C J 1 S Y S T E M P O W E R A N D E X PA N S I O N Power and Expansion Selection This section provides tools to calculate the CJ1 system current consumption total needed to select the power supply. When the number of modules or power requirements exceeds the capability of the power supplies available, I/O expansion racks solve the problem. If the number of modules per rack exceeds 10 or the current consumption is greater than the capacity of the power supply units, use the CPU and expansion rack configuration. What is the basic configuration? A CJ1 system consists of a power supply, a CPU, and up to 10 basic I/O, special I/O and CPU bus units, and an end cover. See page B-109. What goes on expansion I/O racks? The expansion I/O rack contains a power supply, an I/O interface module and the remaining I/O modules. Each expansion rack requires a power supply, the I/O interface module and up to 10 more modules. Where are ratings to calculate overall current consumption? All the current consumption ratings for the CPU, basic I/O, special I/O and CPU bus units are collected in the tables on pages B-110 to B-111. Which power supply is right? Compare the current consumption total of basic I/O, special I/O, and CPU bus units to determine which power supply to use. Input Voltage 100 to 240 VAC 24 VDC Output rating 5 A, 5 VDC with 2 A RUN output 2.8 A, 5 VDC 5 A, 5 VDC Output capacity 25 W max. 14 W max. 25 W max. Power supply model CJ1W-PA205R CJ1W-PA202 CJ1W-PD025 See page B-110 B-110 B-110 Note: If more than 10 modules are required or the current consumption exceeds the output capacity of the power supplies, go to page B-109 for configuration of I/O expansion racks. The same power supply units can be used for both CPU and I/O expansion racks. How many expansion I/O racks can be used? Depending on the CPU chosen, the system can be expanded with up to three additional racks of basic I/O, special I/O and CPU bus units. Maximum I/O modules per CPU 40 30 20 10 10 Maximum I/O expansion racks per CPU 3 2 1 0 0 CPU models CJ1G-CPU44H CJ1G-CPU42H CJ1M-CPU13 CJ1M-CPU12 CJ1M-CPU11 CJ1G-CPU45H CJ1G-CPU43H CJ1M-CPU23 CJ1M-CPU22 CJ1M-CPU21 CJ1H-CPU65H CJ1H-CPU66H Note: Order one CJ1W-IC101 I/O control module for the CPU rack and one CJ1W-II101 I/O interface module for each I/O expansion rack. Connect the modules with a cable of the appropriate length. Second and third I/O expansion racks connect between I/O interface modules. See page B-117 for details. B-108 System Power and Expansion System Configuration J Basic Configuration A CJ1 Series basic configuration consists of a CPU, Power Supply Unit, Basic I/O Modules, Special I/O Modules, CPU Bus Modules, and an End Cover. Add up the current consumption of all the modules and the CPU according to the formula on the following page and then select the Power Supply Unit right for the application. Basic Configuration Power Supply Unit Configuration Modules (Basic I/O Modules, Special I/O Modules, CPU Bus Modules) CPU Memory Card End Cover J CPU and Expansion Racks If the number of modules per rack exceeds 10 or the current consumption is greater than the capacity of the Power Supply Units, use the CPU and Expansion Rack configuration. This divides the load from the modules across two Power Supply Units. To ensure communication and automatic channel assignment in programming, order an I/O Control Module for the CPU Rack and an I/O Interface Module on each Expansion Rack. CPU Rack Power Supply Unit I/O Control Module CPU Configuration Modules (Basic I/O Modules, Special I/O Modules, CPU Bus Modules) Memory Card Expansion Rack (Up to 3 Expansion Racks Allowed) Power Supply Unit I/O Interface Module Configuration Modules (Basic I/O Modules, Special I/O Modules, CPU Bus Modules) End Cover End Cover I/O Connecting Cable Programmable Controller CJ1 B-109 System Power and Expansion Current Consumption Calculate All Aspects of Current Consumption J Calculating Maximum Current Consumption A. Calculate Maximum Current Supply (See the table below.) • • • Current required at 5 VDC by all Modules in column (A) ≤ Maximum current consumption shown in table Current required at 24 VDC by all Modules in column (B) ≤ Maximum current consumption shown in table Current required at 24 VDC for service power supply in column (C) ≤ Maximum current consumption shown in table B. Calculate Maximum Total Power Supply (See the table below.) • • • A × 5 VDC + B × 24 VDC + C × 24 VDC ≤ Maximum total power consumption shown in column (D) The amount of current/power that can be supplied to the Modules mounted in a Rack is limited by the capacity of the Power Supply Unit. Design the system so that the total current consumption of the Modules does not exceed the maximum current for each voltage group and the total power consumption does not exceed the maximum for the Power Supply Unit. Reference Table for Maximum Current Consumption The following table shows the maximum currents and power that can be supplied by Power Supply Units on CPU Racks and Expansion Racks. Power Supply pp y Unit Maximum current consumption ((D)) Maximum total ti power consumption (A) 5-V group (B) 24-V group relay driver power supply (C) 24-V group service power supply CJ1W-PA205R 5.0 A 0.8 A None 25 W CJ1W-PA202 2.8 A 0.4 A None 14 W CJ1W-PD025 5.0 A 0.8 A None 25 W Note:1. When calculating current/power consumption in a CPU Rack — be sure to include the power required by the CPU itself. When expanding the configuration, be sure to include the power required by the I/O Control Module. 2. When calculating current/power consumption in an Expansion Rack — be sure to include the power required by the I/O Interface Module itself. J Example Calculations In this example, the following modules are mounted to a CJ1 Series CPU Rack with a CJ1W-PA205R Power Supply Unit. Module Model Quantity 5 VDC 24 VDC CPU CJ1G-CPU45 1 0.910 A — I/O Control Module CJ1W-IC101 1 0.020 A — Input p Modules CJ1W-ID211 2 0.080 A — CJ1W-ID231 2 0.090 A — Output Modules CJ1W-OC201 2 0.090 A 0.048 A Special I/O Module CJ1W-DA041 1 0.120 A — CPU Bus Module CJ1W-CLK21 1 0.350 A — Current consumption Calculation 0.910+0.020+0.080×2+0.090×2+ 0.090×2+0.120+0.350 0.048 A×2 Result 1.92 A (≦5.0 A) 0.096 A (≦0.8 A) Calculation 1.92×5 V = 9.60 W 0.096 A×24 V = 2.304 W Result 9.60+2.304 = 11.904 W (≦25 W) Power consumption p B-110 Programmable Controller CJ1 System Power and Expansion Current Consumption J Current Consumption Tables 5-Volt Group: CPUs and Expansion Modules Module Model CPUs CJ1H-CPU66H/ CJ1H-CPU65H (These values include current consumption for a Programming Console or CX-Programmer.) Current consumption at 5 V (A) 0.99 (See note.) Special I/O Modules Category Module Model Special p I/O Modules Analog g Input p M d l Modules CJ1W-AD081-V1 CJ1W-AD041-V1 CJ1W-DA041 CJ1W-DA021 CJ1W-DA08V CJ1W-DA08C CJ1W-MAD42 Current consumption at 5 V (A) 0.42 0.42 0.12 0.12 0.14 0.14 0.58 CJ1G-CPU45H/ CJ1G-CPU44H/ CJ1G-CPU43H/ CJ1G-CPU42H CJ1G-CPU45/ CJ1G-CPU44 0.91 (See note.) CJ1M-CPU11/ CJ1M-CPU12 CJ1M-CPU13 CJ1M-CPU21/ CJ1M-CPU22 CJ1M-CPU23 0.58 Mixed Analog Module Temperature Control Modules CJ1W-TCjjj 0.25 0.64 Position Control M d l Modules CJ1W-NC113/133 CJ1W-NC213/233 0.25 CJ1W-NC413/433 CJ1W-CT021 0.36 0.28 CJ1W-V600C11 CJ1W-V600C12 0.26 0.32 0.91 (See note.) I/O Control Module CJ1W-IC101 0.02 I/O Interface Module CJ1W-II101 0.13 End Cover CJ1W-TER01 — (Included in CPU or Expansion Module.) Note: Add 0.15 A per Module when the NT-AL001-E is connected. High-speed Counter Module ID Sensor M d l Modules Basic I/O Modules and Interrupt Input Module Category Name Model Basic I t Input Modules DC Input p M d l Modules CJ1W-ID201 CJ1W-ID211 CJ1W-ID231 CJ1W-ID232 CJ1W-ID261 CJ1W-ID262 CJ1W-IA111 CJ1W-IA201 CJ1W-OD201 CJ1W-OD202 CJ1W-OD203 CJ1W-OD204 CJ1W-OD211 CJ1W-OD212 CJ1W-OD231 CJ1W-OD232 CJ1W-OD233 CJ1W-OD261 CJ1W-OD262 CJ1W-OD263 CJ1W-OC201 CJ1W-OC211 CJ1W-OA201 CJ1W-INT01 CJ1W-IDP01 CJ1W-MD231 CJ1W-MD232 CJ1W-MD233 CJ1W-MD261 CJ1W-MD263 CJ1W-MD563 AC Input p M d l Modules Basic O t t Output Modules Transistor Relayy Triac Interrupt Input Module Pulse Catch Module Mixed Current consumption at 5 V (A) 0.06 0.08 0.09 0.09 0.09 0.09 0.09 0.08 0.09 0.11 0.10 0.10 0.10 0.10 0.14 0.15 0.14 0.17 0.17 0.17 0.09 0.11 0.22 0.08 0.08 0.13 0.13 0.13 0.14 0.14 0.19 Analog g O t t Output Modules CPU Bus Communication Modules Category Name Model CPU Bus Modules Ethernet Module CJ1W-ETN21 Current consumption at 5 V (A) 0.38 Controller Link Module CJ1W-CLK21-V1 0.35 DeviceNet Module CJ1W-DRM21 0.33 ProfiBus-DP M d l Module CJ1W-PRM21 CJ1W-PRT21 CJ1W-SCU41 0.40 0.40 0.38 (See note.) CJ1W-SCU21 0.28 (See note.) Serial Communicati M d l tions Module CompoBus/S CJ1W-SRM21 Master Module 0.15 Note: Add 0.15 A per Module when the NT-AL001-E is connected. 24-Volt Group: CJ1 Series Basic Output Modules Category Name Model Basic Output Modules Relay Output Units CJ1W-OC201 CJ1W-OC211 Programmable Controller Current consumption at 24 V (A) 0.048 (0.006×No. of points ON) 0.096 (0.006×No. of points ON) CJ1 B-111 System Power, Expansion and I/O Allocations I/O Allocations J Overview In CJ1 Series PLCs, I/O memory is allocated based on the following: Basic I/O are automatically assigned words based on position in the rack. In contrast, for Communications and Bus I/O, the user assigns the word allocations within set ranges. J Allocations to Basic I/O Module Groups Allocations to Expansion Racks Basic I/O Modules can be mounted to the CPU Rack and to the Expansion Racks. CPU Rack Allocations I/O allocation to Basic I/O Modules continues from the CPU Rack to the Expansion Racks. Words are allocated from left to right, and each module is allocated as many words as it requires in word units— just like modules in the CPU Rack. A Rack’s first word setting can be changed to any word from CIO 0000 to CIO 9999. Basic I/O Modules on the CPU Rack are allocated words left to right (i.e., from the module nearest the CPU) starting from CIO 0000. Modules are allocated as many words as required in word units. Words can be reserved using CX-Programmer Software. Power Supply Unit Words allocated from the left. End Cover CPU Rack CPU Rack IN 16 IN 16 IN 32 OUT 32 OUT 64 CIO 0000 CIO 0001 CIO 0002 to 0003 CIO 0004 to 0005 CIO 0006 to 0009 Modules with between 1 and 16 I/O points are allocated 1 word (16 bits), and modules having between 17 and 32 I/O points are allocated 2 words (32 bits). For example, 8-point Relay Modules are allocated 1 word, with bits 00 to 07 actually allocated to the I/O points. Programmable Controller CJ1 Words allocated in order from Rack nearest CPU Rack. Power Supply Unit Words allocated from the left. Power Supply Unit CPU Power Supply Unit An example of : words allocated from the left. B-112 CIO 0000 CPU Rack CIO 0000 CPU Power Supply Unit Up to 10 modules can be mounted. 0000 CH CPU Allocated words in the CIO Area: CIO 0000 to CIO 0079 Expansion Rack Expansion Rack System Power, Expansion and I/O Allocations I/O Allocations J CompoBus/S and Special I/O Allocations When allocating I/O in CPU memory, CompoBus/S is considered a Special I/O Module. These modules can be mounted to the CPU Rack and Expansion Racks. Each CompoBus/S Module is allocated ten words in the Special I/O Module Area (CIO 2000 to CIO 2959). Refer to the table provided to the right. Note: During I/O allocation to Basic I/O Modules, Special I/O Modules are ignored. (Slots containing Special I/O Modules are treated as empty slots.) J Allocations for All Networking and Communications Modules — Except CompoBus/S Special I/O Allocations for CompoBus/S Unit number Words allocated 0 CIO 2000 to CIO 2009 1 CIO 2010 to CIO 2019 2 CIO 2020 to CIO 2029 15 CIO 2150 to CIO 2159 95 CIO 2950 to CIO 2959 Allocations for All Networking and Communications Modules — Except Special I/O Unit number Words allocated Each CPU Bus Module is allocated 25 words in the CPU Bus Module Area (CIO 1500 to CIO 1899). 0 CIO 1500 to CIO 1524 1 CIO 1525 to CIO 1549 CPU Bus Modules can be mounted to the CPU Rack or Expansion Racks. 2 CIO 1550 to CIO 1574 Each Module is allocated 25 words in the CPU Bus Module Area according to its unit number, as shown in the table to the right. 15 CIO 1875 to CIO 1899 Note: CPU Bus Modules are ignored during I/O allocation to Basic I/O Modules. The same unit numbers can be used for Special I/O Modules and CPU Bus Modules. Programmable Controller CJ1 B-113 System Power and Expansion Power Supply Units J Features Select the Power Supply Unit to match the current consumption requirements of a Basic Configuration CJ1 Series system or a CPU Rack and Expansion Rack system. • • Choose 100-120 VAC/200-240 VAC or 24 VDC models. Separate RUN output on CJ1W-PA205R Power Supply Unit provides confirmation of operation for troubleshooting and remote diagnostics. Power Supply Units CJ1W-PA205R CJ1W-PA202 CJ1W-PD025 J Specifications Item Specifications Power Supply Unit CJ1W-PA205R Supply voltage 100 to 240 VAC (wide-range), 50/60 Hz 24 VDC Operating voltage and frequency ranges 85 to 264 VAC, 47 to 63 Hz 19.2 to 28.2 VDC Power consumption 100 VA max. 50 VA max. 50 W max. Inrush current (See note 3.) 100 to 120-VAC input: 15 A/8 ms max. (with cold start at room temperature) 100 to 120-VAC input: 20 A/8 ms max.(with cold start at room temperature) At 24 VDC: 30 A/20 ms max. for cold start at room temperature 200 to 240-VAC input: 30 A/8 ms max. (at cold start under room temperature) 200 to 240-VAC input: 40 A/8 ms max. (with cold start at room temperature) Output capacity 5.0 A, 5 VDC (including supply to the CPU); 0.8 A, 24 VDC (total: 25 W max.) 2.8 A, 5 VDC (including supply to the CPU); 0.4 A, 24 VDC (total: 14 W max.) Output terminal Not provided RUN output (See note 2.) Contact configuration: SPST-NO Switching capacity: 250 VAC, 2 A (resistive load) 120 VAC, 0.5 A (inductive load) 24 VDC, 2 A (resistive load) 24 VDC, 2 A (inductive load) Insulation resistance (See note 1.) 20 MΩ min. (at 500 VDC) between AC external and GR terminals 20 MΩ min. (at 500 VDC) between DC external and GR terminals Dielectric strength ((See note 1.)) 2,300 VAC 50/60 Hz for 1 min between AC external and GR terminals Leakage current: 10 mA max. 1,000 VAC 50/60 Hz for 1 min between DC external and GR t i l terminals CJ1W-PA202 CJ1W-PD025 5.0 A, 5 VDC (including supply to CPU); 0.8 A, 24 VDC;(total: 25 W max.) None provided 1,000 VAC 50/60 Hz for 1 min between DC external and GR terminals Leakage current: 10 mA max. Leakage current: 10 mA max. (This table continues on the next page.) Note: 1. Disconnect the Power Supply Unit’s LG terminal from the GR terminal when testing insulation and dielectric strength. Testing the insulation and dielectric strength with the LG terminal and the GR terminals connected will damage internal circuits in the CPU. 2. Supported only when mounted to CPU Rack. 3. These values are based on the condition that the Unit is cold-started at room temperature. Thermistor elements with current suppression characteristics are used in the inrush current limiting circuits provided in the power supply. The inrush current may exceed as much as twice these values if the ambient temperature is high or when the power supply is hot-started with insufficient cooling down time because the thermistors are not sufficiently cooled down. When selecting fuses or breakers for external circuits, ensure a sufficient allowance for fuse or current detection characteristics. B-114 Programmable Controller CJ1 System Power and Expansion Power Supply Units Specifications (continued) Item Specifications Power Supply Unit CJ1W-PA205R Noise immunity Conforms to IEC61000-4-4, 2 kV (power lines) Vibration resistance 10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s2 in X, Y, and Z directions for 80 minutes. (Time coefficient: 8 minutes ×coefficient factor 10 = total time 80 min.) Shock resistance 147 m/s2, 3 times each in X, Y, and Z directions (Relay Output Module: 100 m/s2) Operating temperature 0 to 55_C Operating humidity 10% to 90% (with no condensation) Atmosphere Must be free from corrosive gases. Storage temperature -20 to 75_C (excluding battery) Grounding Less than 100 Ω Enclosure Mounted in a panel. Item Specifications CJ1 Series CPU Rack dimensions Refer to “Dimensions” in the Reference Section of this catalog Dimensions 60 × 90 × 65 mm (W × H × D) power supply only, not including terminal block) Safety measures Conforms to cULus and EC directives. CJ1W-PA202 CJ1W-PD025 Programmable Controller CJ1 B-115 System Power and Expansion CPU Rack Configuration Checklist J CPU Rack Configuration Item Products Requirements CJ1 Series CPU Rack CJ1 Series CPU (Provided with 1 End Cover as a standard accessory.) One of each Module required for every CPU Rack. CJ1 Series Power Supply Unit CJ1 Series Basic I/O Module CJ1 Series Special I/O Module Total number of Modules: 10 Modules max. (M (Mounting ti 11 or more Modules M d l will ill resultlt in i a fatal f t l error.)) CJ1 Series CPU Bus Module End Cover (CJ1W-TER01) Required on the right-hand side of CJ1 Series CPU Racks. (One End Cover is provided with each CPU as a standard accessory. Not mounting an End Cover on the right-hand side of the CPU Rack will result in a fatal error.) Memory Card Install as required. I/O Control Module (CJ1W-IC101) Required for connection to CJ1 Series Expansion Racks. Connect to the right-hand side of the CPU Rack. I/O Connecting Cable Required for connecting CPU Racks to Expansion Racks. J Products Used in CPU Racks Item Model Specifications CJ1 Series CPUs CJ1H-CPU66H I/O bits: 2,560 (3 Expansion Racks), program capacity: 120K steps, LD execution time: 0.02 µs, Data Memory: 256K words (DM: 32K words, EM: 32K words x 7 banks) I/O bits: 2,560 (3 Expansion Racks), program capacity: 60K steps, LD execution time: 0.02 µs, Data Memory: 128K words (DM: 32K words, EM: 32K words x 3 banks) CJ1H-CPU65H CJ1G-CPU45H I/O bits: 1,280 (3 Expansion Racks), program capacity: 60K steps, LD execution time: 0.04 µs, Data Memory: 128K words (DM: 32K words, EM: 32K words x 3 banks) CJ1G-CPU44H I/O bits: 1,280 (3 Expansion Racks), program capacity: 30K steps, LD execution time: 0.04 µs, Data Memory: 64K words (DM: 32K words, EM: 32K words x 1 bank) CJ1G-CPU43H I/O bits: 960 (2 Expansion Racks), program capacity: 20K steps, LD execution time: 0.04 µs, Data Memory: 64K words (DM: 32K words, EM: 32K words x 1 bank) CJ1G-CPU42H I/O bits: 960 (2 Expansion Racks), program capacity: 10K steps, LD execution time: 0.04 µs, Data Memory: 64K words (DM: 32K words, EM: 32K words x 1 bank) CJ1M-CPU23 I/O bits: 640 (1 Expansion Rack), program capacity: 20K steps, LD execution time: 0.1 µs, Data Memory: 32K words, (No EM); built-in I/O: 10 inputs, 6 outputs CJ1M-CPU22 I/O bits: 320 (No Expansion Racks), program capacity: 10K steps, LD execution time: 0.1 µs, Data Memory: 32K words, (No EM); built-in I/O: 10 inputs, 6 outputs I/O bits: 160 (No Expansion Racks), program capacity: 5K steps, LD execution time: 0.1 µs, Data Memory: 32K words, (No EM); built-in I/O: 10 inputs, 6 outputs I/O bits: 640 (1 Expansion Rack), program capacity: 20K steps, LD execution time: 0.1 µs, Data Memory: 32K words, (No EM) CJ1M-CPU21 CJ1M-CPU13 CJ1M-CPU12 CJ1M-CPU11 Battery Set CJ1 Series P Power Supply I/O Control Module CPM2A-BAT01 CJ1W-BAT01 Can be used with CJ1M only. This battery cannot be used for CJ1G/H or CS1 Series PLCs. CJ1W-PA205R CJ1W-PA202 CJ1W-PD025 CJ1W-IC101 100 to 240 VAC (with RUN output); output capacity: 5 A, 5 VDC 100 to 240 VAC; output capacity: 2.8 A, 5 VDC 24 VDC; Output capacity: 5 A, 5 VDC Used to connect a CJ1 Series Expansion Rack to a CJ1 Series CPU Rack. Connect to the right-hand side of the CPU. Connect to an I/O Interface Module mounted on a CJ1 Series Expansion Rack using a CS1/CJ1 Series Connecting Cable. Required on the right-hand side of CJ1 Series CPU Racks. (Not mounting an End Cover on the right-hand side of the CPU Rack will result in a fatal error.) Note: One is provided with CPUs and I/O Interface Modules as a standard accessory. Length: 50 cm; height: 7.3 mm Length: 1 m; height: 7.3 mm Length: 1 m; height: 16 mm There are two locking clips provided with each CPU and I/O Interface Module as standard accessories to secure the Modules on the DIN Track. End Cover CJ1W-TER01 Din Track and d Accessories PFP-50N PFP-100N PFP-100N2 PFP-M B-116 I/O bits: 320 (No Expansion Racks), program capacity: 10K steps, LD execution time: 0.1 µs, Data Memory: 32K words, (No EM) I/O bits: 160 (No Expansion Racks), program capacity: 5K steps, LD execution time: 0.1 µs, Data Memory: 32K words, (No EM) Can also be used with CPM2A and CQM1H PLCs. This battery cannot be used for CS1 Series PLCs. Programmable Controller CJ1 System Power and Expansion Expansion Rack Configuration Checklist J Expansion Rack Configuration CJ1 Series Expansion Racks can be connected to CJ1 Series CPU Racks or other CJ1 Series Expansion Racks. Rack Configuration Requirements CJ1 Series Expansion Rack CJ1 Series Power Supply Unit One of each Module required for every Expansion Rack. Connect Unit the I/O Interface Module to the right of the Power Supply Unit. I/O Interface Module CJ1W-II101 (Provided with 1 End Cover as a standard accessory.) CJ1 Series Basic I/O Module CJ1 Series Special I/O Module Note: An I/O Control Module is required for each CJ1 Series Expansion Rack. Total number of Modules: 10 Modules max. (M (Mounting ti 11 or more Modules M d l will ill resultlt in i a fatal f t l error.)) CJ1 Series CPU Bus Module CS1/CJ1 Series I/O Connecting Cable Required to connect I/O Control Modules to I/O Interface Modules. Note: The total length of CS1/CJ1 Series I/O Connecting Cable used in the system must not exceed 12 m. Correct operation is not ensured if the total cable length exceeds 12 m. J Capacity Overview CPU Models Maximum I/O Modules per CPU (depending on power supply capacity) Maximum I/O Expansion Racks per CPU (depending on power supply capacity) CJ1M-CPU13 CJ1M-CPU23 CJ1G-CPU42H CJ1G-CPU43H CJ1G-CPU44H CJ1G-CPU45H CJ1H-CPU65H CJ1H-CPU66H 20 1 30 2 40 3 J Products Used in Expansion Racks Item Model Specifications Cable Length CJ1 Series Power S Supply l Unit U it CJ1W-PA205R CJ1W-PA202 CJ1W-PD025 CJ1W-II101 100 to 240 VAC (with RUN output), output capacity: 5 A, 5 VDC 100 to 240 VAC, output capacity: 2.8 A, 5 VDC 24 VDC, 5A, 5 VDC One is required for each CJ1 Series Expansion Rack. An End Cover is provided as a standard accessory. (Connect to an I/O Control Module on a CPU Rack or to another I/O Interface Module on an Expansion Rack using CS1/CJ1 Series Connecting Cable.) Required for the right-hand side of CJ1 Series Expansion Racks. One is provided with I/O Interface Modules as a standard. (Not connecting an End Cover will result in a fatal error.) Used to connect I/O / Interface Modules ((CJ1W-II101)) to I/O / Control Modules (CJ1W IC101) or tto other th I/O Interface I t f M d l (CJ1W-IC101) Modules. — I/O Interface Module End Cover CJ1W-TER01 CJ1/CS1 Series / C ti I/O Connecting Cables CS1W-CN313 CS1W-CN713 CS1W-CN223 CS1W-CN323 CS1W-CN523 CS1W-CN133 CS1W-CN133-B2 — — 0.3 m 0.7 m 2m 3m 5m 10 m 12 m Special Ordering Information • • • Order one CJ1W-IC101 I/O Control Module for the CPU rack and one CJ1W-II101 I/O Interface Module for each I/O Expansion rack. Connect the modules with a cable of the appropriate length. The second and third I/O Expansion racks connect between I/O Interface Modules. Programmable Controller CJ1 B-117