
F100mA (HRC)
2K, 5K or 10K
6.3mm Amp tags
FUSING:
It is recommended to use semiconductor (fast acting) type fuses or circuit breakers (Semiconductor - MCB) for
unit protection and appropriate protection for unit supply (HRC F1A). See SRA Datasheet for further
information.
CE MARKING
This product family carries a “CE marking. For information see recommendation section and contact our sales
desk. (See Declaration of Conformity).
RECOMMENDATION
Other documents available on request, which may be appropriate for your applications.
CODE
IDENTITY
DESCRIPTION
X10229
RFI
Filtering recommendation - addressing the EMC Directive
X10213
ITA
Interaction, uses for phase angle and for burst fire control.
X10255
SRA
Safety requirements - addressing the Low Voltage Directive (LVD)
including :- Thermal data/cooling ; “Live” parts warning & Earthing
requirements; Fusing recommendations.
AP02/4
COS
UAL Conditions of sale
NOTE It is recommended that installation and maintenance of this equipment should be done with reference to
the current edition of the I.E.E. wiring regulations (BS7671) by suitably qualified/trained personnel. The
regulations contain important requirements regarding safety of electrical equipment. (For International
standards refer to I.E.C directive IEC 950).
ORDER CODE:
State part number: BM1, BM2 or BM3 + Signal option.
Optional extras include: Potentiometer, Supply transformer, Power stack.
UNITED AUTOMATION LIMITED
1 Southport Business Park
Southport, PR8 4HQ, U.K.
Page No 2 of 2 Issue 1
Tel (01704)-565713
Fax (01704)-569760
06/03/98