CJ1W-OC/OA/OD

CJ-series Output Units
CJ1W-OC/OA/OD
CSM_CJ1W-OUTPUT_DS_E_8_1
A Wide Range of Basic Output
Units for High Speed Output
and Different Applications
• These Output Units receive the results of
output instructions from the CPU Unit and
perform ON/OFF control for external devices.
• High-speed Output models CJ1W-OD213 and
CJ1W-OD234 can help to increase system
throughput.
CJ1W-OD213
CJ1W-OD234
Features
• High-speed output models are available, meeting versatile applications.
ON Response Time: 15μs, OFF Response Time: 80μs
• Output Units are available with any of three output types: relay contact outputs, triac outputs, or transistor outputs.
• For transistor outputs, select from sinking outputs or sourcing outputs.
• Output Units with load short-circuit protection are also available. *1
• Select the best interface for each application: Fujitsu connectors or MIL connectors. *2
• A wide variety of Connector-Terminal Block Conversion Units are available to allow you to easily wire external output devices.
*1. The following Units have load short-circuit protection: CJ1W-OC202, CJ1W-OD204, CJ1W-OD212, and CJ1W-OD232.
*2. Available for models with 32 outputs or 64 outputs
1
CJ1W-OC/OA/OD
Ordering Information
International Standards
• The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2
Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
• Contact your OMRON representative for further details and applicable conditions for these standards.
Output Units
Unit type
Product
name
Specifications
Current
consumption
No. of
(A)
words
allocated
5V
24 V
Model
Output
type
I/O
points
Maximum switching
capacity
Commons
External
connection
−
8
outputs
250 VAC/24 VDC, 2 A
Independen
t contacts
Removable
terminal
block
1 words
0.09
0.048
max.
CJ1W-OC201
−
16
outputs
250 VAC/24 VDC, 2 A
16 points,
1 common
Removable
terminal
block
1 words
0.11
0.096
max.
CJ1W-OC211
−
8
outputs
250 VAC, 0.6 A
8 points,
1 common
Removable
terminal
block
1 words
0.22
−
CJ1W-OA201
Sinking
8
outputs
12 to 24 VDC, 2 A
4 points,
1 common
Removable
terminal
block
1 words
0.09
−
CJ1W-OD201
Sinking
8
outputs
12 to 24 VDC, 0.5 A
8 points,
1 common
Removable
terminal
block
1 words
0.10
−
CJ1W-OD203
Sinking
16
outputs
12 to 24 VDC, 0.5 A
16 points,
1 common
Removable
terminal
block
1 words
0.10
−
CJ1W-OD211
Transistor
Sinking
Output Units
16
outputs
(High
speed)
24 VDC, 0.5 A
16 points,
1 common
Removable
terminal
block
1 words
0.15
−
CJ1W-OD213
Sinking
32
outputs
12 to 24 VDC, 0.5 A
16 points,
1 common
Fujitsu
connector
2 words
0.14
−
CJ1W-OD231
Sinking
32
outputs
12 to 24 VDC, 0.5 A
16 points,
1 common
MIL
connector
2 words
0.14
−
CJ1W-OD233
Sinking
32
outputs
(High
speed)
24 VDC, 0.5 A
16 points,
1 common
MIL
connector
2 words
0.22
−
CJ1W-OD234
Sinking
64
outputs
12 to 24 VDC, 0.3 A
16 points,
1 common
Fujitsu
connector
4 words
0.17
−
CJ1W-OD261
Sinking
64
outputs
12 to 24 VDC, 0.3 A
16 points,
1 common
MIL
connector
4 words
0.17
−
CJ1W-OD263
Sourcing
8
outputs
24 VDC, 2 A
4 points,
Short-circuit protection 1 common
Removable
terminal
block
1 words
0.11
−
CJ1W-OD202
Sourcing
8
outputs
24 VDC, 0.5 A
8 points,
Short-circuit protection 1 common
Removable
terminal
block
1 words
0.10
−
CJ1W-OD204
Sourcing
16
outputs
24 VDC, 0.5 A
16 points,
Short-circuit protection 1 common
Removable
terminal
block
1 words
0.10
−
CJ1W-OD212
Sourcing
32
outputs
24 VDC, 0.5 A
16 points,
Short-circuit protection 1 common
MIL
connector
2 words
0.15
−
CJ1W-OD232
Sourcing
64
outputs
12 to 24 VDC, 0.3 A
16 points,
1 common
MIL
connector
4 words
0.17
−
CJ1W-OD262
Relay
Contact
Output Units
Standards
Triac Output
Unit
CJ1
Basic
I/O Units
UC1, N, L,
CE
N, L, CE
UC1, N, L,
CE
N, L, CE
UC1, N, L,
CE
Accessories
Connectors are not included for models with connectors. Either use one of the applicable connector listed below or use an applicable ConnectorTerminal Block Conversion Unit or I/O Relay Terminal. For details on wiring methods, refer to External Interface.
2
CJ1W-OC/OA/OD
Applicable Connectors
Fujitsu Connectors for 32-input, 32-output, 64-input, 64-output, 32-input/32-output, and 16-input/16-output Units
Name
40-pin
Connectors
24-pin
Connectors
Connection
Remarks
Applicable Units
Soldered
FCN-361J040-AU
FCN-360C040-J2
Connector
Connector Cover
Crimped
FCN-363J040
FCN-363J-AU
FCN-360C040-J2
Housing
Contactor
Connector Cover
Pressure welded
FCN-367J040-AU/F
Soldered
FCN-361J024-AU
FCN-360C024-J2
Connector
Connector Cover
Crimped
FCN-363J024
FCN-363J-AU
FCN-360C024-J2
Socket
Contactor
Connector Cover
Pressure welded
FCN-367J024-AU/F
Model
Fujitsu Connectors:
CJ1W-ID231(32 inputs): 1 per Unit
CJ1W-ID261 (64 inputs): 2 per Unit
CJ1W-OD231 (32 outputs): 1 per Unit
CJ1W-OD261 (64 outputs): 2 per Unit
CJ1W-MD261 (32 inputs, 32 outputs): 2 per Unit
Standards
C500-CE404
C500-CE405
C500-CE403
−
C500-CE241
Fujitsu Connectors:
CJ1W-MD231 (16 inputs, 16 outputs): 2 per Unit
C500-CE242
C500-CE243
MIL Connectors for 32-input, 32-output, 64-input, 64-output, 32-input/32-output, and 16-input/16-output Units
Name
Connection
Pressure welded
Remarks
FRC5-AO40-3TOS
40-pin
Connectors
−
Crimped
20-pin
Connectors
Pressure welded
FRC5-AO20-3TOS
−
Crimped
Applicable Units
Model
MIL Connectors:
CJ1W-ID232/233 (32 inputs): 1 per Unit
CJ1W-OD232/233/234 (32 outputs):1 per Unit
CJ1W-ID262 (64 inputs): 2 per Unit
CJ1W-OD262/263 (64 outputs): 2 per Unit
CJ1W-MD263/563 (32 inputs, 32 outputs): 2 per Unit
Standards
XG4M-4030-T
−
XG5N-401*
XG4M-2030-T
MIL Connectors:
CJ1W-MD232/233 (16 inputs, 16 outputs): 2 per Unit
XG5N-201*
−
* Crimp Contacts are also required. Refer to page 31 for details.
Applicable Connector-Terminal Block Conversion Units
Type
Series
I/O
Number
Wiring method
of poles
Terminal
type
Size
Mounting
Common Bleeder
Indicators
Depth Height Width DIN
Screws terminals resistance
(mm) (mm) (mm) Track
Model
Standards
CJ1W-OD231
XW2R-J34G-C3
CJ1W-OD261
Phillips screw
M3
50
CJ1W-OD232
CJ1W-OD233
CJ1W-OD234 XW2R-J34G-C4
CJ1W-OD262
CJ1W-OD263
48.35 130.7
CJ1W-OD231
XW2R-E34G-C3
CJ1W-OD261
Slotted screw
(rise up)
M3
(European 50
type)
PLCs XW2R Output 34
I/O Units
45.11 98.5
Yes
Yes
No
No
No
CJ1W-OD232
CJ1W-OD233
CJ1W-OD234 XW2R-E34G-C4
CJ1W-OD262
CJ1W-OD263
−
CJ1W-OD231
XW2R-P34G-C3
CJ1W-OD261
Push-in
spring
Clamp
50
45.11 98.5
CJ1W-OD232
CJ1W-OD233
CJ1W-OD234 XW2R-P34G-C4
CJ1W-OD262
CJ1W-OD263
Note: For the combination of Output Units with Connector-Terminal Block Conversion Units, refer to 2. Connecting Connector-Terminal Block
Conversion Units.
3
CJ1W-OC/OA/OD
Applicable I/O Relay Terminals
Size (horizontal
mounting)
Specifications
Type
Series
Classification
Polarity
Relay
outputs
Vertical
type
G70D-V
MOSFET NPN
relay
outputs
Number
of
points
Rated ON
current at
contacts
5A or 3A
16
(SPSTNO × 16) 0.3A
Operation
indicators
Terminal
block for
Horizontal Vertical Height DIN
Screws
power
(mm)
(mm)
(mm) Track
supply
wiring
Yes
Expandable 135
SpaceG70D
saving
Flat
type
G70D
Highcapacity,
G70R
spacesaving
Outputs Relay
outputs
PNP
Outputs
Inputs
MOSFET NPN
relay
outputs
PNP
16
0.3A
(SPSTNO × 16)
Relay
outputs
NPN
8 (SPST10A
NO × 8)
NPN
16
1A
(SPSTNO × 16)
AC
inputs
DC
inputs
8 (SPSTNO × 8)
Standard G7TC
NPN
Outputs
Relay
outputs
PNP
NPN
Highcapacity
socket
G70A
(Socket only)
Relay
Outputs
outputs
PNP
46
81
Yes
Yes
G70D-VFOM16
68
93
44
G70D-SOC08
16
3A
(SPSTNO × 16)
16
(SPST3A
NO × 16)
Standrads
U, C,
CE
−
G70D-SOC16
Yes
−
−
Yes
156
51
Yes
39
G70D-SOC16-1
G70D-FOM16
−
G70D-FOM16-1
Yes
−
136
93
55
Yes
Yes
G70R-SOC08
−
G7TC-IA16
182
G7TC-ID16
Yes
−
16
(SPST5A
NO × 16)
102
85
68
Yes
−
G7TC-OC08
G7TC-OC16
G7TC-OC16-1
10 A
(Terminal
block
No
allowable
current)
U, C
182
16
(SPSTNO × 16)
16
(SPDT ×
16
possible
with G2R
Relays)
Model
G70D-VSOC16
8 (SPST5A
NO × 8)
NPN
Mounting
−
234
75
64
Yes
−
−
G70A-ZOC16-3
(Socket only) +
Relay/SSR/
MOSFET Relay/
Timer
U, C,
G70A-ZOC16-4 CE
(Socket only) +
Relay/SSR/
MOSFET Relay/
Timer
Note: For the combination of Output Units with I/O Relay Terminal and Connecting Cables, refer to 3. Connecting I/O Relay Terminals.
4
CJ1W-OC/OA/OD
Mountable Racks
NJ system
Model
CJ system (CJ1, CJ2)
CPU Rack
Expansion Rack
CPU Rack
Expansion
Backplane
10 Units
10 Units
(Per Expansion
Rack)
10 Units
10 Units
(Per Expansion
Backplane)
CP1H system
NSJ system
CP1H PLC
NSJ Controller
Expansion
Backplane
Not Supported
Not Supported
10 Units
(Per Expansion
Backplane)
CJ1W-OC201
CJ1W-OC211
CJ1W-OA201
CJ1W-OD201
CJ1W-OD203
CJ1W-OD211
CJ1W-OD213
CJ1W-OD231
CJ1W-OD233
CJ1W-OD234
CJ1W-OD261
CJ1W-OD263
CJ1W-OD202
CJ1W-OD204
CJ1W-OD212
CJ1W-OD232
CJ1W-OD262
5
CJ1W-OC/OA/OD
Specifications
CJ1W-OC201 Contact Output Unit (Independent Relays, 8 Points)
Name
8-point Contact Output Unit with Terminal Block (Independent Relays)
Model
CJ1W-OC201
Max. Switching
Capacity
2 A 250 VAC (cosφ = 1), 2 A 250 VAC (cosφ = 0.4), 2 A 24 VDC (16 A/Unit)
Min. Switching
Capacity
1 mA 5 VDC
Relays
NY-24W-K-IE (Fujitsu Takamizawa Components, Ltd.), Cannot be replaced.
Service Life of Relay
Electrical: 150,000 operations (24 VDC, resistive load)/100,000 operations (240 VAC, cosφ = 0.4, inductive load)
Mechanical: 20,000,000 operations
Service life will vary depending on the connected load.
ON Response Time
15 ms max.
OFF Response Time
15 ms max.
Number of Circuits
8 independent contacts
Insulation Resistance
20 MΩ between external terminals and the GR terminal (500 VDC)
Dielectric Strength
2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Internal Current
Consumption
90 mA 5 VDC max.
48 mA 24 VDC max. (6 mA × No. of ON points)
Weight
140 g max.
Signal
name
Circuit Configuration
Internal circuits
Jxx_Ch1_Out00
Jxx_Ch1_Out00
Output indicator
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
Connector pin *
Signal
name
Jxx_Ch1_Out00
Jxx_Ch1_Out01
Jxx_Ch1_Out02
Jxx_Ch1_Out03
Jxx_Ch1_Out04
Jxx_Ch1_Out05
External connection
and terminal-device
variable diagram
Jxx_Ch1_Out06
Jxx_Ch1_Out07
NC
A0
A1
A2
B0 Jxx_Ch1_Out00
L
B1 Jxx_Ch1_Out01
L
B2 Jxx_Ch1_Out02
L
Jxx_Ch1_Out03
L
B4 Jxx_Ch1_Out04
L
Jxx_Ch1_Out05
L
B6 Jxx_Ch1_Out06
L
B7 Jxx_Ch1_Out07
L
A3
B3
A4
A5
B5
A6
A7
A8
B8
2A
2A
Signal
name
NC
250 VAC,
24 VDC max.
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
• The input power supply polarity can be connected in either direction.
* Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on
the Units.
Note: Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O.
6
CJ1W-OC/OA/OD
CJ1W-OC211 Contact Output Unit (16 Points)
Name
16-point Contact Output Unit with Terminal Block
Model
CJ1W-OC211
Max. Switching
Capacity
2 A 250 VAC (cosφ = 1), 2 A 250 VAC (cosφ = 0.4), 2 A 24 VDC (8 A/Unit)
Min. Switching
Capacity
1 mA 5 VDC
Relays
NY-24W-K-IE (Fujitsu Takamizawa Components, Ltd.), Cannot be replaced.
Service Life of Relay
Electrical: 150,000 operations (24 VDC, resistive load)/ 100,000 operations (250 VAC, cosφ = 0.4, inductive load)
Mechanical: 20,000,000 operations
Service life will vary depending on the connected load.
ON Response Time
15 ms max.
OFF Response Time
15 ms max.
Number of Circuits
16 points/common, 1 circuit
Insulation Resistance
20 MΩ between external terminals and the GR terminal (500 VDC)
Dielectric Strength
2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Internal Current
Consumption
110 mA 5 VDC max.
96 mA 24 VDC max. (6 mA × No. of ON points)
Weight
170 g max.
Signal
name
Jxx_Ch1_Out00
to
Circuit Configuration
Internal circuits
Jxx_Ch1_Out15
COM
COM
Output indicator
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
Connector pin *
Signal
name
External connection
and terminal-device
variable diagram
L
Jxx_Ch1_Out00
A0
L
Jxx_Ch1_Out02
A1
L
Jxx_Ch1_Out04
L
Jxx_Ch1_Out06
L
Jxx_Ch1_Out08
L
L
L
2A
2A
250 VAC,
24 VDC max.
Jxx_Ch1_Out10
Jxx_Ch1_Out12
Jxx_Ch1_Out14
COM
B0
B1
A2
B2
A3
B3
A4
B4
A5
B5
A6
B6
A7
B7
A8
B8
Signal
name
Jxx_Ch1_Out01
L
Jxx_Ch1_Out03
L
Jxx_Ch1_Out05
L
Jxx_Ch1_Out07
L
Jxx_Ch1_Out09
L
Jxx_Ch1_Out11
L
Jxx_Ch1_Out13
L
Jxx_Ch1_Out15
L
COM
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
* Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on
the Units.
7
CJ1W-OC/OA/OD
CJ1W-OA201 Triac Output Unit (8 Points)
Name
8-point Triac Output Unit with Terminal Block
Model
CJ1W-OA201
Max. Switching
Capacity
0.6 A 250 VAC, 50/60 Hz (2.4 A/Unit)
Max. Inrush Current
15 A (pulse width: 10 ms max.)
Min. Switching
Capacity
50 mA 75 VAC
Leakage Current
1.5 mA (200 VAC) max.
Residual Voltage
1.6 VAC max.
ON Response Time
1 ms max.
OFF Response Time
1/2 of load frequency + 1 ms or less.
Number of Circuits
8 (8 points/common, 1 circuit)
Surge Protector
C.R Absorber + Surge Absorber
Fuses
5 A (1/common, 1 used)
The fuse cannot be replaced by the user.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (500 VDC)
Dielectric Strength
2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Internal Current
Consumption
220 mA max.
Weight
150 g max.
Signal
name
Internal circuits
Output indicator
Circuit Configuration
Jxx_Ch1_Out00
to
Jxx_Ch1_Out07
COM
Fuse
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
Signal
name
Connector pin *
NC
A0
B0
NC
A1
Jxx_Ch1_Out00
L
Jxx_Ch1_Out01
L
Jxx_Ch1_Out02
L
Jxx_Ch1_Out03
L
B1
NC
A2
B2
External connection
and terminal-device
variable diagram
NC
A3
NC
A4
B3
Jxx_Ch1_Out04
B4
NC
A5
Jxx_Ch1_Out05
L
Jxx_Ch1_Out06
L
Jxx_Ch1_Out07
L
B5
NC
A6
B6
NC
A7
B7
NC
A8
L
250 VAC max.
COM
B8
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
* Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on
the Units.
Note: Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O.
8
CJ1W-OC/OA/OD
CJ1W-OD201 Transistor Output Unit (8 Points)
Name
8-point Transistor Output Unit with Terminal Block (Sinking Outputs)
Model
CJ1W-OD201
Rated Voltage
12 to 24 VDC
Operating Load
Voltage Range
10.2 to 26.4 VDC
Maximum Load
Current
2.0 A/point, 8.0 A/Unit
Maximum Inrush
Current
10 A/point, 10 ms max.
Leakage Current
0.1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
0.5 ms max.
OFF Response Time
1.0 ms max.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Number of Circuits
8 (4 points/common, 2 circuits)
Internal Current
Consumption
90 mA max.
Fuse
6.3 A (1/common, 2 used)
The fuse cannot be replaced by the user.
External Power
Supply
12 to 24 VDC, 10 mA min.
Weight
110 g max.
Signal name
+V
Jxx_Ch1_Out00
to
Circuit Configuration
Internal circuits
Jxx_Ch1_Out03
Fuse
COM0
Output indicator
+V
Jxx_Ch1_Out04
to
Jxx_Ch1_Out07
Fuse
COM1
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
Connector pin *
Signal
name
L
L
Jxx_Ch1_Out00
A0
B0
Jxx_Ch1_Out02
A1
B1
NC
12 to 24 VDC
A2
B2
COM0
A3
B3
NC
External connection
and terminal-device
variable diagram
A4
B4
L
Jxx_Ch1_Out04
L
Jxx_Ch1_Out06
A5
B5
A6
B6
NC
12 to 24 VDC
COM1
A7
B7
A8
B8
Signal
name
Jxx_Ch1_Out01
L
Jxx_Ch1_Out03
L
NC
+V
NC
Jxx_Ch1_Out05
L
Jxx_Ch1_Out07
L
NC
+V
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed.
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
* Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on
the Units.
Note: Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O.
9
CJ1W-OC/OA/OD
CJ1W-OD203 Transistor Output Unit (8 Points)
Name
8-point Transistor Output Unit with Terminal Block (Sinking Outputs)
Model
CJ1W-OD203
Rated Voltage
12 to 24 VDC
Operating Load
Voltage Range
10.2 to 26.4 VDC
Maximum Load
Current
0.5 A/point, 4.0 A/Unit
Maximum Inrush
Current
4.0 A/point, 10 ms max.
Leakage Current
0.1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
0.1 ms max.
OFF Response Time
0.8 ms max.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Number of Circuits
8 (8 points/common, 1 circuit)
Internal Current
Consumption
100 mA max.
Fuse
None
External Power
Supply
10.2 to 26.4 VDC, 20 mA min.
Weight
110 g max.
Signal
name
Circuit Configuration
Internal circuits
Output indicator
+V
Jxx_Ch1_Out00
to
Jxx_Ch1_Out07
COM
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
Signal
name
External connection
and terminal-device
variable diagram
Connector pin *
L Jxx_Ch1_Out00 A0
L Jxx_Ch1_Out02 A1
L Jxx_Ch1_Out04 A2
L Jxx_Ch1_Out06 A3
NC
A4
NC
A5
NC
A6
NC
12 to 24 VDC
A7
COM
A8
B0
B1
B2
B3
B4
B5
B6
B7
B8
Signal
name
Jxx_Ch1_Out01 L
Jxx_Ch1_Out03 L
Jxx_Ch1_Out05 L
Jxx_Ch1_Out07 L
NC
NC
NC
NC
+V
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed.
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
* Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on
the Units.
Note: Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O.
10
CJ1W-OC/OA/OD
CJ1W-OD211 Transistor Output Unit (16 Points)
Name
16-point Transistor Output Unit with Terminal Block (Sinking Outputs)
Model
CJ1W-OD211
Rated Voltage
12 to 24 VDC
Operating Load
Voltage Range
10.2 to 26.4 VDC
Maximum Load
Current
0.5 A/point, 5.0 A/Unit
Maximum Inrush
Current
4.0 A/point, 10 ms max.
Leakage Current
0.1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
0.1 ms max.
OFF Response Time
0.8 ms max.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Number of Circuits
16 (16 points/common, 1 circuit)
Internal Current
Consumption
5 VDC 100 mA max.
Fuse
None
External Power
Supply
10.2 to 26.4 VDC, 20 mA min.
Weight
110 g max.
Circuit Configuration
Internal circuits
Signal
name
Output indicator
+V
Jxx_Ch1_Out00
to
Jxx_Ch1_Out15
COM
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
Connector pin *
Signal
name
L
L
L
External connection
and terminal-device
variable diagram
Jxx_Ch1_Out00
Jxx_Ch1_Out02
Jxx_Ch1_Out04
L
Jxx_Ch1_Out06
L
Jxx_Ch1_Out08
L
Jxx_Ch1_Out10
L
Jxx_Ch1_Out12
L
Jxx_Ch1_Out14
COM
12 to 24 VDC
A0
B0
A1
B1
A2
B2
A3
B3
A4
B4
A5
B5
A6
B6
A7
B7
A8
B8
Signal
name
Jxx_Ch1_Out01
Jxx_Ch1_Out03
Jxx_Ch1_Out05
Jxx_Ch1_Out07
Jxx_Ch1_Out09
Jxx_Ch1_Out11
Jxx_Ch1_Out13
Jxx_Ch1_Out15
L
L
L
L
L
L
L
L
+V
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed.
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
* Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on
the Units.
11
CJ1W-OC/OA/OD
CJ1W-OD213 Transistor Output Unit (16 Points)
Name
16-point Transistor Output Unit with Terminal Block (Sinking Outputs)
Model
CJ1W-OD213
Rated Voltage
24 VDC
Operating Load
Voltage Range
20.4 to 26.4 VDC
Maximum Load
Current
0.5 A/point, 5.0 A/Unit
Maximum Inrush
Current
4.0 A/point, 10 ms max.
Leakage Current
0.1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
15 μs max.
OFF Response Time
80 μs max.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Number of Circuits
16 (16 points/common, 1 circuit)
Internal Current
Consumption
5 VDC 150 mA max.
Fuse
None
External Power
Supply
20.4 to 26.4 VDC, 55 mA min.
Weight
110 g max.
Signal
name
+V
Jxx_Ch1_Out00
Internal circuits
Circuit Configuration
to
Jxx_Ch1_Out15
COM
Output indicator
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
Connector pin *
Signal
name
L
L
L
External connection
and terminal-device
variable diagram
Jxx_Ch1_Out00
Jxx_Ch1_Out02
Jxx_Ch1_Out04
L
Jxx_Ch1_Out06
L
Jxx_Ch1_Out08
L
Jxx_Ch1_Out10
L
Jxx_Ch1_Out12
L
Jxx_Ch1_Out14
COM
24 VDC
A0
B0
A1
B1
A2
B2
A3
B3
A4
B4
A5
B5
A6
B6
A7
B7
A8
B8
Signal
name
Jxx_Ch1_Out01
Jxx_Ch1_Out03
Jxx_Ch1_Out05
Jxx_Ch1_Out07
Jxx_Ch1_Out09
Jxx_Ch1_Out11
Jxx_Ch1_Out13
Jxx_Ch1_Out15
L
L
L
L
L
L
L
L
+V
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed.
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
* Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on
the Units.
12
CJ1W-OC/OA/OD
CJ1W-OD231 Transistor Output Unit (32 Points)
Name
Model
Rated Voltage
Operating Load
Voltage Range
Maximum Load
Current
Maximum Inrush
Current
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
Insulation Resistance
Dielectric Strength
Number of Circuits
Internal Current
Consumption
Fuse
External Power
Supply
Weight
Accessories
32-point Transistor Output Unit with Fujitsu Connector (Sinking Outputs)
CJ1W-OD231
12 to 24 VDC
10.2 to 26.4 VDC
0.5 A/point, 2.0 A/common, 4.0 A/Unit
4.0 A/point, 10 ms max.
0.1 mA max.
1.5 V max.
0.1 ms max.
0.8 ms max.
20 MΩ between the external terminals and the GR terminal (100 VDC)
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
32 (16 points/common, 2 circuits)
5 VDC 140 mA max.
None
10.2 to 26.4 VDC, 30 mA min.
70 g max.
None
Signal
name
Allocated
CIO word
+V
Jxx_Ch1_Out00
to
Wd m
Connector
row A
Wd m+1
Connector
row B
Internal circuits
Jxx_Ch1_Out15
Circuit Configuration
Output indicator
COM0
COM0
SW
+V
Jxx_Ch2_Out00
to
Jxx_Ch2_Out15
COM1
COM1
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
Allocated
CIO word
Wd m
External connection
and terminal-device
variable diagram
Wd m
•
•
•
•
•
•
12 to
24 VDC
ConnecSignal
Signal
tor pin
name
name
L Jxx_Ch1_Out00 A1 B1 Jxx_Ch2_Out00 L
Jxx_Ch1_Out01
Jxx_Ch2_Out01
A2 B2
L
L
L Jxx_Ch1_Out02 A3 B3 Jxx_Ch2_Out02 L
L Jxx_Ch1_Out03 A4 B4 Jxx_Ch2_Out03 L
L Jxx_Ch1_Out04 A5 B5 Jxx_Ch2_Out04 L
L Jxx_Ch1_Out05 A6 B6 Jxx_Ch2_Out05 L
Jxx_Ch2_Out06
Jxx_Ch1_Out06
L
A7 B7
L
Jxx_Ch2_Out07
Jxx_Ch1_Out07
L
A8 B8
L
COM1
COM0
A9 B9
+V
+V
A10 B10
Jxx_Ch1_Out08
Jxx_Ch2_Out08
L
A11 B11
L
Jxx_Ch1_Out09
Jxx_Ch2_Out09
A12 B12
L
L
L Jxx_Ch1_Out10 A13 B13 Jxx_Ch2_Out10 L
L Jxx_Ch1_Out11 A14 B14 Jxx_Ch2_Out11 L
Jxx_Ch1_Out12
Jxx_Ch2_Out12
L
L
A15 B15
Jxx_Ch2_Out13
Jxx_Ch1_Out13
L
A16 B16
L
Jxx_Ch2_Out14
Jxx_Ch1_Out14
L
A17 B17
L
L Jxx_Ch1_Out15 A18 B18 Jxx_Ch2_Out15 L
COM1
COM0
A19 B19
+V
+V
A20 B20
Allocated
CIO word
12 to
24 VDC
Wd m+1
Wd m+1
When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed.
Be sure to wire both terminals A9 and A19 (COM0).
Be sure to wire both terminals B9 and B19 (COM1).
Be sure to wire both terminals A10 and A20 (+V).
Be sure to wire both terminals B10 and B20 (+V).
The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
13
CJ1W-OC/OA/OD
CJ1W-OD233 Transistor Output Unit (32 Points)
Name
Model
Rated Voltage
Operating Load
Voltage Range
Maximum Load
Current
Maximum Inrush
Current
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
Insulation Resistance
Dielectric Strength
Number of Circuits
Internal Current
Consumption
Fuse
External Power
Supply
Weight
32-point Transistor Output Unit with MIL Connector (Sinking Outputs)
CJ1W-OD233
12 to 24 VDC
10.2 to 26.4 VDC
0.5 A/point, 2 A/common, 4 A/Unit
4.0 A/point, 10 ms max.
0.1 mA max.
1.5 V max.
0.1 ms max.
0.8 ms max.
20 MΩ between the external terminals and the GR terminal (100 VDC)
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
32 (16 points/common, 2 circuits)
140 mA max.
None
12 to 24 VDC, 30 mA min.
70 g max.
Signal
name
Allocated
CIO word
+V
Internal circuits
Jxx_Ch1_Out00
to
Jxx_Ch1_Out15
Circuit Configuration
Wd m
COM0
COM0
Output indicator
SW
+V
Jxx_Ch2_Out00
to
Jxx_Ch2_Out15
Wd m+1
COM1
COM1
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
Connector pin
12 to
24 VDC
+V
COM1
L
L
Wd m+1
L
L
L
L
L
L
Jxx_Ch2_Out15
Jxx_Ch2_Out14
Jxx_Ch2_Out13
Jxx_Ch2_Out12
Jxx_Ch2_Out11
Jxx_Ch2_Out10
Jxx_Ch2_Out09
Jxx_Ch2_Out08
+V
COM0
External connection
and terminal-device
variable diagram
L
L
Wd m
L
L
L
L
12 to
24 VDC
•
•
•
•
•
•
L
L
Jxx_Ch1_Out15
Jxx_Ch1_Out14
Jxx_Ch1_Out13
Jxx_Ch1_Out12
Jxx_Ch1_Out11
Jxx_Ch1_Out10
Jxx_Ch1_Out09
Jxx_Ch1_Out08
1 2
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
25 26
27 28
29 30
31 32
33 34
35 36
37 38
39 40
Signal
name
Allocated
CIO word
+V
COM1
Jxx_Ch2_Out07
Jxx_Ch2_Out06
Jxx_Ch2_Out05
Jxx_Ch2_Out04
Jxx_Ch2_Out03
Jxx_Ch2_Out02
Jxx_Ch2_Out01
Jxx_Ch2_Out00
L
L
L
L
L
Wd m+1
Signal
name
L
L
L
+V
COM0
Jxx_Ch1_Out07
Jxx_Ch1_Out06
Jxx_Ch1_Out05
Jxx_Ch1_Out04
Jxx_Ch1_Out03
Jxx_Ch1_Out02
Jxx_Ch1_Out01
Jxx_Ch1_Out00
L
L
L
L
L
Wd m
Allocated
CIO word
L
L
L
When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed.
Be sure to wire both terminals 23 and 24 (COM0).
Be sure to wire both terminals 3 and 4 (COM1).
Be sure to wire both terminals 21 and 22 (+V).
Be sure to wire both terminals 1 and 2 (+V).
The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
14
CJ1W-OC/OA/OD
CJ1W-OD234 Transistor Output Unit (32 Points)
Name
Model
Rated Voltage
Operating Load
Voltage Range
Maximum Load
Current
Maximum Inrush
Current
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
Insulation Resistance
Dielectric Strength
Number of Circuits
Internal Current
Consumption
Fuse
External Power
Supply
Weight
32-point Transistor Output Unit with MIL Connector (Sinking Outputs)
CJ1W-OD234
24 VDC
20.4 to 26.4 VDC
0.5 A/point, 2 A/common, 4 A/Unit
4.0 A/point, 10 ms max.
0.1 mA max.
1.5 V max.
15 μs max.
80 μs max.
20 MΩ between the external terminals and the GR terminal (100 VDC)
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
32 (16 points/common, 2 circuits)
220 mA max.
None
20.4 to 26.4 VDC, 110 mA min.
70 g max.
Signal name
+V
Jxx_Ch1_Out00
Allocated
CIO word
Wd m
to
Jxx_Ch1_Out15
Internal circuits
COM0
COM0
Circuit Configuration
Output indicator
SW
+V
Jxx_Ch2_Out00
Wd m+1
to
Jxx_Ch2_Out15
COM1
COM1
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
L
L
L
L
L
L
L
L
Jxx_Ch2_Out15
Jxx_Ch2_Out14
Jxx_Ch2_Out13
Jxx_Ch2_Out12
Jxx_Ch2_Out11
Jxx_Ch2_Out10
Jxx_Ch2_Out09
Jxx_Ch2_Out08
+V
COM0
External connection
and terminal-device
variable diagram
L
L
Wd m
L
L
L
L
L
24 VDC
•
•
•
•
•
•
L
Jxx_Ch1_Out15
Jxx_Ch1_Out14
Jxx_Ch1_Out13
Jxx_Ch1_Out12
Jxx_Ch1_Out11
Jxx_Ch1_Out10
Jxx_Ch1_Out09
Jxx_Ch1_Out08
1 2
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
25 26
27 28
29 30
31 32
33 34
35 36
37 38
39 40
+V
COM1
Jxx_Ch2_Out07
Jxx_Ch2_Out06
Jxx_Ch2_Out05
Jxx_Ch2_Out04
Jxx_Ch2_Out03
Jxx_Ch2_Out02
Jxx_Ch2_Out01
Jxx_Ch2_Out00
L
L
L
L
L
Wd m+1
+V
COM1
Allocated
CIO word
Signal
name
L
L
L
+V
COM0
Jxx_Ch1_Out07
Jxx_Ch1_Out06
Jxx_Ch1_Out05
Jxx_Ch1_Out04
Jxx_Ch1_Out03
Jxx_Ch1_Out02
Jxx_Ch1_Out01
Jxx_Ch1_Out00
L
L
L
L
L
Wd m
24 VDC
Wd m+1
Connector pin
Signal
name
Allocated
CIO word
L
L
L
When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed.
Be sure to wire both terminals 23 and 24 (COM0).
Be sure to wire both terminals 3 and 4 (COM1).
Be sure to wire both terminals 21 and 22 (+V).
Be sure to wire both terminals 1 and 2 (+V).
The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
15
CJ1W-OC/OA/OD
CJ1W-OD261 Transistor Output Unit (64 Points)
Name
64-point Transistor Output Unit with Fujitsu Connectors (Sinking Outputs)
Model
CJ1W-OD261
Rated Voltage
12 to 24 VDC
Operating Load
Voltage Range
10.2 to 26.4 VDC
Maximum Load
Current
0.3 A/point, 1.6 A/common, 6.4 A/Unit
Maximum Inrush
Current
3.0 A/point, 10 ms max.
Leakage Current
0.1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
0.5 ms max.
OFF Response Time
1.0 ms max.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Number of Circuits
64 (16 points/common, 4 circuits)
Internal Current
Consumption
5 VDC, 170 mA max.
Fuse
None
External Power
Supply
10.2 to 26.4 VDC, 50 mA min.
Weight
110 g max.
Accessories
None
Signal name
Allocated
CIO word
Circuit Configuration
Internal circuits
+V
SW
Output indicator
Jxx_Ch1_Out00
to
Jxx_Ch1_Out15
COM0
COM0
+V
Jxx_Ch2_Out00
to
Jxx_Ch2_Out15
COM1
COM1
+V
Jxx_Ch3_Out00
to
Jxx_Ch3_Out15
COM2
COM2
+V
Jxx_Ch4_Out00
to
Jxx_Ch4_Out15
COM3
COM3
Wd m
Connector
row A
CN1
Wd m+1
Connector
row B
Connector
row A
Wd m+2
Connector
row B
CN2
Wd m+3
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
16
CJ1W-OC/OA/OD
Jxx_Ch2_Out14
Wd m+1
L
L
B17 A17
Jxx_Ch2_Out12
L
Jxx_Ch2_Out10
L
Jxx_Ch2_Out09
Jxx_Ch2_Out08
+V
External connection
and terminal-device
variable diagram
COM1
L
Jxx_Ch2_Out07
L
Jxx_Ch2_Out06
L
Jxx_Ch2_Out05
12 to
24
VDC
L
L
L
L
L
Jxx_Ch1_Out14
Jxx_Ch2_Out04
Jxx_Ch2_Out03
Jxx_Ch2_Out02
Jxx_Ch2_Out01
Jxx_Ch2_Out00
L
L
L
L
Jxx_Ch1_Out12
L
B14 A14
12 to
24
VDC
L
L
L
L
L
Jxx_Ch1_Out11
Jxx_Ch2_Out11
L
Jxx_Ch1_Out15
Jxx_Ch1_Out13
B15 A15
L
COM0
B16 A16
Jxx_Ch2_Out13
L
Wd m+1
B18 A18
L
+V
Wd m+2
L
Jxx_Ch2_Out15
B19 A19
B13 A13
B12 A12
B11 A11
B10 A10
B9 A9
B8 A8
B7 A7
B6 A6
Jxx_Ch1_Out10
Jxx_Ch1_Out09
Jxx_Ch1_Out08
L
L
COM0
L
L
Jxx_Ch1_Out07
L
Jxx_Ch1_Out06
L
Jxx_Ch1_Out05
Jxx_Ch1_Out04
B4 A4
Jxx_Ch1_Out03
Jxx_Ch1_Out02
B2 A2
Jxx_Ch1_Out01
B1 A1
Jxx_Ch1_Out00
L
Jxx_Ch3_Out01
Jxx_Ch3_Out02
Jxx_Ch3_Out03
Jxx_Ch3_Out04
Jxx_Ch3_Out05
Jxx_Ch3_Out06
Jxx_Ch3_Out07
+V
L
L
Jxx_Ch3_Out00
COM2
L
+V
B5 A5
B3 A3
L
L
Wd m+2
COM1
L
B20 A20
Connector pin
Signal
name
Allocated
CIO word
Allocated
CIO word
Wd m
+V
Signal
name
12 to
24
VDC
L
L
L
• When wiring, pay careful attention to the polarity of the external
power supply. The load may operate incorrectly if the polarity is
reversed.
• Be sure to wire both terminals A9 and A19 (COM0) of CN1.
• Be sure to wire both terminals B9 and B19 (COM1) of CN1.
• Be sure to wire both terminals A10 and A20 (+V) of CN1.
• Be sure to wire both terminals B10 and B20 (+V) of CN1.
• The signal names of the terminals are the device variable
names.The device variable names are the names that use "Jxx" as
the device name.
L
L
L
L
L
Jxx_Ch3_Out08
Jxx_Ch3_Out09
Jxx_Ch3_Out10
Jxx_Ch3_Out11
Jxx_Ch3_Out12
Jxx_Ch3_Out13
Jxx_Ch3_Out14
Jxx_Ch3_Out15
COM2
+V
A1 B1
A2 B2
A3 B3
A4 B4
A5 B5
A6 B6
A7 B7
A8 B8
A9 B9
A10 B10
A11 B11
A12 B12
A13 B13
A14 B14
A15 B15
A16 B16
A17 B17
A18 B18
A19 B19
A20 B20
Signal
name
Jxx_Ch4_Out00
Jxx_Ch4_Out01
Jxx_Ch4_Out02
Jxx_Ch4_Out03
Jxx_Ch4_Out04
Jxx_Ch4_Out05
Jxx_Ch4_Out06
Jxx_Ch4_Out07
Allocated
CIO word
L
L
L
L
L
12 to
24
VDC
Wd m+3
Connector pin
Signal
name
Wd m
Allocated
CIO word
CN2
L
L
L
COM3
+V
Jxx_Ch4_Out08
Jxx_Ch4_Out09
Jxx_Ch4_Out10
Jxx_Ch4_Out11
Jxx_Ch4_Out12
Jxx_Ch4_Out13
Jxx_Ch4_Out14
Jxx_Ch4_Out15
L
L
L
L
L
Wd m+3
CN1
L
L
L
COM3
+V
• When wiring, pay careful attention to the polarity of the external
power supply. The load may operate incorrectly if the polarity is
reversed.
• Be sure to wire both terminals A9 and A19 (COM2) of CN2.
• Be sure to wire both terminals B9 and B19 (COM3) of CN2.
• Be sure to wire both terminals A10 and A20 (+V) of CN2.
• Be sure to wire both terminals B10 and B20 (+V) of CN2.
• The signal names of the terminals are the device variable
names.The device variable names are the names that use "Jxx" as
the device name.
17
CJ1W-OC/OA/OD
CJ1W-OD263 Transistor Output Unit (64 Points)
Name
64-point Transistor Output Unit with MIL Connectors (Sinking Outputs)
Model
CJ1W-OD263
Rated Voltage
12 to 24 VDC
Operating Load
Voltage Range
10.2 to 26.4 VDC
Maximum Load
Current
0.3 A/point, 1.6 A/common, 6.4 A/Unit
Maximum Inrush
Current
3.0 A/point, 10 ms max.
Leakage Current
0.1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
0.5 ms max.
OFF Response Time
1.0 ms max.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Number of Circuits
64 (16 points/common, 4 circuits)
Internal Current
Consumption
170 mA max.
Fuse
None
External Power
Supply
12 to 24 VDC, 50 mA min.
Weight
110 g max.
Signal
name
Allocated
CIO word
Circuit Configuration
Internal circuits
+V
SW
Output indicator
Jxx_Ch1_Out00
to
Jxx_Ch1_Out15
COM0
COM0
+V
Jxx_Ch2_Out00
to
Jxx_Ch2_Out15
COM1
COM1
+V
Jxx_Ch3_Out00
to
Jxx_Ch3_Out15
COM2
COM2
+V
Jxx_Ch4_Out00
to
Jxx_Ch4_Out15
COM3
COM3
Wd m
CN1
Wd m+1
Wd m+2
CN2
Wd m+3
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
18
CJ1W-OC/OA/OD
Jxx_Ch1_Out01
L
Jxx_Ch1_Out02
L
Jxx_Ch1_Out03
L
Jxx_Ch1_Out04
L
Jxx_Ch1_Out05
L
Jxx_Ch1_Out06
L
Jxx_Ch1_Out07
COM0
External connection
and terminal-device
variable diagram
Wd m+1
+V
L
Jxx_Ch2_Out00
L
Jxx_Ch2_Out01
L
Jxx_Ch2_Out02
L
Jxx_Ch2_Out03
L
Jxx_Ch2_Out04
L
Jxx_Ch2_Out05
L
Jxx_Ch2_Out06
L
Jxx_Ch2_Out07
COM1
+V
40 39
38 37
36 35
34 33
32 31
30 29
28 27
26 25
24 23
22 21
Jxx_Ch1_Out08
Jxx_Ch1_Out09
Jxx_Ch1_Out10
Jxx_Ch1_Out11
Jxx_Ch1_Out12
Jxx_Ch1_Out13
Jxx_Ch1_Out14
Jxx_Ch1_Out15
L
L
L
12 to
24
VDC
L
L
L
L
L
L
L
L
L
L
L
COM0
L
+V
L
20 19
Jxx_Ch2_Out08
L
18 17
Jxx_Ch2_Out09
L
16 15
Jxx_Ch2_Out10
L
14 13
Jxx_Ch2_Out11
L
12 11
Jxx_Ch2_Out12
L
10 9
Jxx_Ch2_Out13
L
8
7
Jxx_Ch2_Out14
L
6
5
Jxx_Ch2_Out15
L
4
3
2
1
Jxx_Ch4_Out15
Jxx_Ch4_Out14
Jxx_Ch4_Out13
Jxx_Ch4_Out12
Jxx_Ch4_Out11
Jxx_Ch4_Out10
Jxx_Ch4_Out09
Jxx_Ch4_Out08
+V
1
2
3
4
5
6
7
8
Signal
name
Allocated
CIO word
+V
COM3
9 10
11 12
13 14
15 16
17 18
19 20
21 22
COM2
Jxx_Ch4_Out07
Jxx_Ch4_Out06
Jxx_Ch4_Out05
Jxx_Ch4_Out04
Jxx_Ch4_Out03
Jxx_Ch4_Out02
Jxx_Ch4_Out01
Jxx_Ch4_Out00
L
L
L
L
L
L
L
L
+V
COM2
23 24
Jxx_Ch3_Out15
L
L
Jxx_Ch3_Out14
Jxx_Ch3_Out13
L
Jxx_Ch3_Out12
L
L
Jxx_Ch3_Out11
Jxx_Ch3_Out10
L
COM1
+V
+V
COM3
Wd m+3
Jxx_Ch1_Out00
L
Connector pin
Signal
name
Allocated
CIO word
12 to
24
VDC
Wd m+2
L
Allocated
CIO word
Signal
name
12 to
24
VDC
• When wiring, pay careful attention to the polarity of the external
power supply. The load may operate incorrectly if the polarity is
reversed.
• Be sure to wire both terminals 23 and 24 (COM0) of CN1.
• Be sure to wire both terminals 3 and 4 (COM1) of CN1.
• Be sure to wire both terminals 21 and 22 (+V) of CN1.
• Be sure to wire both terminals 1 and 2 (+V) of CN1.
• The signal names of the terminals are the device variable
names.The device variable names are the names that use "Jxx" as
the device name.
12 to
24
VDC
Jxx_Ch3_Out09
L
L
Jxx_Ch3_Out07
25 26
L
Jxx_Ch3_Out06
L
27 28
Jxx_Ch3_Out05
L
29 30
Jxx_Ch3_Out04
L
31 32
Jxx_Ch3_Out03
L
33 34
Wd m+2
Connector pin
Wd m
Signal
name
Wd m+1
Wd m
Allocated
CIO word
CN2
Wd m+3
CN1
Jxx_Ch3_Out02
35 36
L
Jxx_Ch3_Out01
L
37 38
Jxx_Ch3_Out00
Jxx_Ch3_Out08
39 40
L
• When wiring, pay careful attention to the polarity of the external
power supply. The load may operate incorrectly if the polarity is
reversed.
• Be sure to wire both terminals 23 and 24 (COM2) of CN2.
• Be sure to wire both terminals 3 and 4 (COM3) of CN2.
• Be sure to wire both terminals 21 and 22 (+V) of CN2.
• Be sure to wire both terminals 1 and 2 (+V) of CN2.
• The signal names of the terminals are the device variable
names.The device variable names are the names that use "Jxx" as
the device name.
19
CJ1W-OC/OA/OD
CJ1W-OD202 Transistor Output Unit (8 Points)
Name
8-point Transistor Output Unit with Terminal Block (Sourcing Outputs)
Model
CJ1W-OD202
Rated Voltage
24 VDC
Operating Load
Voltage Range
20.4 to 26.4 VDC
Maximum Load
Current
2 A/point, 8 A/Unit
Leakage Current
0.1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
0.5 ms max.
OFF Response Time
1.0 ms max.
Load Short-circuit
Protection
Detection current: 6 A min.
Automatic restart after error clearance.
Line Disconnection
Detection
Detection current: 200 mA
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Number of Circuits
8 (4 points/common, 2 circuits)
Internal Current
Consumption
110 mA max.
Fuse
None
External Power
Supply
24 VDC, 50 mA min.
Weight
120 g max.
Signal name
Jxx_Ch1_Out00
to
Jxx_Ch1_Out03
0V
Output indicator
COM1 (+V)
Short-circuit
protection
Circuit Configuration
Internal circuits
Short-circuit
protection
COM0 (+V)
Jxx_Ch1_Out04
to
Jxx_Ch1_Out07
0V
ERR indicator
• When overcurrent or line disconnection is detected, the ERR indicator will light, and the corresponding bit (two points per bit) in the Basic
I/O Unit Information Area (A050 to A069) will change to TRUE.
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
Signal
name
L
L
Jxx_Ch1_Out00
Jxx_Ch1_Out02
NC
0V
NC
External connection
and terminal-device
variable diagram
L
L
Signal
name
Connector pin *
Jxx_Ch1_Out04
Jxx_Ch1_Out06
NC
0V
A0
A1
A2
A3
A4
A5
A6
A7
A8
B0
B1
B2
B3
B4
B5
B6
B7
B8
Jxx_Ch1_Out01
Jxx_Ch1_Out03
L
L
NC
24 VDC
COM0 (+V)
NC
Jxx_Ch1_Out05
Jxx_Ch1_Out07
L
L
NC
24 VDC
COM1 (+V)
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed.
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
* Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on
the Units.
Note: Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O.
20
CJ1W-OC/OA/OD
CJ1W-OD204 Transistor Output Unit (8 Points)
Name
8-point Transistor Output Unit with Terminal Block (Sourcing Outputs)
Model
CJ1W-OD204
Rated Voltage
24 VDC
Operating Load
Voltage Range
20.4 to 26.4 VDC
Maximum Load
Current
0.5 A/point, 4.0 A/Unit
Leakage Current
0.1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
0.5 ms max.
OFF Response Time
1.0 ms max.
Load Short-circuit
Protection
Detection current: 0.7 to 2.5 A
Automatic restart after error clearance.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Number of Circuits
8 (8 points/common, 1 circuit)
Internal Current
Consumption
5 VDC, 100 mA max.
Fuse
None
External Power
Supply
20.4 to 26.4 VDC, 40 mA min.
Weight
120 g max.
Signal name
Circuit Configuration
Short-circuit
protection
Internal circuits
COM (+V)
Jxx_Ch1_Out00
to
Jxx_Ch1_Out07
0V
Output indicator
ERR indicator
• When overcurrent is detected, the ERR indicator will light, and the corresponding bit in the Basic I/O Unit Information Area (A050 to A069)
will change to TRUE.
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
Signal
name
External connection
and terminal-device
variable diagram
Signal
name
Connector pin *
L Jxx_Ch1_Out00 A0
L Jxx_Ch1_Out02 A1
L Jxx_Ch1_Out04 A2
L Jxx_Ch1_Out06 A3
NC
A4
NC
A5
NC
A6
NC
A7
0V
A8
B0
B1
B2
B3
B4
B5
B6
B7
B8
Jxx_Ch1_Out01 L
Jxx_Ch1_Out03 L
Jxx_Ch1_Out05 L
Jxx_Ch1_Out07 L
NC
NC
NC
NC
COM (+V)
24 VDC
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed.
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
* Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on
the Units.
Note: Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O.
21
CJ1W-OC/OA/OD
CJ1W-OD212 Transistor Output Unit (16 Points)
Name
16-point Transistor Output Unit with Terminal Block (Sourcing Outputs)
Model
CJ1W-OD212
Rated Voltage
24 VDC
Operating Load
Voltage Range
20.4 to 26.4 VDC
Maximum Load
Current
0.5 A/point, 5.0 A/Unit
Maximum Inrush
Current
0.1 mA max.
Leakage Current
1.5 V max.
ON Response Time
0.5 ms max.
OFF Response Time
1.0 ms max.
Load Short-circuit
Protection
Detection current: 0.7 to 2.5 A
Automatic restart after error clearance.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Number of Circuits
16 (16 points/common, 1 circuit)
Internal Current
Consumption
5 VDC, 100 mA max.
External Power
Supply
20.4 to 26.4 VDC, 40 mA min.
Weight
120 g max.
Signal name
Internal circuits
Circuit Configuration
Short-circuit
protection
COM (+V)
Jxx_Ch1_Out00
to
Jxx_Ch1_Out15
0V
Output indicator
ERR indicator
• When overcurrent is detected, the ERR indicator will light, and the corresponding bit in the Basic I/O Unit Information Area (A050 to A069)
will change to TRUE.
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
Connector
pin *
Signal
name
L
L
L
L
External connection
and terminal-device
variable diagram
L
L
L
L
Jxx_Ch1_Out00
Jxx_Ch1_Out02
Jxx_Ch1_Out04
Jxx_Ch1_Out06
Jxx_Ch1_Out08
Jxx_Ch1_Out10
Jxx_Ch1_Out12
Jxx_Ch1_Out14
0V
A0
A1
A2
A3
A4
A5
A6
A7
A8
B0
B1
B2
B3
B4
B5
B6
B7
B8
Signal
name
Jxx_Ch1_Out01
Jxx_Ch1_Out03
Jxx_Ch1_Out05
Jxx_Ch1_Out07
Jxx_Ch1_Out09
Jxx_Ch1_Out11
Jxx_Ch1_Out13
Jxx_Ch1_Out15
L
L
L
L
L
L
L
L
COM (+V)
24 VDC
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed.
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
* Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on
the Units.
22
CJ1W-OC/OA/OD
CJ1W-OD232 Transistor Output Unit (32 Points)
Name
32-point Transistor Output Unit with MIL Connector (Sourcing Outputs)
Model
CJ1W-OD232
Rated Voltage
24 VDC
Operating Load
Voltage Range
20.4 to 26.4 VDC
Maximum Load
Current
0.5 A/point, 2.0 A/common, 4.0 A/Unit
Leakage Current
0.1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
0.5 ms max.
OFF Response Time
1.0 ms max.
Load Short-circuit
Protection
Detection current: 0.7 to 2.5 A
Automatic restart after error clearance.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Number of Circuits
32 (16 points/common, 2 circuits)
Internal Current
Consumption
5 VDC 150 mA max.
External Power
Supply
20.4 to 26.4 VDC, 70 mA min.
Weight
80 g max.
Accessories
None
Short-circuit
protection
Signal name
COM0 (+V)
COM0 (+V)
Jxx_Ch1_Out00
to
Jxx_Ch1_Out15
Allocated
CIO word
Wd m
SW
Output indicator
Short-circuit
protection
Circuit Configuration
Internal circuits
0V
COM1 (+V)
COM1 (+V)
Jxx_Ch2_Out00
to
Wd m+1
Jxx_Ch2_Out15
0V
ERR indicator
• When overcurrent is detected, the ERR indicator will light, and the corresponding bit (bit allocated for each common) in the Basic I/O Unit
Information Area (A050 to A069) will change to TRUE.
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
23
CJ1W-OC/OA/OD
Connector pin
24 VDC
COM1 (+V)
0V
L
Wd m+1
L
Jxx_Ch2_Out15
Jxx_Ch2_Out14
L
Jxx_Ch2_Out13
L
Jxx_Ch2_Out12
L
L
L
L
Jxx_Ch2_Out11
Jxx_Ch2_Out10
Jxx_Ch2_Out09
Jxx_Ch2_Out08
COM0 (+V)
0V
External connection
and terminal-device
variable diagram
L
L
Wd m
L
L
L
L
L
L
1
2
3
4
5
6
7
8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
Allocated
CIO word
Signal
name
COM1 (+V)
0V
Jxx_Ch2_Out07
Jxx_Ch2_Out06
L
L
Jxx_Ch2_Out05
L
Jxx_Ch2_Out04
L
Jxx_Ch2_Out03
Jxx_Ch2_Out02
Jxx_Ch2_Out01
Jxx_Ch2_Out00
L
Wd m+1
Signal
name
L
L
L
COM0 (+V)
0V
Jxx_Ch1_Out15 25 26 Jxx_Ch1_Out07
Jxx_Ch1_Out14 27 28 Jxx_Ch1_Out06
Jxx_Ch1_Out13 29 30 Jxx_Ch1_Out05
Jxx_Ch1_Out12 31 32 Jxx_Ch1_Out04
Jxx_Ch1_Out11 33 34 Jxx_Ch1_Out03
Jxx_Ch1_Out10 35 36 Jxx_Ch1_Out02
Jxx_Ch1_Out09 37 38 Jxx_Ch1_Out01
Jxx_Ch1_Out08 39 40 Jxx_Ch1_Out00
L
L
L
L
L
Wd m
Allocated
CIO word
L
L
L
24 VDC
•
•
•
•
•
•
When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed.
Be sure to wire both terminals 21 and 22 (COM0 (+V)).
Be sure to wire both terminals 1 and 2 (COM1 (+V)).
Be sure to wire both terminals 3 and 4 (0 V).
Be sure to wire both terminals 23 and 24 (0 V).
The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
24
CJ1W-OC/OA/OD
CJ1W-OD262 Transistor Output Unit (64 Points)
Name
64-point Transistor Output Unit with MIL Connectors (Sourcing Outputs)
Model
CJ1W-OD262
Rated Voltage
12 to 24 VDC
Operating Load
Voltage Range
10.2 to 26.4 VDC
Maximum Load
Current
0.3 A/point, 1.6 A/common, 6.4 A/Unit
Maximum Inrush
Current
3.0 A/point, 10 ms max.
Leakage Current
0.1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
0.5 ms max.
OFF Response Time
1.0 ms max.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Number of Circuits
64 (16 points/common, 4 circuits)
Internal Current
Consumption
170 mA max. (5 VDC)
Fuse
None
External Power
Supply
10.2 to 26.4 VDC, 50 mA min.
Weight
110 g max.
Accessories
None
Signal
name
Allocated
CIO word
COM0
COM0
Circuit Configuration
Internal circuits
Output indicator
Indicator switch
Jxx_Ch1_Out00
to
Jxx_Ch1_Out15
0V
COM1
COM1
Jxx_Ch2_Out00
to
Jxx_Ch2_Out15
0V
COM2
COM2
Jxx_Ch3_Out00
to
Jxx_Ch3_Out15
0V
COM3
COM3
Jxx_Ch4_Out00
to
Jxx_Ch4_Out15
0V
Wd m
CN1 (OUT)
Wd m+1
Wd m+2
CN2 (OUT)
Wd m+3
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
25
CJ1W-OC/OA/OD
CN1
Jxx_Ch1_Out02
L
L
L
L
L
Jxx_Ch1_Out03
Jxx_Ch1_Out04
Jxx_Ch1_Out05
Jxx_Ch1_Out06
Jxx_Ch1_Out07
0V
COM0 (+V)
L
L
Wd m+1
External connection
and terminal-device
variable diagram
L
L
L
L
L
L
Jxx_Ch2_Out00
Jxx_Ch2_Out01
Jxx_Ch2_Out02
Jxx_Ch2_Out03
Jxx_Ch2_Out04
Jxx_Ch2_Out05
Jxx_Ch2_Out06
Jxx_Ch2_Out07
0V
COM1 (+V)
38 37
36 35
34 33
32 31
30 29
28 27
26 25
24 23
22 21
20 19
18 17
16 15
14 13
12 11
10 9
8 7
6 5
4 3
2 1
L
Jxx_Ch1_Out09
L
Jxx_Ch1_Out10
L
Jxx_Ch1_Out11
Jxx_Ch1_Out12
Jxx_Ch1_Out13
Jxx_Ch1_Out14
Jxx_Ch1_Out15
L
L
COM3 (+V)
0V
L
L
L
0V
COM0 (+V)
Jxx_Ch2_Out08
Jxx_Ch2_Out09
Jxx_Ch2_Out10
Jxx_Ch2_Out11
Jxx_Ch2_Out12
Jxx_Ch2_Out13
Jxx_Ch2_Out14
Jxx_Ch2_Out15
L
Jxx_Ch4_Out15
L
Jxx_Ch4_Out14
L
Jxx_Ch4_Out13
L
Jxx_Ch4_Out12
L
Jxx_Ch4_Out11
L
Jxx_Ch4_Out10
L
Jxx_Ch4_Out09
L
Jxx_Ch4_Out08
COM2 (+V)
L
0V
L
L
L
L
Allocated
CIO word
L
L
L
0V
COM1 (+V)
12 to
24 VDC
• When wiring, pay careful attention to the polarity of the external
power supply. The load may operate incorrectly if the polarity is
reversed.
• Be sure to wire both terminals 21 and 22 (COM0 (+V)) of CN1.
• Be sure to wire both terminals 1 and 2 (COM1 (+V)) of CN1.
• Be sure to wire both terminals 23 and 24 (0 V) of CN1.
• Be sure to wire both terminals 3 and 4 (0 V) of CN1.
• The signal names of the terminals are the device variable
names.The device variable names are the names that use "Jxx" as
the device name.
L
Jxx_Ch3_Out15
L
Jxx_Ch3_Out14
L
Jxx_Ch3_Out13
L
Jxx_Ch3_Out12
L
Jxx_Ch3_Out11
L
Jxx_Ch3_Out10
L
Jxx_Ch3_Out09
L
Jxx_Ch3_Out08
1 2
3 4
5 6
7 8
9 10
10 12
13 14
15 16
17 18
19 20
21 22
23 24
25 26
27 28
29 30
31 32
33 34
35 36
37 38
39 40
COM3 (+V)
0V
Jxx_Ch4_Out07
L
Jxx_Ch4_Out06
L
Jxx_Ch4_Out05
L
Jxx_Ch4_Out04
L
Jxx_Ch4_Out03
L
Jxx_Ch4_Out02
L
Jxx_Ch4_Out01
L
Jxx_Ch4_Out00
L
Wd m+3
L
40 39
Signal
name
COM2 (+V)
0V
Jxx_Ch3_Out07
L
Jxx_Ch3_Out06
L
Jxx_Ch3_Out05
L
Jxx_Ch3_Out04
L
Jxx_Ch3_Out03
L
Jxx_Ch3_Out02
L
Jxx_Ch3_Out01
L
Jxx_Ch3_Out00
L
Wd m+2
Jxx_Ch1_Out01
Connector
pin
12 to
24 VDC
12 to
24 VDC
Wd m+3
L
Jxx_Ch1_Out08
Signal
name
Allocated
CIO word
Wd m+2
L
Jxx_Ch1_Out00
Allocated
CIO word
Signal
name
Wd m
Connector pin
Signal
name
Wd m+1
Wd m
Allocated
CIO word
CN2
12 to
24 VDC
• When wiring, pay careful attention to the polarity of the external
power supply. The load may operate incorrectly if the polarity is
reversed.
• Be sure to wire both terminals 21 and 22 (COM2 (+V)) of CN2.
• Be sure to wire both terminals 1 and 2 (COM3 (+V)) of CN2.
• Be sure to wire both terminals 23 and 24 (0 V) of CN2.
• Be sure to wire both terminals 3 and 4 (0 V) of CN2.
• The signal names of the terminals are the device variable
names.The device variable names are the names that use "Jxx" as
the device name.
26
CJ1W-OC/OA/OD
Bit Allocations for Output Unit
8-point Output Unit
16-point Output Unit
Allocated CIO word
CIO
Bit
Wd m
(Output)
Signal name (CJ/NJ)
Wd m+1
(Output)
Signal name (CJ/NJ)
OUT0/Jxx_Ch1_Out00
00
OUT0/Jxx_Ch1_Out00
01
OUT1/Jxx_Ch1_Out01
01
OUT1/Jxx_Ch1_Out01
:
:
06
Wd m
(Output)
:
:
OUT6/Jxx_Ch1_Out06
14
OUT14/Jxx_Ch1_Out14
07
OUT7/Jxx_Ch1_Out07
15
OUT15/Jxx_Ch1_Out15
08
−
09
−
:
:
14
−
15
−
64-point Output Unit
Allocated CIO word
Wd m
(Output)
Bit
00
32-point Output Unit
CIO
Allocated CIO word
CIO
Bit
Signal name (CJ/NJ)
Allocated CIO word
CIO
Bit
Signal name (CJ/NJ)
00
OUT0/Jxx_Ch1_Out00
00
OUT0/Jxx_Ch1_Out00
01
OUT1/Jxx_Ch1_Out01
01
OUT1/Jxx_Ch1_Out01
:
:
14
Wd m
(Output)
:
:
OUT14/Jxx_Ch1_Out14
14
OUT14/Jxx_Ch1_Out14
15
OUT15/Jxx_Ch1_Out15
15
OUT15/Jxx_Ch1_Out15
00
OUT0/Jxx_Ch2_Out00
00
OUT0/Jxx_Ch2_Out00
01
OUT1/Jxx_Ch2_Out01
01
OUT1/Jxx_Ch2_Out01
:
:
14
15
Wd m+1
(Output)
:
:
OUT14/Jxx_Ch2_Out14
14
OUT14/Jxx_Ch2_Out14
OUT15/Jxx_Ch2_Out15
15
OUT15/Jxx_Ch2_Out15
00
OUT0/Jxx_Ch3_Out00
01
OUT1/Jxx_Ch3_Out01
Wd m+2
(Output)
Wd m+3
(Output)
:
:
14
OUT14/Jxx_Ch3_Out14
15
OUT15/Jxx_Ch3_Out15
00
OUT0/Jxx_Ch4_Out00
01
OUT1/Jxx_Ch4_Out01
:
:
14
OUT14/Jxx_Ch4_Out14
15
OUT15/Jxx_Ch4_Out15
27
CJ1W-OC/OA/OD
External Interface
8-point/16-point Units (18-point Terminal Blocks)
Model number label
I/O indicators
Connector
Connect to the connector on the next Unit.
Terminal block for
I/O wiring, 18P × 1
ERR
0
1
8
9 10 11 12 13 14 15
2 3
4 5
6
7
Note: The CJ1W-OD202, CJ1W-OD204, and CJ1W-OD212 also have an ERR indicator for the load short-circuit alarm.
32-point Units (Models with 40-point Fujitsu Connector or MIL Connector)
Model number
Indicator Switch
ID231
1
ID232
I/O indicators
2
Changes the 16 I/O displayed on the I/O indicators.
I/O wiring
connector
(40-pin × 1)
Unit with Fujitsu-compatible
Connector
Word m
or
m+1
ERR
0 1 2 3
4 5 6 7
8 9 10 11
12 13 14 15
Setting 1
Setting 2
MIL connector
Fujitsu connector
Bottom of connector
Wd m (Row A on connector)
Wd m+1 (Row B on connector) Top of connector
Unit with MIL Connector
Connector
Connected to the connector on the next Unit.
Note: Only the CJ1W-OD232 has an ERR indicator for the load short-circuit alarm.
28
CJ1W-OC/OA/OD
64-point Units (Models with Two 40-point Fujitsu Connectors or MIL Connector)
Indicator Switch
Model number
1
2
Changes the 32 I/O displayed on the I/O indicators.
ID261
ID261
I/O indicators
Setting 1
Setting 2
Wd m and m+1: CN1
Wd m+2 and m+3: CN2
I/O wiring
connector
(40-pin × 2)
Unit with MIL Connector
Unit with Fujitsu-compatible
Connector
Connector
Connected to the connector on the next Unit.
Word m or
m+2
I
Word m+1
or m+3
II
0
8
0
8
1
9
1
9
2
10
2
10
3 4 5 6 7
11 12 13 14 15
3 4 5 6 7
11 12 13 14 15
Wiring Basic I/O Units with Terminal Blocks
Electric Wires
The following wire gauges are recommended.
Terminal Block Connector
18-terminal
Wire Size
AWG 22 to 18 (0.32 to 0.82 mm2)
Crimp terminals
Use crimp terminals (M3) having the dimensions shown below.
6.2 mm max.
6.2 mm max.
29
CJ1W-OC/OA/OD
I/O Unit Wiring Methods
An I/O Unit can be connected to an external device by any of the following three methods.
1. User-provided Cable
An I/O Unit can be directly connected to an external device by using a connector.
A
B
A
User-provided cable
B
External device
C
Connector
C
2. Connector-Terminal Block Conversion Unit
Use a Connecting Cable to connect to a Connector-Terminal Block Conversion Unit.
Converting the I/O Unit connector to a screw terminal block makes it easy to connect external devices.
A
B
A
Connecting Cable for Connector-Terminal Block Conversion Unit
XW2Z
B
Connector-Terminal Block Conversion Unit
XW2R
C
Conversion to a screw terminal block
C
3. I/O Relay Terminal
Use a Connecting Cable to connect to an I/O Relay Terminal.
The I/O specifications can be converted to relay outputs and AC inputs by connecting the I/O Relay Terminal to an I/O Unit.
A
B
A
G79 I/O Relay Terminal Connecting Cable
B
G7@@ I/O Relay Terminals
Or, conversion to relay outputs and AC inputs.
B
30
CJ1W-OC/OA/OD
1. Using User-made Cables with Connector
Available Connectors
Use the following connectors when assembling a connector and cable.
32- and 64-point Basic I/O Units with Fujitsu-compatible Connectors
Applicable Units
Model
Specifications
CJ1W-OD231
Transistor Output Unit with Sinking Outputs, 32 outputs
CJ1W-OD261
Transistor Output Unit with Sinking Outputs, 64 outputs
Pins
40
Applicable Cable-side Connectors
Connection
Pins
OMRON set
Fujitsu parts
Solder-type
40
C500-CE404
Socket: FCN-361J040-AU
Connector cover: FCN-360C040-J2
Crimped
40
C500-CE405
Socket: FCN-363J040
Connector cover: FCN-360C040-J2
Contacts: FCN-363J-AU
Pressure-welded
40
C500-CE403
FCN-367J040-AU/F
32- and 64-point Basic I/O Units with MIL Connectors
Applicable Units
Model
Specifications
CJ1W-OD232
Transistor Output Unit with sourcing outputs, 32 outputs
CJ1W-OD262
Transistor Output Unit with sourcing outputs, 64 outputs
CJ1W-OD233
CJ1W-OD234
Transistor Output Unit with sinking outputs, 32 outputs
CJ1W-OD263
Transistor Output Unit with sinking outputs, 64 outputs
Pins
40
Applicable Cable-side Connectors
Connection
Pressure-welded
Crimped
Pins
OMRON set
DDK parts
40
XG4M-4030-T *1
FRC5-A040-3T0S
40
XG5N-401 *2
HU-40OS2-001
−
Crimp Contacts for XG5N *3
XG5W-0232 (loose contacts: 100 pieces)
XG5W-0232-R (reel contacts: 10,000 pieces)
HU-111S
*1. Socket and Stain Relief set.
*2. Crimp Contacts (XG5W-0232) are sold separately.
*3. Applicable wire size is AWG 28 to 24. For applicable conductor construction and more information, visit the OMRON website at
www.ia.omron.com.
Wire Size
We recommend using cable with wire gauges of AWG 28 to 24 (0.08 to 0.2 mm2). Use cable with external wire diameters of 1.61 mm max.
Crimping Tools
The following models are recommended for crimping tools and pressure-welding tools for Fujitsu connectors.
Tools for Crimped Connectors (Fujitsu Component)
Product Name
Model
Hand Crimping Tool
FCN-363T-T005/H
Contact Withdrawal Tool
FCN-360T-T001/H
Tools for Pressure-welded Connectors (Fujitsu Component)
Product Name
Hand Press
Model
FCN-707T-T101/H
Cable Cutter
FCN-707T-T001/H
Locator Plate
FCN-367T-T012/H
The following models are recommended for tools for OMRON MIL connectors.
Tools for Pressure-welded Connectors (OMRON)
Product Name
Model
Pressure-welding Tool
XY2B-0002
Attachment
XY2B-1007
Tools for Crimped Connectors (OMRON)
Product Name
Manual Crimping Tool
Model
XY2B-7007
31
CJ1W-OC/OA/OD
2. Connecting Connector-Terminal Block Conversion Units
Connection Patterns for Connector-Terminal Block Conversion Units
Pattern
Configuration
Number of Connectors
Connecting Cable
Connector-Terminal
Block Conversion Unit
A
1
34 terminals
Connecting Cable
Connector-Terminal
Block Conversion Unit
B
34 terminals
2
34 terminals
Combination of I/O Units with Connector-Terminal Block Conversion Units
Unit
CJ1WOD231
CJ1WOD232
CJ1WOD233
CJ1WOD234
I/O
capacity
32 outputs
32 outputs
32 outputs
32 outputs
Number of
connectors
1 Fujitsu
connector
1 MIL
connector
1 MIL
connector
1 MIL
connector
Polarity
NPN
PNP
NPN
NPN
Connection
pattern
A
A
A
A
Connecting
Cable
XW2Z-@@@B
XW2Z-@@@K
XW2Z-@@@K
XW2Z-@@@K
Connector-Terminal
Block
Conversion Unit
Wiring method
XW2R-J34G-C3
Phillips screw
XW2R-E34G-C3
Slotted screw (rise up)
XW2R-P34G-C3
Push-in spring
XW2R-J34G-C4
Phillips screw
XW2R-E34G-C4
Slotted screw (rise up)
XW2R-P34G-C4
Push-in spring
XW2R-J34G-C4
Phillips screw
XW2R-E34G-C4
Slotted screw (rise up)
XW2R-P34G-C4
Push-in spring
XW2R-J34G-C4
Phillips screw
XW2R-E34G-C4
Slotted screw (rise up)
XW2R-P34G-C4
Push-in spring
Common
terminals
No
No
No
No
XW2R-J34G-C3 (2 Units) Phillips screw
CJ1WOD261
64 outputs
2 Fujitsu
connectors
NPN
B
XW2Z-@@@B
(2 Cables)
XW2R-E34G-C3 (2 Units) Slotted screw (rise up)
No
XW2R-P34G-C3 (2 Units) Push-in spring
XW2R-J34G-C4 (2 Units) Phillips screw
CJ1WOD262
64 outputs
2 MIL
connectors
PNP
B
XW2Z-@@@K
(2 Cables)
XW2R-E34G-C4 (2 Units) Slotted screw (rise up)
No
XW2R-P34G-C4 (2 Units) Push-in spring
XW2R-J34G-C4 (2 Units) Phillips screw
CJ1WOD263
64 outputs
2 MIL
connectors
NPN
B
XW2Z-@@@K
(2 Cables)
XW2R-E34G-C4 (2 Units) Slotted screw (rise up)
No
XW2R-P34G-C4 (2 Units) Push-in spring
32
CJ1W-OC/OA/OD
Types of Connecting Cables
Appearance
Connectors
Model
XW2Z-050B
XW2Z-@@@B
One 40-pin Connector Made by Fujitsu Component, Ltd.
to One 40-pin MIL Connector
XW2Z-@@@K
Cable lenght [m]
0.5
XW2Z-100B
1
XW2Z-150B
1.5
XW2Z-200B
2
XW2Z-300B
3
XW2Z-500B
5
XW2Z-C50K
0.5
XW2Z-100K
1
XW2Z-150K
1.5
XW2Z-200K
2
XW2Z-300K
3
XW2Z-500K
5
One 40-pin MIL Connector to One 40-pin MIL Connector
3. Connecting I/O Relay Terminals
Connection Patterns for I/O Relay Terminals
Pattern
Configuration
Connecting Cable
I/O Relay Terminal
A
I/O Relay Terminal
I/O Relay Terminal
B
Connecting Cable
Combination of I/O Units with I/O Relay Terminal and Connecting Cables
Unit
CJ1W-OD231
CJ1W-OD232
I/O capacity
32 outputs
32 outputs
Number of
connectors
1 Fujitsu connector
1 MIL connector
Polarity
NPN
PNP
Connection
pattern
Number of
branches
Connecting Cable
I/O Relay Terminal
A
2
G79-O@C-@
G7TC-OC16
A
2
G79-O@C-@
G7TC-OC08
A
2
G79-O@C-@
G70D-SOC16
A
2
G79-O@C-@
G70D-FOM16
A
2
G79-O@C-@
G70D-VSOC16
A
2
G79-O@C-@
G70D-VFOM16
A
2
G79-O@C-@
G70A-ZOC16-3 and Relay
A
2
G79-O@C-@
G70R-SOC08
A
2
G79-O@C-@
G70D-SOC08
A
2
G79-I@-@-D1
G7TC-OC16-1
A
2
G79-O@-@-D1
G70D-SOC16-1
A
2
G79-O@-@-D1
G70D-FOM16-1
A
2
G79-O@-@-D1
G70A-ZOC16-4 and Relay
33
CJ1W-OC/OA/OD
Unit
CJ1W-OD233
CJ1W-OD234
CJ1W-OD261
CJ1W-OD262
CJ1W-OD263
I/O capacity
32 outputs
Number of
connectors
1 MIL connector
32 outputs
NPN
1 MIL connector
64 outputs
NPN
2 Fujitsu connectors
64 outputs
2 MIL connectors
64 outputs
Polarity
2 MIL connectors
NPN
PNP
NPN
Connection
pattern
Number of
branches
Connecting Cable
I/O Relay Terminal
A
2
G79-O@-@-D1
G7TC-OC16
A
2
G79-O@-@-D1
G7TC-OC08
A
2
G79-O@-@-D1
G70D-SOC16
A
2
G79-O@-@-D1
G70D-FOM16
A
2
G79-O@-@-D1
G70D-VSOC16
A
2
G79-O@-@-D1
G70D-VFOM16
A
2
G79-O@-@-D1
G70A-ZOC16-3 and Relay
A
2
G79-O@-@-D1
G70R-SOC08
A
2
G79-O@-@-D1
G70D-SOC08
A
2
G79-O@-@-D1
G7TC-OC16
A
2
G79-O@-@-D1
G7TC-OC08
A
2
G79-O@-@-D1
G70D-SOC16
A
2
G79-O@-@-D1
G70D-FOM16
A
2
G79-O@-@-D1
G70D-VSOC16
A
2
G79-O@-@-D1
G70D-VFOM16
A
2
G79-O@-@-D1
G70A-ZOC16-3 and Relay
A
2
G79-O@-@-D1
G70R-SOC08
A
2
G79-O@-@-D1
G70D-SOC08
B
2
G79-O@C-@
G7TC-OC16
B
2
G79-O@C-@
G7TC-OC08
B
2
G79-O@C-@
G70D-SOC16
B
2
G79-O@C-@
G70D-FOM16
B
2
G79-O@C-@
G70D-VSOC16
B
2
G79-O@C-@
G70D-VFOM16
B
2
G79-O@C-@
G70A-ZOC16-3 and Relay
B
2
G79-O@C-@
G70R-SOC08
B
2
G79-O@C-@
G70D-SOC08
B
2
G79-I@-@-D1
G7TC-OC16-1
B
2
G79-O@-@-D1
G70D-SOC16-1
B
2
G79-O@-@-D1
G70D-FOM16-1
B
2
G79-O@-@-D1
G70A-ZOC16-4 and Relay
B
2
G79-O@-@-D1
G7TC-OC16
B
2
G79-O@-@-D1
G7TC-OC08
B
2
G79-O@-@-D1
G70D-SOC16
B
2
G79-O@-@-D1
G70D-FOM16
B
2
G79-O@-@-D1
G70D-VSOC16
B
2
G79-O@-@-D1
G70D-VFOM16
B
2
G79-O@-@-D1
G70A-ZOC16-3 and Relay
B
2
G79-O@-@-D1
G70R-SOC08
B
2
G79-O@-@-D1
G70D-SOC08
Types of Connecting Cables
G79-O@C-@
G79-O@-@-D1
0.25m
Cable length
−
−
0.5m
−
G79-O50-25-D1
G79-I@-@-D1
−
G79-I50-25-D1
1.0m
G79-O100C-75
1.5m
G79-O150C-125
G79-O75-50-D1
−
G79-I75-50-D1
−
2.0m
G79-O200C-175
−
−
3.0m
G79-O300C-275
−
−
5.0m
G79-O500C-475
−
−
34
CJ1W-OC/OA/OD
Dimensions
(Unit: mm)
8-point/16-point Units (18-point Terminal Blocks)
CJ1W-OC201/ OC211/ OA201/ OD201 / OD202/ OD203/ OD204/ OD211/ OD213 / OD212
2.7
89
65
ID211
0
1
2
8
9
10 11 12 13 14 15
3
4
5
6
7
0
1
2
3
4
5
6
90
7
8
9
10
11
12
13
14
15
COM
COM
2.7
DC24V
7mA
31
32-point Unit (Output Units)
With Fujitsu-Compatible Connector (40-pin × 1)
CJ1W-OD231
(112.5)
2.7
66.5
65
ID231
0 1 2 3
4 5 6 7
8 9 10 11
12 13 14 15
0
1
1
2.7
DC24V 4.1mA
90
1
20
20
A
B
20
With MIL Connector (40-pin × 1)
CJ1W-OD232 / OD233 / OD234
2.7
83.6
65
ID231
0 1 2 3
4 5 6 7
8 9 10 11
12 13 14 15
0
1
2.7
DC24V 4.1mA
90
1ch
0ch
20
35
CJ1W-OC/OA/OD
64-point Units (Output Units)
With Fujitsu-Compatible Connector (40-pin × 2)
CJ1W-OD261
66.5
65
31
2.7
90
2.7
(112.5)
With MIL Connector (40-pin × 2)
CJ1W-OD262 / OD263
65
2.7
90
2.7
83.6
31
Related Manuals
Name
Cat. No.
Contents
CJ-series CJ2 CPU Unit Hardware User's Manual
CJ2H-CPU6@-EIP
CJ2H-CPU6@
CJ2M-CPU@@
W472
Describes the following for CJ2 CPU Units:
• Overview and features
• Basic system configuration
• Part nomenclature and functions
• Mounting and setting procedure
• Remedies for errors
• Also refer to the Software User’s Manual (W473).
CJ Series
CJ1H-CPU@@H-R, CJ1G/H-CPU@@H, CJ1G-CPU@@P,
CJ1G-CPU@@, CJ1M-CPU@@
Programmable Controllers Operation Manual
W393
Provides an outlines of and describes the design, installation, maintenance, and other
basic operations for the CJ-series PLCs.
W500
An introduction to the entire NJ-series system is provided along with the following
information on a Controller built with an NJ501 CPU Unit.
• Features and system configuration
• Introduction
• Part names and functions
• General specifications
• Installation and wiring
• Maintenance and inspection
Use this manual together with the NJ-series CPU Unit Software User's Manual (Cat. No.
W501).
NJ-series
CPU Unit Hardware User's Manual
NJ501-@@@@
36
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2014.9
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2014 All Right Reserved.